Table 4–9 DataCORDER Pre-trip Result Records
Test
Title
Data
1-0
Heater On
Pass / Fail / Skip Result, Change in currents for Phase A, B and C
1-1
Heater Off
Pass / Fail / Skip Result, Change in currents for Phase A, B and C
2-0
Condenser Fan On
Pass / Fail / Skip Result, Water pressure switch (WPS) - Open /
Closed; Change in currents for Phase A, B and C
2-1
Condenser Fan Off
Pass / Fail / Skip Result, Change in currents for Phase A, B and C
3-0
Low Speed Evaporator Fan On Pass / Fail / Skip Result, Change in currents for Phase A, B and C
3-1
Low Speed Evaporator Fan Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
4-0
High Speed Evaporator Fan On Pass / Fail / Skip Result, Change in currents for Phase A, B and C
4-1
High Speed Evaporator Fan Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
5-0
Supply / Return Probe Test
Pass / Fail / Skip Result, STS, RTS, SRS and RRS
5-1
Secondary Supply Probe
(SRS) Test
Pass / Fail / Skip
5-2
Secondary Return Probe
(RRS) Test
Pass / Fail / Skip
6-0
Discharge Thermistor Test
Pass / Fail / Skip
6-1
Suction Thermistor Test
Pass / Fail / Skip
6-2
Discharge Pressure
Transducer Test
Pass / Fail / Skip
6-3
Suction Pressure
Transducer Test
Pass / Fail / Skip
6-4
Compressor Current Draw Test Pass / Fail / Skip
6-5
Compressor Leak Test
Pass / Fail / Skip
6-6
Economizer Valve Test
Pass / Fail / Skip
6-7
Digital Unloader Valve Test
Pass / Fail / Skip
6-9
Liquid Injection Valve Test
(If equipped)
Pass / Fail / Skip
6-10
Electronic Expansion Valve Test Pass / Fail / Skip
7-0
High Pressure Switch Closed
Pass / Fail / Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
7-1
High Pressure Switch Open
Pass / Fail / Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
8-0
Perishable Mode Heat Test
Pass / Fail / Skip Result, STS, time it takes to heat to 16°C (60°F)
8-1
Perishable Mode Pulldown Test Pass / Fail / Skip Result, STS, time it takes to pull down to 0°C (32°F)
8-2
Perishable Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER supply tempera
-
ture (SRS) over last recording interval.
9-0
Defrost Test
Pass / Fail / Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
10-0
Frozen Mode Heat Test
Pass / Fail / Skip Result, STS, time unit is in heat.
10-1
Frozen Mode Pulldown Test
Pass / Fail / Skip Result, STS, time to pull down unit to -17.8°C (0°F).
10-2
Frozen Mode Maintain Test
Pass / Fail / Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.
Содержание Transicold 69NT40-561-001
Страница 2: ......
Страница 4: ......
Страница 14: ......
Страница 22: ......
Страница 36: ......
Страница 92: ......
Страница 159: ...7 47 T 340...
Страница 163: ...8 3 T 340 Figure 8 2 Schematic Diagram for Standard Unit Configuration Based on Drawing 62 11271 Rev A...
Страница 169: ...8 9 T 340 Figure 8 8 Schematic and Diagram for Lower Vent Position Sensor VPS Option...
Страница 170: ...T 340 8 10 Figure 8 9 Unit Wiring Diagram for Standard Unit Configuration With 3 Phase Condenser Fan Motors...
Страница 172: ...T 340 8 12 Figure 8 10 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater...
Страница 173: ...8 13 T 340 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater Based on Drawing 62 66721...
Страница 174: ...T 340 8 14 Figure 8 11 Unit Wiring Diagram for Configuration With eAutoFresh and Emergency Bypass Options...
Страница 176: ......
Страница 180: ......
Страница 181: ......