8.8 - Water exchanger pumps

The unit can control one evaporator water pump and one 

condenser water pump. The pump can be turned on only when 

this option is configured (PUMPCONF) and when the unit is in 

one of the “on” modes described in section 8.1 or in “delay” mode. 
The Touch Pilot control provides the signal to command the pump, 

but it does not include the protection of the pump itself (low water 

pressure, overload, etc.). 

8.8.1 - Pump operation

The pump keeps running for about 20 seconds after the unit goes 

to the stopping mode. The pump is turned off if the unit is shut 

down due to an alarm unless the fault is a freeze protection error. 

The pump can be started in particular operating conditions when 

freeze protection of the heat exchanger is active.
Since the minimum value for the delay at start-up is 1 minute 

(configurable between 1 and 15 minutes), the pump will run for at 

least one minute before the first compressor starts.
If configured, the cooler pump can be stopped when the unit is in 

Heating and the condenser pump can be stopped when the unit 

is in Cooling mode.

To set cooler pump behaviour in Heating mode OR condenser 

pump behaviour in Cooling mode

1.  Navigate to the Configuration menu.

2. Select 

Pump Configuration

 (PUMPCONF).

3. Set 

Cooler Pump Off In Heat 

[stopheat] or 

Cond Pump Off In 

Cool 

[stopcool] to “yes”.

Cooler Pump Off In Heat [stopheat]
Cond Pump Off In Cool [stopcool]

no/yes

yes

NOTE: The water pump can also be stopped when the unit is 

in Standby mode (see section 8.8.3).

8.8.2 - Pump protection (pump anti-stick function)

The control provides a means to automatically start the pump each 

day at 14:00 for 2 seconds when the unit is off. 
Starting the pump periodically for a few seconds extends the 

lifetime of the pump bearings and the tightness of the pump seal. 

To set pump sticking protection

1.  Navigate to the Configuration menu.

2. Select 

Pump Configuration 

(PUMPCONF).

3. Set

 Pump Sticking Protection

 [pump_per] to “yes”.

Pump Sticking Protection [pump_per]

no/yes

yes

8.8.3 - 

Standby pump (fixed speed pumps only)

The control provides the Eco pump functionality which allows for 

stopping the pump periodically when the unit is in satisfied mode 

(no cooling or heating is required). 
The Eco pump mode can be applied to the condenser pump when 

the unit is in Heating mode and the cooler pump when in Cooling 

mode.

To verify pump behaviour in Standby mode

1.  Navigate to the Main menu.

2. Select 

Miscellaneous Status 

(MSC_STAT).

3. Verify 

Eco Pump Mode Active 

[m_ecopmp].

Eco Pump Mode Active [m_ecopmp]

no/yes

yes

IMPORTANT: The Eco pump functionality can be enabled only 

by service technicians.

8.9 - Customer variable speed pump

As standard the unit provides the functionality to control a variable 

speed pump. It is possible to control the water flow to keep constant 

temperature difference on the evaporator water exchanger. 
Pump speed control may also be optimised by the installer 

(service-access level required).

The pump is turned on and off the same way that the fixed speed 

pump, excluding the situation when the water loop does not require 

production (the pump will be set to its minimum speed).

8.10 - Condenser water valve (option 152)

Saturated condensing temperature control is assured if the three-

way valve option is selected. The saturated condensing 

temperature is controlled based on a fixed setpoint that can be 

configured by the user via the SETPOINT table. The three-way 

valve control can be configured by the service department via the 

SERVICE table.

8.11 - Unit short cycling protection

The Touch Pilot control constantly monitors the control point which 

determines the operation of compressor(s). Compressors are 

turned on and off in order to maintain the required control point 

and satisfy the current cooling/heating demand. 
The control provides a protection that prevents the premature 

starting  of  compressors.  The  service-configured  temperature 

threshold (acting upon the control point) is used for compressor(s) 

control. 
This unit short cycling option can be enabled via the touch screen 

by setting the “short cycle management” parameter in the General 

Configuration menu (GEN_CONF) to “yes”.

8.12 - Refrigerant leak detection (option 159)

This option permits refrigerant leak detection. Two sensors (not 

supplied) that detect the refrigerant concentration in the air must 

be installed on the unit. 
If one of the two sensors detects an abnormal refrigerant level for 

more than one hour, an alarm is triggered (10050), without shutting 

the unit down. The refrigerant level and the time before triggering 

an alert are configurable. To modify them, contact Manufacturer 

Service Agency.

