Guide specifications

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner 

unit suitable for ground or rooftop installation. Unit consists 
of a hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil 
or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of 

ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed 

in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have c-UL 
approval.

Unit cabinet will be capable of withstanding Federal Test 

Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.

Air-cooled condenser coils will be leak tested at 250 psig 

and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner 

unit. Contained within the unit enclosure is all factory 
wiring, piping, controls, compressor, refrigerant charge 
Puron®, and special features required prior to field start-up.

Refrigerant

Refrigerant will be Puron HFC refrigerant with zero ozone 

depletion potential. Puron is approved under the EPA’s 
Significant New Alternatives Policy (SNAP) Program.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Air-Cooled, Split-System

Air Conditioner

38TSA

2 to 3-1/2 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase 

type with class B insulation and permanently lubricated 
bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated 

steel wire safety guards.

Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 

bonded to copper tubes which are then cleaned, dehydrated, 
and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line 

shutoff valve with sweat connections, vapor-line shutoff 
valve with sweat connections, system charge of refrigerant 
Puron® (R-410A), and compressor oil.

Unit will be equipped with factory supplied TXV 

(Thermostatic Expansion Valve), high pressure switch, low 
pressure switch, and filter drier for Puron refrigerant.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at 

a suction temperature of _____ °F. The power consumption 
at full load will not exceed _____ kw.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of _____ Btuh or 
greater at conditions of _____ CFM entering air temperature 
at the evaporator at _____ °F wet bulb and _____ °F dry 
bulb, and air entering the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or 

greater at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, 

single phase, 60 hertz. The unit will be capable of 
satisfactory operation within voltage limits of _____ v
to _____ v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories 

and descriptions for specific features and available 
enhancements.

Содержание Puron 38TSA

Страница 1: ...ing systems as the traditional refrigerant R 22 has been Puron refrigerant is in service in thousands of systems providing highly reliable environmentally sound performance For specific R 22 phase out information see your Carrier distributor WeatherArmor III System The casingsteelisgalvanizedandcoatedwitha layer of zinc phosphate A modified polyester powder coating is then applied and baked on pro...

Страница 2: ... transmission to the rest of the system Application Versatility Carrier s systems utilizing Puron refrigerant have the same application guidelines as other systems Applications which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F 12 8 C are approved under Carrier s standard guidelines CarrierCoilsandFanCoilstoComplete ...

Страница 3: ...t Lb 290 290 293 294 COMPRESSOR Copeland Manufacturer Type Scroll REFRIGERANT Puron Control AccuRater Bypass Type Charge Lb 8 76 9 11 9 83 9 66 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 2400 2400 2800 2800 Motor HP 1 8 1 8 1 5 1 5 Motor RPM 825 825 825 825 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 18 25 18 25 18 25 18 25 Fins per In 20 20 20 20 Rows 2 2...

Страница 4: ...1LLS Liquid Line Solenoid Valve All Sizes KSASF0101AAA Support Feet All Sizes KAACF0801MED Coastal Filter All Sizes THERMOSTAT SUBBASE PKG DESCRIPTION TSTATCCNAC01 B Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCPAC01 B Thermostat Auto Changeover 7 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCPRH01 B Thermidistat Control Non Programmable Programmable The...

Страница 5: ...oller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil It is designed to cycle the outdoor fan motor in order to maintain condensing temperature within normal operating limits approximately 100 F 37 8 C high and 60 F 15 5 C low The control will maintain working head pressure at low ambient temperatures down to 0 F 17 8 C when properly install...

Страница 6: ...A Full Load Amps LRA Locked Rotor Arms MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 v on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Sound power dBA UNIT SIZE SERIES V PH OPER VOLTS COMPR FAN FLA MCA 60 C MIN WIRE SIZE 75 C MIN WIRE SIZE 60 C MAX LENGTH F...

Страница 7: ...roper airflow Minimum outdoor operating ambient in cooling mode is 55 F unless low ambient control is used max 125 F 2 Series designation is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 024 30 32 39 13 16 30 34 15 16 4 9 3 4 27 1 2 33 7 8 5 8 8 3 16 16 3 4 19 1 ...

Страница 8: ...ANF030 24 600 TDR TXV 14 00 14 00 12 15 FX4ANF036 25 000 TDR TXV 13 60 13 60 11 85 COILS 58MVP040 14 VARIABLE SPEED FURNACE CC5A CD5AW030 24 600 TDR TXV 14 50 14 50 12 60 CC5A CD5AW036 25 000 TDR TXV 15 00 15 00 13 15 CK5A CK5BW030 24 600 TDR TXV 14 50 14 50 12 75 CK5A CK5BW036 25 000 TDR TXV 15 00 15 00 13 20 COILS 58MVP060 14 VARIABLE SPEED FURNACE CC5A CD5AA036 25 000 TDR TXV 15 00 15 00 13 10 ...

