SYSTXCCITW01--A, SYSTXCCITN01--A

& SYSTXCCITC01--A

Infinity

r

Touch Control

Installation Instructions

NOTE

: Read the entire instruction manual before starting the installation.

The features and functions outlined in the Installation Instructions reflect Version

13 software. See the Infinity Touch product page on the HVACPartner.com website
or the Downloads section of the www.MyInfinityTouch.Carrier.com website for the
latest software release and literature.
US Patents: Carrier

r

U.S. Pat No. 7,243,004, Carrier

r

U.S. Pat No. 7,775,452,

pointSET

t

U.S. Pat No. 7,415,102

Содержание SYSTXCCITN01-A Infinity

Страница 1: ...ures and functions outlined in the Installation Instructions reflect Version 13 software See the Infinity Touch product page on the HVACPartner com website or the Downloads section of the www MyInfini...

Страница 2: ......

Страница 3: ...e Zone 4 3 1 3 Enable Time Synchronization 4 3 2 Set Dealer Information 4 4 Installation 5 4 1 Overview 5 4 2 Check Equipment 6 4 3 Location 7 4 3 1 Wall Control 7 4 3 2 Remote Room Sensors 8 4 3 2 1...

Страница 4: ...Searching for Outdoor Unit 17 5 3 Indoor Evaporator Selection 18 5 4 Electric Heater Selection 18 5 4 1 Hydronic Heat Application 19 5 5 Searching SAM Module If Applicable 20 5 6 Searching for Zones...

Страница 5: ...1 2 Heat Cool Deadband 28 6 3 1 3 Offsets 29 6 3 1 4 Reset factory defaults 29 6 3 1 5 Scheduling Enable 29 6 3 1 6 Smart Recovery Enable 30 6 3 2 Fan Coil 30 6 3 2 1 Airflow 31 6 3 2 2 Altitude 32 6...

Страница 6: ...6 Altitude 38 6 3 3 7 Furnace Dehumidifier Drain 38 6 3 3 8 Furnace G Terminal 39 6 3 3 9 Furnace G Terminal Alert 39 6 3 3 10 Furnace G Terminal Alert Label 40 6 3 4 AC Heat Pump 40 6 3 4 1 Latching...

Страница 7: ...6 3 7 1 Freeze Limits 47 6 3 7 2 Lockout Count 47 6 3 7 3 Brownout Override 48 6 3 8 Zoning If Applicable 48 6 3 8 1 Zoning Disable 49 6 3 8 2 Zone Offsets 49 6 3 8 3 Zone Airflow Limits 49 6 3 8 4 Du...

Страница 8: ...ing 56 6 4 5 Heat Pump Heating 57 6 4 6 Heat Pump Cooling 58 6 4 7 Humidifier 58 6 4 8 Ventilator 59 6 4 9 Zoning If Applicable 59 6 4 9 1 Airflow Limits 59 6 4 9 2 Damper Sensor Check 59 6 4 9 3 Zone...

Страница 9: ...1 Service Phone Number 66 6 5 12 Energy Tracking 66 6 6 Refrigerant Charging Greenspeed 18VS 19VS Systems 67 6 6 1 Charging 68 6 6 2 Pump down 69 6 6 3 Evacuation 70 6 6 4 EXV Position 70 6 7 Dealer L...

Страница 10: ...warnings and cautions included in literature and attached to the unit Consult local building codes and the current edition of the National Electrical Code NEC NFPA 70 In Canada refer to the current e...

Страница 11: ...System communicating or a standard single stage 24VAC controlled outdoor unit may be used When using conventional single stage outdoor units the Infinity System furnace or fan coil provides the 24 vo...

Страница 12: ...screen touch MENU on the bottom of the control The TIME DATE icon will bring up the time and date menu A14215 3 1 1 Manually Adjust Time and Date d To set the HOUR MINUTE MONTH DAY or YEAR touch the f...

