7–59
62-11637
P00181
CHECK SV4 VALVE
• ACTIVATION: Suction pressure did not rise within range & discharge pressure did not drop within range
when SV4 was energized (opened).
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Auto reset if Pretrip is started again or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check for Alarms
Alarm conditions must be corrected and the alarm cleared to continue
2.
Check System Pressures
Check and compare compressor discharge & suction pressures with those shown in unit data. Refer
to
for instruction on comparison.
3.
Repair SV4. Refer to Section 8.9.6
Refer to
P00182
CHECK SV1 VALVE
• ACTIVATION: Discharge pressure did not decrease when SV1 was de-energized (opened) as expected in
Heat Pretrip, or discharge pressure did not increase as expected when SV1 was energized (closed) in
Cool Pretrip.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Auto reset if Pretrip is started again or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check for Alarms
Alarm conditions must be corrected and the alarm cleared to continue.
2.
Check System Pressures
Check and compare compressor discharge & suction pressures with those shown in unit data. Refer
to
for instruction on comparison.
3.
Check SV1. Refer to Section 8.9.5
Refer to SV1 Checkout Procedure in
P00186
CHECK EVAP OUTLET TEMP
• ACTIVATION: Evaporator Outlet Temperature Sensor (EVOT) is not within the range of -53 to +158°F (-47
to +70°C.)
• UNIT CONTROL: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
• RESET CONDITION: Auto reset if Pretrip is started again, or alarm may be manually reset via keypad or
by turning the unit off, then back on again.
CORRECTIVE ACTIONS:
1.
Check Sensor
Refer to procedure for alarm