Страница 9: ...14 00 12 15 FX4ANF036 29 600 TDR TXV 13 85 13 85 11 90 FX4ANF042 30 000 TDR TXV 13 60 13 60 11 90 COILS 58MVP040 14 VARIABLE SPEED FURNACE CC5A CD5AA042 30 000 TDR TXV 15 00 15 00 13 00 CC5A CD5AW030 29 000 TDR TXV 14 00 14 00 12 30 CD5AW036 29 600 TDR TXV 15 00 15 00 12 90 CK5A CK5BA042 30 000 TDR TXV 15 00 15 00 13 05 CK5A CK5BW030 29 000 TDR TXV 14 00 14 00 12 35 CK5A CK5BW036 29 600 TDR TXV 15...

Страница 10: ...2 10 CF5AA036 35 000 TXV 13 50 13 50 11 90 CF5AA048 36 000 TXV 13 80 13 80 12 00 CK3BA036 35 000 TXV 13 70 13 70 11 95 CK3BA042 35 600 TXV 13 70 13 70 11 95 CK3BA048 36 000 TXV 14 00 14 00 12 05 CK5A CK5BA036 35 000 TXV 13 70 13 70 11 95 CK5A CK5BA042 35 600 TXV 13 70 13 70 11 95 CK5A CK5BA048 36 000 TXV 14 00 14 00 12 05 CK5A CK5BN036 35 000 TXV 13 70 13 70 12 05 CK5A CK5BN042 35 600 TXV 13 70 13...

Страница 11: ...K5BA042 35 600 TDR TXV 15 00 15 00 13 10 CK5A CK5BA048 36 000 TDR TXV 15 00 15 00 13 20 CK5A CK5BW036 35 000 TDR TXV 15 00 15 00 13 05 COILS 58MVP120 20 VARIABLE SPEED FURNACE CC5A CD5AA042 35 600 TDR TXV 15 00 15 00 13 00 CC5A CD5AW048 36 000 TDR TXV 15 00 15 00 13 00 CD5AW036 35 000 TDR TXV 15 00 15 00 12 90 CK5A CK5BW036 35 000 TDR TXV 15 00 15 00 12 95 CK5A CK5BW048 36 000 TDR TXV 15 00 15 00 ...

Страница 12: ...NB006 42 000 TDR TXV 15 10 15 10 13 60 FV4ANF003 40 000 TDR TXV 14 30 14 30 12 65 FV4ANF005 41 500 TDR TXV 15 00 15 00 13 20 FX4ANB060 42 000 TDR TXV 13 50 13 50 11 95 FX4ANF042 40 000 TDR TXV 13 50 13 50 11 70 FX4ANF048 41 000 TDR TXV 13 60 13 60 11 90 COILS 58MVP040 14 VARIABLE SPEED FURNACE CC5A CD5AA042 40 000 TDR TXV 14 00 14 00 12 15 CC5A CD5AW048 41 000 TDR TXV 14 00 14 00 12 30 CK5A CK5BA0...

Страница 13: ...X060 42 000 TDR TXV 15 00 15 00 13 15 COILS 58MVP120 20 VARIABLE SPEED FURNACE CC5A CD5AA042 40 000 TDR TXV 14 50 14 50 12 55 CC5A CD5AA060 41 000 TDR TXV 14 50 14 50 12 60 CC5A CD5AW048 41 000 TDR TXV 14 50 14 50 12 60 CC5A CD5AW060 42 000 TDR TXV 15 00 15 00 12 95 CK3BA060 41 500 TDR TXV 14 50 14 50 12 95 CK5A CK5BA042 40 000 TDR TXV 14 50 14 50 12 55 CK5A CK5BA060 41 500 TDR TXV 14 50 14 50 12 ...

Страница 14: ...7 8 2 33 21 1 17 2 2 57 19 5 16 5 2 83 62 26 1 24 4 1 71 24 9 23 8 1 90 23 7 23 2 2 10 22 3 22 3 2 32 21 3 21 3 2 57 20 0 20 0 2 83 57 25 7 25 7 1 71 24 7 24 7 1 90 23 7 23 7 2 10 22 4 22 4 2 32 21 2 21 2 2 57 20 0 20 0 2 84 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5AA 024 0 96 1 0...

Страница 15: ...3 07 23 0 20 9 3 39 62 31 7 31 2 2 08 30 2 30 2 2 29 28 8 28 8 2 52 27 5 27 5 2 79 25 9 25 9 3 08 24 0 24 0 3 39 57 31 6 31 6 2 08 30 3 30 3 2 29 28 9 28 9 2 53 27 4 27 4 2 79 25 7 25 7 3 07 24 1 24 1 3 39 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 FX4ANF 030 0...