8.13 - Night mode

Night  mode  allows  users  to  configure  the  unit  to  operate  with 

specific  parameters  in  a  specific  time  period.  During  the  night 

period, the unit capacity is limited and the number of operating 

fans is reduced.

The night period is defined by a start time and an end time that 

are the same for each day of the week. The Night mode settings 

or the maximum capacity value can be configured in the General 

Configuration menu (GEN_CONF).

During the night period the condensing point is increased to limit 

the number of fans operating (units with dry cooler condensing 

control option). 

To set night mode settings

1.  Navigate to the Configuration menu.

2. Select 

General Configuration

 (GEN_CONF).

3.  Set night mode parameters.

Night Mode Start Hour [nh_start], Night Mode End Hour [nh_end]

00:00

Night Capacity Limit [nh_limit]

0 to 100% 

100%

8 - STANDARD CONTROL OPERATIONS AND OPTIONS

28

Содержание Touch Pilot Control Series

Страница 1: ...C O N T R O L S M A N U A L Original document Touch Pilot Control 19PV 550 1600 ...

Страница 2: ...tart stop 11 6 5 Display settings 12 6 6 Display language 12 6 7 System of measurement 12 6 8 User login 12 6 9 Password change 12 6 10 Main menu 13 6 11 Configuration menu 13 6 12 System configuration override 13 6 13 Schedule setting 14 6 14 Web connection 15 7 DETAILED MENU STRUCTURE 16 7 1 Main menu MAINMEN1 16 7 2 Configuration menu CONFIG1 22 7 3 Alarms menu 24 8 STANDARD CONTROL OPERATIONS ...

Страница 3: ...y offer for sale or contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 30 9 1 Control diagnostics 30 9 2 Current alarms 30 9 3 Alarms history 30 9 4 Resetting alarms 30 9 5 E mail notifications 30 9 6 Alarms description 31 10 MAINTENANCE 34 3 ...

Страница 4: ...nit IMPORTANT All screenshots of the user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information provided herein is solely for the purpose of allowing customers to operate and service...

Страница 5: ... in injury or product damage Apply all standard safety codes and practices Wear safety glasses and gloves Use the proper tools to move heavy objects Move units carefully and set them down gently 2 2 Safety precautions Only personnel qualified in accordance with IEC International Electrotechnical Commission recommendations may be permitted access to electrical components It is particularly recommen...

Страница 6: ...r of mechanisms that allow the unit to operate effectively including the following 7 inch touch screen BMS connection Oil free centrifugal compressor technology Diagnostics Web connectivity e mail transmission Cooling Heating control Dry Cooler Free Cooling control optional Condenser dry cooler control optional only LEN connector provided dry cooler installed separately 3 4 Operating modes Touch P...

Страница 7: ...l EXV evaporating pressure in heating mode and monitor suction pressure safeties related to the compressor operating envelope Suction pressure sensors are located on the suction piping of the circuit 4 5 Temperature sensors Temperature sensors constantly measure the temperature of various components of the unit ensuring the correct operation of the system Cooler entering leaving water temperature ...

Страница 8: ...switch 2 open open closed closed 4 HARDWARE DESCRIPTION Terminal block connections Description Board Connector Remarks On Off switch SIOB 1 DI 01 32 33 Used for the unit on off control Remote mode only open unit is Off closed unit is on Heat Cool Switch SIOB 1 DI 02 63 64 Used to switch between heating and cooling Remote mode only Demand Limit Switch 1 SIOB 1 DI 03 73 74 Used to control demand lim...

Страница 9: ...S Building Management System connection thanks to BACnet IP communication Legend 1 USB connector 2 Ethernet connector 3 Internal bus RS485 4 Internal bus RS485 5 Power supply connector 24 VAC 1 2 3 4 5 5 3 Touch Pilot buttons Home button Main Menu button Back button Home screen displayed Main Menu displayed Go back to the previous screen Login button Start Stop button Alarm button Basic access Uni...

Страница 10: ...e Time configuration Reset Configuration Schedule Menu Pump Configuration User Configuration Holiday Menu Configuration menu Main menu General Parameters Run Times Miscellaneous Status Setpoint Table Inputs Status Temperatures Modes DC Free Cooling Status Configuration Menu Outputs Status Pressures Air Condenser Status Pump Status Reset Alarms Alarm Historic Current Alarms Alarms menu 10 ...

Страница 11: ...not respond while reading the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The exit must be confirmed by pressing Save or Cancel HIGHER FORCE IN EFFECT Equipment controller rejects Force or Auto command Too many users connected Please try again later Too man...

