background image

4

3. Press MODE button once. The SET icon will come on. The

display now shows Option 07 setting.

4. Use up and down buttons to move between available

Option 07 choices of ON or OF. Factory default is OF.

5. Press MODE button again to return to Option 07. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 10 -- O (REVERSING VALVE) ON WITH HEAT
OR COOL SELECTION

This selection is only available on HP model thermostats when HP
is selected via Option 05. This selection determines whether the

reversing valve is energized in the heating or cooling mode.
Factory default is C, energized in cooling. Use up and down

buttons to change between H and C.

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 10.
3. Press MODE button once. The SET icon will come on. The

isplay now shows Option 10 setting.

4. Use up and down buttons to move between available

Option 10 choices of H (heat) or C (cool). Factory default is
C.

5. Press MODE button again to return to Option 10. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 13 -- ROOM TEMPERATURE OFFSET

This option allows calibration (or deliberate miscalibration) of
room temperature sensor. There are various reasons why the home

owner may want to have displayed temperature adjusted to a

higher or lower value. The selected number is the number of
degrees, plus or minus, which will be added to the actual

temperature. The number can range between --5 and +5. Factory
default is 0. This adjusted value will be used as actual temperature

for both display and control action. For example, if 2 is selected,

72

_

F/22

_

C actual will read 74

_

F/23

_

C. If setpoint is 72

_

F/22

_

C,

the room will control to an actual value of 70

_

F/21

_

C which will

be displayed and acted upon as if it were 72

_

F/22

_

C. The effect is

that a positive number selection will make the room temperature

lower and vice versa.

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 13. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 13 setting.

4. Use up and down buttons to move between available

Option 13 choices of --5 t5 in 1

_

steps. Factory

default is 0.

5. Press MODE button again to return to Option 13. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 15 -- AUTO MODE ON/OFF SELECTION

This options allows the installer to enable or disable AUTO mode

(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE

button are used to move between OFF, HEAT, and EHEAT (in heat
pump systems). Factory default is ON (AUTO mode enabled).

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 15. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 15 setting.

4. Use up and down buttons to move between available

Option 15 choices of ON or OF. Factory default is ON.

5. Press MODE button again to return to Option 15. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 18 -- BACKLIGHT CONFIGURATION

This function is only available when the thermostat is operating

from full power via R and C. It is not available when the

thermostat operates from batteries. In OF (off) mode, this function
is disabled. The thermostat backlight will normally be off. It turns

on with any button press and stays on for 10 seconds in between
button presses. In ON mode, this function is enabled. The

thermostat backlight will normally be on and dim in appearance.
The backlight becomes brighter with any button press and remains

bright for 10 seconds. Factory default is OF.

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 18. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 18 setting.

4. Use up and down buttons to move between available

Option 18 choices of ON or OF. Factory default is OF.

5. Press MODE button again to return to Option 18. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 19 -- EQUIPMENT PRESENT

This selection informs the thermostat of the heat, cool, and fan
capabilities of the installed equipment. Select number 2, 3, or 4.

Default is 4.
For equipment with heat and cool capability and fan selection,
choose 4.
For equipment with only heat or cool, but with fan selection,
choose 3.
For equipment with only heat or cool and no fan selection, choose

2.

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 19. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 19 setting.

4. Use up and down buttons to move between available

Option 19 choices of 2 through 4. Factory default is 4.

5. Press MODE button again to return to Option 19. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

OPTION 21 -- KEYPAD LOCKOUT

In OF (off) mode, the keypad is not locked out and has full

functionality. In ON mode, the keypad is locked out and the lock

icon on the display is illuminated. To unlock the keypad, the user
must press and hold the up and down buttons simultaneously for

approximately 5 seconds. The lock icon is turned off and the
keypad will remain unlocked as long as the user presses a button at

least every 30 seconds or for the entire duration of the installer test
mode. If keypad remains idle for 30 seconds and the installer test

mode is not in operation, the keypad will return to the locked state

and the lock icon will illuminate on the screen.

TC

SN

Содержание TCSNAC01

Страница 1: ...dels There are 2 different models The 5th and 6th letters of the part number indicate the model These 2 letters also appear on the package and on the circuit board Be sure to have the proper thermostat for the intended application Models are AC 1 stage cool 1 stage heat for AC systems only HP 1 stage cool 2 stage heat for either HP or AC with 2 stage heat Use each only for its intended purpose See...

Страница 2: ... 1 4 6mm of extra wire Strip only 1 4 6mm of insulation from each wire to prevent adjacent wires from shorting together when connected 8 Match and connect equipment wires to proper terminals of the connector blocks See Table 1 ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring or installation may damage the thermostat Che...

Страница 3: ...lable Option 02 values of OF and 1 through 9 Factory default is 2 5 Press MODE button again to return to Option 02 The SET icon will now be off 6 Use up and down buttons to select another Option or press FAN button to exit configuration mode OPTION 03 FAHRENHEIT CELSIUS SELECTION This option selects Fahrenheit or Celsius operation To Select 1 Enter configuration mode if not already there 2 Use up ...

Страница 4: ... not already there 2 Use up and down buttons to display Option 15 The SET icon should be off 3 Press MODE button once The SET icon will come on The display now shows Option 15 setting 4 Use up and down buttons to move between available Option 15 choices of ON or OF Factory default is ON 5 Press MODE button again to return to Option 15 The SET icon will now be off 6 Use up and down buttons to selec...

Страница 5: ...ree then first and second stages if a second stage exists will turn on for three minutes 4 If the mode is set to EHEAT auxiliary heat turns on for three minutes then the mode returns to OFF Terminating Installer Test After 15 minutes of inactivity no button presses by the installer thermostat will automatically revert to normal operation Pressing RESET FILTER any time during installer test will te...

Страница 6: ...ck the furnace into low heat operation and let O B control high heat operation Refer to indoor equipment Installation Instructions for proper setup 4 O B can control second stage heat Refer to indoor equipment Installation Instructions for proper setup 5 Refer to outdoor equipment Installation Instructions for latent kit requirements if any 6 Terminals marked with may not be present on equipment 7...

Страница 7: ...ashing the equipment is temporarily prevented from turning on by one of the timers see above While the icon remains on without flashing the equipment is on Power On Check When AC power is first applied all segments of the display are turned on for a few seconds Following this the temperature display indicates the model configuration via the following 2 digit code AC 1 speed air conditioner HP 1 sp...

Страница 8: ...10 W Morris St S Indianapolis IN 46231 Printed in China Edition Date 03 08 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No TCSNAC 01SI Replaces NEW TCSN ...

Страница 9: ... displayed when the cooling equipment is operating HEAT ON Indicator is displayed when the heating equipment is operating RESET FILTER Button restarts the timer that calculates the next air filter change or cleaning AUXILIARY HEAT Indicator is displayed when a heat pump system is operating with auxiliary heat air filter SETTING OPERATING THE THERMOSTAT Setting your indoor temperature set points 1 ...

Страница 10: ...reading on the LCD display means there is not enough voltage for the system to operate Contact your dealer for further information If the outdoor air temperature sensor is absent the outdoor temperature reading will be The batteries are low If the batteries are low the display will indicate a low battery signal on the thermostat Replace the batteries with two AA alkaline batteries NOTE If the prod...