Addressing the TV-MPCXP1628-NR
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
22
For the Open controllers connected to the TV-MPCXP1628-NR
•
BACnet MSTP Device Instance Number = BACnet MSTP Network yy
•
BACnet ARCNET Device Instance Number = BACnet ARCNET Network yy
•
BACnet MSTP Device Instance Name = the name "device" + Device Instance
•
BACnet ARCNET Device Instance Name = the name "device" + Device Instance
•
BACnet MSTP or ARCNET MAC Address = yy
•
BACnet MSTP Network Number = 161xx (learned from the router, defaults to 16101 if no TV-MPCXP1628-NR
is operating)
NOTES
•
Do not configure the rotary switches on the TV-MPCXP1628-NR to a number greater than 127 unless Port S1
is enabled for ARCNET. Doing so will not allow the i-Vu® server to discover the TV-MPCXP1628-NR.
If you change the TV-MPCXP1628-NR's switches or jumpers, you must cycle its power for the changes to take
effect.
•
If the BACnet automatic settings need to be changed, see
To communicate through the Local Access port
(page 69).
To set up BACnet Broadcast Management Devices (BBMDs)
If your system has multiple routers that reside on different IP subnets, you must set up one router on each IP
subnet as a BACnet/IP Broadcast Management Device (BBMD).