Страница 12: ...ows users to add new languages to the control To learn more about language customization please contact your local service representative 6 7 System of measurement The control offers the possibility of selecting the system of measurement displayed on the user interface metric imperial To change a system of measurement Press the Login button to open User Login Screen Select the system of measuremen...

Страница 13: ...f user modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left part of the Synoptic screen and then find and press Configuration Menu Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down butt...

Страница 14: ...ine 7 Press the Save button to save your changes or the Cancel button to exit the screen without making modifications Legend 1 Selection of days for the time schedule 2 Start end of the schedule 3 Save 4 Cancel 5 Previous time period 6 Next time period Each program is in unoccupied mode unless a schedule time period is active If two periods overlap and are both active on the same day then the occu...

Страница 15: ...ntrol panel clear the Keep temporary files on my computer check box and use a direct connection IMPORTANT Two users can be connected simultaneously with no priority between them Note that the last modification is always taken into account 6 14 3 Technical documentation When the Touch Pilot control is used via a pc web browser the controller allows the user to access the technical documentation for...

Страница 16: ...us Pump status PUMPSTAT Miscellaneous Status Miscellaneous parameters status MSC_STAT Run Times Run times RUNTIME DC Free Cooling Status Dry Cooler Free Cooling status DCFC_STA Air Condenser Status Air Condenser status AIR_COND Setpoint Table Setpoint settings SETPOINT Configuration Menu Configuration menu CONFIG1 Displayed in English by default CAUTION Since specific units may not include additio...

Страница 17: ...e unit is in Network mode the minimum value will be used compared to the status of the external limit switch contact and the demand limit switch setpoint Displayed in English by default Temperatures Menu TEMP No Name Status Default Unit Displayed text Description 1 COOL_EWT C F Cooler Entering Fluid Evaporator entering water temperature Used for capacity control 2 COOL_LWT C F Cooler Leaving Fluid...

Страница 18: ...state circuit A 17 OFB_Fb open close open Contactor State Cir B Circuit Contactor state circuit B Displayed in English by default Outputs Status Menu OUTPUTS No Name Status Default Unit Displayed text Description 1 CP_A1_PW 0 to 100 0 Compressor A1 Load Compressor A1 load circuit A 2 CP_A2_PW 0 to 100 0 Compressor A2 Load Compressor A2 load circuit A 3 EXVPosA 0 to 100 0 EXV Position Circuit A EXV...

Страница 19: ...mmand 3 FLOW_SW open close open Cooler Flow Switch Cooler flow switch 4 HPUMP_1 off on off Condenser Pump Command1 Condenser pump control command 5 CONDFLOW open close open Condenser Flow Status Condenser flow switch Displayed in English by default Miscellaneous Status Menu MSC_STAT No Name Status Default Unit Displayed text Description 1 m_ecopmp no yes no Eco Pump Mode Active Eco pump mode activ...

Страница 20: ...FC Variable Fan Hours DCFC Variable speed fan Operating hours Displayed in English by default Air Condenser Status Menu AIR_COND No Name Status Default Unit Displayed text Description 1 oat C F Outdoor Air Temperature Outdoor air temperature 2 Dry Cooler Status Status of the Dry Cooler connected on the condenser side 3 DC_LWT C F Leaving Water Temp Leaving water temperature 4 DC_FanSt Runing Fan S...

Страница 21: ... change within one minute 5 hsp1 26 7 to 63 0 80 to 145 4 37 8 100 C F Heating Setpoint 1 Heating setpoint 1 used during occupied periods 6 hsp2 26 7 to 63 0 80 to 145 4 37 8 100 C F Heating Setpoint 2 Heating setpoint 2 used during unoccupied periods 7 hramp_sp 0 11 to 11 11 0 2 to 20 0 6 1 C F Heating Ramp Loading Heating ramp loading setpoint rate at which the water temperature may change withi...

Страница 22: ...o yes no Ramp Loading Select Ramp loading selection 5 off_on_d 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 6 lim_sel 0 to 2 0 Demand Limit Type Select Demand limit type 7 0 None 0 None 8 1 Switch Control 1 Switch control 9 2 4 20mA Control 2 4 20mA control 10 nh_start 00 00 00 00 Night Mode Start Hour Night mode start hour 11 nh_end 00 00 00 00 Night Mode End Hour Night mode end hour 1...