Страница 16: ... 3 34 57 30 7 30 7 2 03 29 4 29 4 2 24 28 1 28 1 2 47 26 6 26 6 2 74 25 0 25 0 3 02 23 5 23 5 3 34 1125 72 36 7 19 3 2 10 34 5 18 5 2 30 32 1 17 7 2 53 29 9 16 9 2 79 27 8 16 2 3 07 25 6 15 5 3 38 67 33 9 25 4 2 09 32 1 24 7 2 30 30 1 23 9 2 53 28 1 23 1 2 78 26 0 22 3 3 07 23 6 21 4 3 37 63 31 7 24 7 2 08 30 1 24 0 2 29 28 4 23 3 2 52 26 7 22 5 2 78 24 8 21 7 3 07 23 0 20 9 3 39 62 31 7 31 2 2 08...

Страница 17: ...6 30 3 30 3 3 70 27 9 27 9 4 07 57 37 7 37 7 2 48 36 1 36 1 2 74 34 4 34 4 3 04 32 5 32 5 3 36 30 4 30 4 3 71 28 0 28 0 4 08 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 1 00 1 00 FV4ANF 002 0 99 0 95 CC5A CD5AA 036 0 97 1 00 003 0 99 0 91 042 0 99 1 00 005 1 00 0 91 CC5A ...

Страница 18: ...33 2 19 1 3 70 30 5 18 2 4 08 67 40 5 29 9 2 48 38 5 29 1 2 74 36 3 28 3 3 04 33 9 27 4 3 36 31 4 26 4 3 71 28 5 25 3 4 08 63 37 9 29 1 2 48 36 0 28 3 2 74 33 9 27 4 3 04 31 7 26 4 3 36 29 3 25 4 3 70 26 6 24 3 4 06 62 37 8 36 8 2 48 36 1 35 8 2 74 34 3 34 3 3 04 32 4 32 4 3 36 30 3 30 3 3 70 27 9 27 9 4 07 57 37 7 37 7 2 48 36 1 36 1 2 74 34 4 34 4 3 04 32 5 32 5 3 36 30 4 30 4 3 71 28 0 28 0 4 0...

Страница 19: ... 5 42 5 3 21 40 5 40 5 3 55 38 3 38 3 3 92 35 9 35 9 4 34 33 6 33 6 4 80 57 44 6 44 6 2 90 42 6 42 6 3 21 40 6 40 6 3 55 38 4 38 4 3 93 36 0 36 0 4 34 33 7 33 7 4 80 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 0 95 1 00 FV4ANB 006 1 00 0 91 060 0 99 1 00 FV4ANF 003 0 95 0...

Страница 20: ...36 3 29 6 4 27 33 6 28 6 4 72 63 44 2 33 0 2 83 41 9 32 0 3 14 39 6 31 0 3 47 37 1 30 0 3 85 34 5 28 8 4 25 32 0 27 8 4 71 62 43 8 41 5 2 83 41 7 40 5 3 13 39 5 39 3 3 47 37 4 37 4 3 85 35 2 35 2 4 26 33 0 33 0 4 72 57 43 3 43 3 2 82 41 5 41 5 3 13 39 5 39 5 3 47 37 5 37 5 3 85 35 2 35 2 4 27 33 1 33 1 4 73 1575 72 51 1 27 0 2 95 48 3 26 0 3 26 44 5 24 7 3 58 41 8 23 8 3 95 38 5 22 7 4 35 35 5 21 ...

Страница 21: ...127 0 2 64 18 8 136 0 2 96 40 TCG SDT KW 32 9 69 8 1 29 31 2 79 4 1 46 29 5 89 1 1 65 27 8 98 7 1 86 26 0 108 0 2 09 24 3 118 0 2 36 22 5 127 0 2 65 20 6 137 0 2 97 45 TCG SDT KW 36 0 71 1 1 30 34 1 80 7 1 47 32 2 90 2 1 66 30 4 99 8 1 87 28 5 109 0 2 10 26 6 119 0 2 37 24 7 128 0 2 66 22 6 138 0 2 98 50 TCG SDT KW 39 2 72 4 1 32 37 2 82 0 1 48 35 2 91 5 1 67 33 2 101 0 1 88 31 1 111 0 2 12 29 1 1...

Страница 22: ... further consideration For buried lines longer than 3 ft consult your local distributor 8 Use only copper wire for electric connection at unit Aluminum and clad aluminum are not acceptable for the type of connector provided 9 Do not apply capillary tube indoor coils to these units 10 Factory supplied filter drier must be installed 11 Do not deviate from factory supplied TXV s and Liquid Line Solen...

Страница 23: ...23 Typical installation A98600 AIR CLEANER FURNACE FURNACE COIL AIR CONDITIONER COMFORT VENTILATOR HUMIDIFIER COMFORT ZONE II CONTROL CENTER ...

Страница 24: ...P Program Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TSA 2 to 3 1 2 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts wil...

Отзывы: