7–33
T-340
13. Position sensor in unit (see
) and re-check sensor resistance.
).
NOTE
The P5 Pre-Trip test must be run to deactivate probe alarms (see
).
7.24.3
Sensors STS and SRS Reinstallation
To properly position a supply sensor, the sensor must be fully inserted into the probe holder mounting clamp. See
. Do not allow heat shrink covering to contact the probe holder. For proper placement of the sensor, be
sure to position the enlarged positioning section of the sensor against the side of the mounting clamp. This position
-
ing will give the sensor the optimum amount of exposure to the supply air stream, and will provide accurate tempera
-
ture readings to the controller.
Figure 7.19 Supply Sensor Positioning
1) Supply Air Stream
2) Insulation
3) Back Panel
4) Supply Sensor
5) Mounting Clamp
6) Sensor Wires
7) Drip Loop
8) Gasket Mounting Plate
9) Gasketed Support Plate
10) Gasketed Cover
11) TIR Bolts
12) STS Probe
13) SRS Probe
- - - - -
(2.5”)
Содержание Transicold 69NT40-561-001
Страница 2: ......
Страница 4: ......
Страница 14: ......
Страница 22: ......
Страница 36: ......
Страница 92: ......
Страница 159: ...7 47 T 340...
Страница 163: ...8 3 T 340 Figure 8 2 Schematic Diagram for Standard Unit Configuration Based on Drawing 62 11271 Rev A...
Страница 169: ...8 9 T 340 Figure 8 8 Schematic and Diagram for Lower Vent Position Sensor VPS Option...
Страница 170: ...T 340 8 10 Figure 8 9 Unit Wiring Diagram for Standard Unit Configuration With 3 Phase Condenser Fan Motors...
Страница 172: ...T 340 8 12 Figure 8 10 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater...
Страница 173: ...8 13 T 340 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater Based on Drawing 62 66721...
Страница 174: ...T 340 8 14 Figure 8 11 Unit Wiring Diagram for Configuration With eAutoFresh and Emergency Bypass Options...
Страница 176: ......
Страница 180: ......
Страница 181: ......