Страница 23: ...nser 10 dt_cr_no 0 to 13 9 0 to 25 0 0 C F Delta T No Reset Value Delta T no reset value 11 dt_cr_fu 0 to 13 9 0 to 25 0 0 C F Delta T Full Reset Value Delta T max reset value 12 v_cr_no 0 to 20 0 mA Current No Reset Value Current no reset value 13 v_cr_fu 0 to 20 0 mA Current Full Reset Value Current max reset value 14 spacr_no 10 to 51 7 14 to 125 10 14 C F Space T No Reset Value Space temperatu...

Страница 24: ...played in English by default Date Time Configuration Menu DATETIME No Name Status Default Unit Displayed text Description Date DD MM YYYY 1 d_of_m 1 to 31 Day of month Day of the month 2 month 1 to 12 Month of year Month 3 year 20nn Year Year 4 dow Monday Sunday Day of Week Day of the week Time HH MM 5 hour 0 to 24 h Hour Hour 6 minute 0 to 59 min Minute Minutes Daylight Saving Time 7 dlig_on no y...

Страница 25: ...the chiller state in the Network mode Command set to stop The unit is halted Command set to start The unit runs according to schedule 1 Remote start stop contact status Onoff_sw Start stop contact status can be used to control the chiller state in the Remote operating type Master control type ms_ctrl When the unit is the master unit in a two chiller master slave arrangement the master unit may be ...

Страница 26: ...ction is deactivated the setpoint schedule will be used again The following tables summarise the possible setpoint selections based on the control type local remote network and the following parameters Heating Cooling operating mode Setpoint select Setpoint selection contact status Schedule 2 status for setpoint selection 8 STANDARD CONTROL OPERATIONS AND OPTIONS Local operating mode Parameters st...

Страница 27: ...he difference between the lowest reset value no reset value and the highest possible reset value full reset value Cooling Heating Reset Deg Value represents the maximum possible reset Reset parameters i e slope reset and maximum value are configurable in the Reset Configuration menu RESETCFG Cooling mode Cooling control point reset is used to control the evaporator water temperature reset Heating ...

Страница 28: ... standard the unit provides the functionality to control a variable speed pump It is possible to control the water flow to keep constant temperature difference on the evaporator water exchanger Pump speed control may also be optimised by the installer service access level required The pump is turned on and off the same way that the fixed speed pump excluding the situation when the water loop does ...

Страница 29: ...8 4 2 for more information about reset control 8 16 Dry cooler free cooling option 313 19PV units may come with the free cooling option that enables the control of a Carrier dry cooler The chiller and the dry cooler have to be connected through a LEN RS 485 Units fitted with a dry cooler provide the free cooling functionality which means that the chilled water system directly exchanges heat using ...

Страница 30: ... alarms that occurred on the unit To access the alarm history 1 Press the Alarm button in the upper right part of the screen 2 Select Alarm Historic 3 The history of alarms will be displayed 9 4 Resetting alarms The alarm can be reset either automatically by the control or manually through the touch panel display or the web interface in the Reset Alarms menu The Reset alarms menu displays up to 5 ...

Страница 31: ...o normal 12002 Circuit B Discharge Transducer Failure As above Circuit B shuts down As above 12004 Circuit A Suction Transducer Failure As above Circuit A shuts down As above 12005 Circuit B Suction Transducer Failure As above Circuit B shuts down As above 12031 Circuit A Condenser Subcooling is negative Defective transducer or installation fault calculated condenser subcooling is negative No acti...

Страница 32: ...ter temperature sensors swapped Unit shuts down Manual 10098 Discharge pressure sensors swap Pressure sensors swapped Unit shuts down Manual 10099 Suction pressure sensors swap Pressure sensors swapped Unit shuts down Manual 10063 Circuit A Internal safety chain open HP Doors Power One of the high pressure switches is open electrical wiring issue door is open circuit breaker is open pressure is hi...

Страница 33: ...pressor Starting is taking too much time As above Compressor shuts down Automatic if the compressor is stopped xx38 Compressor Interlock discordance As above Compressor shuts down Manual xx39 Compressor Out of map info As above No action warning only Automatic xx90 Compressor Communication lost As above Compressor shuts down Automatic if communication is re established LEN Database modules failure...

Страница 34: ... no serious damage can occur to your equipment The Manufacturer provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The Maintenance contracts represent not only the best way to ensure the maximum operating life of your equipment but also through the expertise of qualified personnel the optimal tool to ma...

Страница 35: ......

Страница 36: ...rder No 10267 03 2018 Supersedes order No New Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union ...

Отзывы: