54
FASTENER TORQUE VALUES
See Table 19 for torque values.
Table 19 — Torque Values
FASTENER LOCATIONS
TORQUE VALUES
Supply fan motor mounting
120 ± 12 in.-lb
Supply fan motor adjustment plate
120 ± 12 in.-lb
Motor pulley setscrew
72 ± 5 in.-lb
Fan pulley setscrew
72 ± 5 in.-lb
Blower wheel hub setscrew
72 ± 5 in.-lb
Bearing locking collar setscrew
65 to 70 in.-lb
Compressor mounting bolts
65 to 75 in.-lb
Condenser fan motor mounting bolts
20 ± 2 in.-lb
Condenser fan hub setscrew
84 ± 12 in.-lb