Страница 13: ...pable Infinity Touch wall controls after setting up the time zone the time synchronization can then be done after connection to the Internet server Both setting the time zone and enabling time synchro...

Страница 14: ...on the bottom of the Infinity Touch Control and follow the on screen prompts S More detailed information can be found on HVACPartners com under the Product tab Thermostats Controls SYSTXCCITW01 Docum...

Страница 15: ...rol according to this instruction S Install indoor unit outdoor unit and accessories according to their instructions S Wire complete system according to this instruction S Setup commission and operate...

Страница 16: ...user For accurate temperature measurement the following guidelines should be followed The Infinity Touch Control and Remote Room Sensors SHOULD be mounted S Approximately 5 ft 1 5 m from the floor S C...

Страница 17: ...e ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Touch Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor NOTE Humidi...

Страница 18: ...Touch control Only one Smart Sensor may be used per zone They cannot be averaged like Remote Room Sensors If a Smart Sensor is used in a zone a Remote Room Sensor may also be used in the same zone The...

Страница 19: ...that the following color code be used when wiring each device A Green Data A B Yellow Data B C White 24VAC Com D Red 24VAC Hot A B C D A03193 It is not mandatory that the above color code be used but...

Страница 20: ...es from existing control d Discard or recycle old control S NOTE Mercury is a hazardous waste if existing control contains any mercury it MUST be disposed of properly The Infinity Touch Control does n...

Страница 21: ...ment and device installation instructions for details S Turn on power to equipment 4 4 1 Shielded Wire If the thermostat wiring will be located near or in parallel with high voltage wiring radio TV or...

Страница 22: ...densation The cover must be installed to prevent damage from other sources Do not locate where it will be accessible to children It may be mounted in either vertical or horizontal position Remember th...

Страница 23: ...he backplate assembly snapped together care must be taken not to bend or break the interlocking tabs when removing 4 5 1 Decorative Backplate Sold separately a thin decorative backplate is available t...

Страница 24: ...ypass Humidifier A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals The Infinity Control Touch will automatically energize the HUM output during a call...

Страница 25: ...ommunicating variable speed furnace fan coil with a 2 stage air conditioner heat pump including HYBRID HEATr dual fuel system The process may vary for other types of systems See the Infinity System HV...

Страница 26: ...utdoor Unit The Infinity Touch Control will then proceed to communicate with the outdoor unit by displaying Searching for outdoor unit This includes Infinityr small packaged products SPP with Infinity...

Страница 27: ...h a variable capacity heat pump or an 18VS heat pump or 19VS air conditioner a screen will appear to select the installed indoor evaporator coil This selection is used to adequately calculate the refr...

Страница 28: ...kit should be installed in place of an electric heater See FE fan coil Product Data for accessory part number The system will self identify that hydronic heat has been installed during electric heate...

Страница 29: ...nce the latest version of the application specification entitled SAM Remote Access Application Specification ASCII Protocol Information available on HVACpartners com or the System Access Module Instal...

Страница 30: ...ext the installer will be prompted to select whether a humidifier is installed in the system Select YES or NO then touch NEXT 5 9 Ultraviolet Lights Installation Next the installer will be prompted to...

Страница 31: ...f water across the equipment at the expected highest delivered airflow If the blower RPM is greater than 1200 a warning will appear but equipment operation and the TrueSenset dirty filter detection op...

Страница 32: ...ctory default time is 1 00 p m but may be changed by entering the Zoning Setup menu see pages 45 47 If there is an active call for heating or cooling the system will wait until the call is satisfied b...

Страница 33: ...egisters After the duct assessment is complete touch NEXT A12186 6 Service Menu The Service menus contain a set of vital information This information enables the installer or service person to view a...

Страница 34: ...is under the display icon on the main menu A14220 6 1 Equipment Summary Touch EQUIPMENT SUMMARY to show indoor unit type and model number outdoor unit type and model number if a 2 stage unit filter ty...

Страница 35: ...can be done if duct modifications have been made since installation of the Infinity Touch wall control Duct assessment can be performed without performing a full system install A14222 NOTE For Small P...

Страница 36: ...installed the following options will be displayed See the Infinity System HVAC equipment Installation Instructions for more details as provided S Indoor d Furnace d Fan coil d PAC AC Indoor d PAC HP I...

Страница 37: ...nce the auto changeover option has been selected touch SAVE S Enable or Disable Choose to enable or disable auto changeover mode d Default Enable S Auto changeover time Adjustable from 5 to 120 minute...

Страница 38: ...m 5 to 5_F 3 to 3_C d Default 0_F S Humidity Adjustable from 10 10 d Default 0 6 3 1 4 Reset factory defaults This option allows the installer to reset certain factory parameters After the selections...

Страница 39: ...setpoints to those for the next programmed schedule period to help save energy during period transitions Smart Recovery will start recovery 90 minutes prior to schedule change in both heating and cool...

Страница 40: ...w is a fixed airflow used to achieve specified ratings no dehumidification airflow reduction is performed This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used The MAX airflow...

Страница 41: ...xisted at the start of or during the cooling cycle The Electric Reheat option enables the electric heat to be used while cool to dehumidify is running This will allow the cool to dehumidify function t...

Страница 42: ...is energized Use the alert function to select the contact state for an alert Select Normally Open or Normally Closed and then save your selection Shutdown shuts off fan and equipment when initiated A...

Страница 43: ...d then save your selection A13231 6 3 2 6 Fan Coil G Terminal Alert Label Once the G Terminal Alert label has been entered it is shown both on the main screen and in the notification email when the al...

Страница 44: ...airflow used to increase the output air temperature and provide increased comfort For the Low heat rise option set to ON if the system contains a bypass humidifier The ON setting will increase the fur...

Страница 45: ...e outdoor unit is used The EFF350 or EFF2 airflow is a fixed airflow used to achieve specified ratings no dehumidification airflow reduction is performed This is nominally 350 CFM ton but will vary if...

Страница 46: ...run the high stage of furnace heat NOTE Two stage furnace has LOW and HIGH selections only S Stages System Low Low Med Med Med High or High d Default System 6 3 3 4 Furnace Airflow Limits modulating f...

Страница 47: ...ructions for further details After the selection is made touch SAVE S Altitude 0000 2000 US 2001 3000 CN 2100 4500 US 3001 4000 US 4001 5000 US 5001 6000 US 6001 7000 US 7001 8000 US 8001 9000 and US...

Страница 48: ...VE S Function Disabled Fan or Shutdown d Default Disabled S Fan Speed Low Med or High d Default Low S Shutdown d Normally Open d Normally Closed d The shutdown function may not be immediate Blower off...

Страница 49: ...lection 6 3 3 10 Furnace G Terminal Alert Label Once the G Terminal Alert label has been entered it is shown both on the main screen and in the notification email when the alert becomes active A14224...

Страница 50: ...41 A14227 6 3 4 1 Latching High Cool Latch A13227 S System in Control d The system will decide which stage should be running to satisfy the cool ing demand S High Cool...

Страница 51: ...l decide which stage should be running to satisfy the heating demand S High Heat d Temperature below which only the high stage of heating will be energized S Only Low Heat d The system will only run i...

Страница 52: ...ting is only available with communicating outdoor units and with Cooling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units After the selection is made touch SAVE S L...

Страница 53: ...ion is made touch SAVE S Defrost Fan Delay Yes or No d Default No 6 3 4 8 Brownout Disable This option turns off the high voltage brownout detection function in the outdoor unit control After the sele...

Страница 54: ...ons are made touch SAVE A12149 S HP Lockout Adjustable from 20 to 55_F 28 to 13_C or None d Default None S Furnace Electric Heat or Hydronic Lockout Adjustable from 15 to 55_F 9 to 13_C or None d Defa...

Страница 55: ...46 A14228 6 3 7 Geo HP First touch SETUP then touch Geo HP to set up the parameters for the Geo HP unit A150178...

Страница 56: ...systems using untreated water and 15F is chosen for closed loop systems using glycol or other anti freeze solutions After the selection is made touch SAVE S Freeze Limits 26F or 15F d Default 26F A15...

Страница 57: ...brownout override function in the Geo HP unit After the selection is made touch SAVE S Brownout Override Active or Inactive d Default Inactive A150181 6 3 8 Zoning If Applicable First touch SETUP then...

Страница 58: ...Right buttons to change the zone After the selection is made touch SAVE S Temperature Offset Adjustable between 5 to 5_F 3 to 3_C d Default 0_F 6 3 8 3 Zone Airflow Limits Since a bypass damper is pro...

Страница 59: ...High or No Limit d Default High 6 3 8 4 Duct Assessment Time NOTE The daily duct assessment will occur even if static pressure monitoring is disabled This is done to ensure that the system will conti...

Страница 60: ...nstaller has the option of selecting pressure monitoring the type of filter installed and the time interval for cleaning After the selections are made touch SAVE S Pressure Monitoring not available or...

Страница 61: ...installer has the option of selecting whether ultraviolet lights are installed and the time interval for changing the ultraviolet lights After the selections are made touch SAVE S UV Lights Installed...

Страница 62: ...ressor section control board to the Utility connections Utility Saver is used to force the equipment to a lower stage low or off when activated by the utility company typically during peak load times...

Страница 63: ...as opened or closed registers This option allows the installer to select the airflow for the fan coil when paired with a hydronic coil After the selections are made touch SAVE A12194 S Airflow Select...

Страница 64: ...cised With self identifying electric heaters three stages of electric heat are available to be exercised in any combination Non identifying heaters will only provide one stage of heat After the select...

Страница 65: ...layed on the screen After the selections are made touch START S Hydronic heater check Selectable from 0 to 120 minutes d Default 5 minutes 6 4 4 Air Conditioning This option allows the air conditioner...

Страница 66: ...tage and time can be changed by pressing the Change button on the checkout status screen After the selections are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setti...

Страница 67: ...lections are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings To view airflows for normal air conditioning cooling...

Страница 68: ...pen all others will close and the indoor unit will provide the maximum airflow for that zone as selected in SETUP ZONING Airflow Limits If the airflow noise is objectionable the installer can select a...

Страница 69: ...s to change the zone under test This should be done with each zone to verify that the zone sensor corresponds to that particular zone Once each zone has been checked touch DONE to return to the ZONING...

Страница 70: ...utton labeled View Diagnostics which provides the top 3 most likely root causes for the most recent fault NOTE This feature is only available with compatible models Those models are currently the FE f...

Страница 71: ...about the furnace operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12198 6 5 4 AC Status The AC status screen displays relevant information about the AC oper...

Страница 72: ...t the heat pump operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12200 6 5 6 Geo HP Status The Geo HP status screen displays relevant information about the G...

Страница 73: ...xit the Service menus touch DONE A12201 6 5 8 Last 10 System Events This screen will show the last 10 events that occurred throughout the system Each entry has the time and date incident recorded Thes...

Страница 74: ...ed on the control The indoor unit and outdoor unit if communicating have the following histories To return to the previous screen touch BACK To exit the Service menus touch DONE S Resettable Faults Fa...

Страница 75: ...return to the previous screen touch BACK To exit the Service menus touch DONE A14230 6 5 11 Service Phone Number This menu item allows the installer to view the name and phone number that the homeowne...

Страница 76: ...screen touch BACK To exit the Service menus touch DONE A14231 6 6 Refrigerant Charging Greenspeed Intelligence 18VSt 19VSt Systems For variable capacity and multi stage heat pumps and AC units a refr...

Страница 77: ...n to verify the current total charge is accurate Once the installer has confirmed touch DONE Next the installer will enter the SERVICE VALVE SUBCOOL screen This screen will show the current liquid lin...

Страница 78: ...ture in _F outdoor temperature in _F compressor discharge pressure in psig and accumulator suction pressure in psig are displayed on this screen Once the stabilization time has expired touch DONE A142...

Страница 79: ...e after a brief delay 6 6 3 Evacuation Because this system has an EXV for the heating expansion device additional steps must be taken to open the EXV if the heat pump unit must be evacuated for servic...

Страница 80: ...Downloads Marketing Miscellaneous Infinity Touch Control Dealer Logo Application Instructions Touch DEALER LOGO to upload the dealer logo and contact information from a standard USB memory device con...

Страница 81: ...Download the program and follow the program instructions Once the dealer logo and contact information have been properly loaded onto the USB memory device insert the USB device into the bottom edge o...

Страница 82: ...the Infinity System to the Internet The model SYSTXCCITW01 wall control comes bundled with an Infinity Wireless Access Point This establishes an independent Infinity System Wi Fi network The model SY...

Страница 83: ...the user s computer network or mobile device with the Infinity Touch Control and or the MyInfinity web server with and the availability of the user s Internet service provider or mobile device carrie...

Страница 84: ...of the router access point After being selected it will be outlined in faint blue and indicated by a checkmark Then select NEXT A150175 S The selected network will show Choose an appropriate Wi Fi net...

Страница 85: ...ecurity key area and the keyboard will appear d Use the on screen keyboard to enter the Wi Fi network security key then touch NEXT S The control will inform you if the connection is successful If so t...

Страница 86: ...the connection to the MyInfinity web server has been established the status screen will show Connected for both Wi Fi and the server Connected Not Connected A13242 7 2 SYSTXCCITW01 A Models only To es...

Страница 87: ...D S Touch SETUP A WI FI CONNECTION to begin the process S Next touch SCAN FOR AVAILABLE ACCESS POINTS A12115 S Select the myHVACxxxxxx connection from the list then touch NEXT myHVAC is followed by th...

Страница 88: ...o the next screen to find myHVACxxxxxx A12116 S Use the on screen keyboard to enter the Wi Fi network security key then touch NEXT d Touch in the security key area and the keyboard will appear d The s...

Страница 89: ...control has connected to the network go to www MyInfinityTouch Carrier com to register the unit and begin remote access This requires the MAC address and serial number of the InfinityR Touch Wall Cont...

Страница 90: ...ontact your servicing dealer S When the connection to the MyInfinity web server has been established the status screen will show Connected for both the Wi Fi network and the server TP LINKr is a trade...

Страница 91: ...White Red OAT Sensor Optional Variable Speed Furnace Fan Coil NOTE Some outdoor units do not require the C and D connections See outdoor unit Installation Instructions NOTE For SPP products ABCD conne...

Страница 92: ...ommunicating AC Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM COM 24V Humidifier Connection Y Y2 S2 S1 OAT OAT Sensor Variable Speed Furnace Fan Coil A12354 Connection...

Страница 93: ...unicating HP Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM C Humidifier Connection Y S2 S1 W2 Y O C R O R W OAT OAT Sensor Variable Speed Fan Coil G A12355 Connection...

Страница 94: ...A B C D OAT Sensor Optional A B C D A B C D Damper Control module A B C D Indoor Unit Communicating AC or HP A04018 Zoning Connection for Communicating Indoor Unit with 2 Stage Communicating Outdoor...

Страница 95: ...een Yellow White Red OAT HUM COM 24V Humidifier Connection OAT Sensor A B C D A B C D Damper Control module A B C D Indoor Unit C Y 1 Stage AC Y Y2 A04019 Zoning Connection Diagram for Furnace or FE F...

Страница 96: ...reen Yellow White Red A B C D A B C D Damper Control module A B C D Variable Speed Fan Coil 1 Spd HP HUM C Y W2 Y O C R O R W OAT OAT Sensor Humidifier Connection G A07149 Zoning Connection diagram fo...

Страница 97: ...88 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...

Страница 98: ...89 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...

Страница 99: ......