3–25
62-11637
3.18 STOPPING UNIT
NOTES:
• The system will close the compressor suction modulation valve (CSMV) and evaporator expansion valve
(EVXV) to 0% open before turning off.
• Due to internal processing, turning the START/RUN - OFF switch OFF then back to the START/RUN posi-
tion will result in a 4 to 50 second delay between the display going off and coming back on again.
3.19 OPTION - DataTrak
DataTrak allows remote communication with the APX control system (cellular, satellite, etc).
One Way Communication providers can request data from the System and transmit it via their equipment to
another location. This is typically done via the Internet to any destination in the world.
WARNING
!
APX control system equipped units may start automatically at any time the START/ RUN - OFF
switch is not in the OFF position. Also, the unit may be fitted with two way communication
equipment that will allow starting of the unit from a remote location even though the switch is
in the OFF position.
Two Way Communication providers can also send commands via their equipment to the control system to start or
stop the unit, change settings and the way the System is operating the unit.
DataTrak is an optional feature. The DataTrak option is generally factory installed, however it can be installed in
the field by inserting a DataTrak option USB memory device into the USB interface port and following the on-
screen instructions.
The DataTrak Option installation can be confirmed by scrolling through the Advanced User Unit Data (refer to
). DataTrak will be listed under the Installed Options heading if it is installed.
Once DataTrak is installed, the control system must be configured for the provider that will be connecting to it (refer
to
). The Satellite Com Configuration can be set for “Qualcomm” or “Other”. If the provider is “Qual-
comm” and the original Qualcomm TrailerTracs system is being used then the “Qualcomm” selection must be
made. If the provider is Qualcomm and the newer TrailerTracs T2 system is being used or another communica-
tions provider is used, the “Other” selection.
Carrier Transicold has worked with approved communication providers with recommended installation locations,
and wiring connections to Carrier units. Instructions for installing this equipment is supplied by each individual pro-
vider, and not by Carrier Transicold. Communications electrical harnesses are available from Carrier Transicold
Performance Parts Group (PPG).
OFF
START/RUN
O
I
CONTINUOUS
START/STOP
MENU
ALARM
DEFROST
COOL
DIESEL
START/STOP
STATUS OK
36
36
.2
BOX TEMPERATURE F
SETPOINT F
To stop the unit, place the
START/RUN-OFF switch in
the OFF position. The unit
will shutdown immediately
while the system completes
a shutdown sequence and
then the LCD display will go
blank.
The engine will stop and the
display will turn off.