Appendix A: TV-VVTZC-E2 Points/Properties
TruVu™ VVTZC
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
129
•
Calibration
–
If needed, enter a
Calculated Value
by adding the
Calibration
to
the
Raw Value
for each ZS or wireless sensor.
D: 0 to 10
Combination Algorithm
–
If using more than one ZS or wireless sensor, select
how the enabled sensors' values are to be combined to determine the output
value. When the calculation is performed, only sensors with a valid value will be
included.
D:
R:
Average
Average
Maximum
Minimum
Input Smoothing
–
If the raw value from the sensor changes frequently, you can
select one of the following options to send out an average of several readings on
the output wire.
•
None
- The raw value
•
Minimum
- The average of the last 2 readings
•
Medium
- The average of the last 5 readings
•
Maximum
- The average of the last 9 readings
D:
R:
Medium
None
Minimum
Medium
Maximum
Show on sensors
–
Select
Local Value
to have each enabled sensor display its
individual sensed value, or
Calculated Value
to have each sensor display the
value determined by the
Combination Algorithm
.
D:
R:
Calculated Value
Calculated Value
Local Value
Display Resolution
–
Defines the resolution of the value to be displayed on the
sensor. For example, 1 displays only integers (e.g., 74) and 0.5 displays values to
the nearest 0.5 (e.g., 74.5).
D:
R:
1
1000
100
10
1
0.5
0.1
0.01
0.001
COV Increment
–
To reduce Rnet traffic, you can force the microblock to update
its output only when the sensed value changes by more than the COV Increment.
D:
R:
.1
0 to 100
Occupancy Contact State
- Current hardware state of the controller's
IN-04
input.
R: Open/Closed
Sensor Invalid
–
This internal input monitors the communication between the controller
and the SPT sensor.
Off
indicates communication is normal.
R: Off/On
Rnet Sensed Occupancy
–
Displays occupancy status detected by wireless infrared
motion sensor.
R: Off/On
Hot Water Valve
- The current value of the controller's
AO-01
output.
R: 0 to 100%
Smart Valve Cmd
–
The current value of the controller's output to the Smart Valve.
R: 0 to 100%
Heating Stage 1
- The current hardware state of the controller's
BO-01
output.
R: Off/On
Heating Stage 2
- The current hardware state of the controller's
BO-02
output.
R: Off/On
Fan S/S or EH 3
-
The current hardware state of the controller’s
BO-03
output. The
function of this output depends on the terminal type.
R: Off/On