38GLS…G / 38YL-…G Puron

GB - 7

E N G L I S H

Gas line (large diameter)

Liquid line (small diameter)

Flare nut

Indoor unit

Outdoor unit

Vacuum pump

Three-way valve

Needle valve

Valve cap

Valve needle

Two-way valve

Allen (hex. head) wrench

Refrigerant connections

Pipe

Pipe insulation

Fastening tape

Air purging

Use only a vacuum pump to purge air from the piping.

NEVER use the system compressor as a vacuum pump.

NEVER use the unit refrigerant gas to purge the connecting
pipes.

No additional refrigerant has been provided in the unit for this
purpose.
Remove the caps from the two and three-way valves.
Create a vacuum with a vacuum pump connected to the service
connection of the suction shut-off valve, as shown, keeping the
shut-off valves completely shut until a 50 Pa (0.5 mbar) vacuum
has been reached.
Now open the two-way valve for 3 sec., then quickly shut it to check
for possible leaks.
After the leak check, fully open the two and three-way valves.
Replace caps and check for leaks.

Cooling (2)

Maximum conditions

outdoor temperature 43

°

C

indoor temperature 32

°

C d.b.; 23

°

C w.b.

Minimum conditions

outdoor temperature 15

°

C (4)

indoor temperature 21

°

C d.b.; 15

°

C w.b.

Heating (3)

Maximum conditions

outdoor temperature 24

°

C d.b.; 18

°

C w.b.

indoor temperature 27

°

C d.b.

Minimum conditions

outdoor temperature –15

°

C d.b.; –17

°

C w.b.

Mains power supply

Nominal single-phase voltage

230V ~ 50Hz

Operating voltage limits

min. 198V – max. 264V

Table III: Operating limits 

(1)

WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.

Notes:

1. Data referred to the outdoor unit only.
2. According to ISO 5151.2/T1.
3. According to ISO 5151.2/High+.
4. 38GLS units are provided with head pressure control

suitable up to –15

°

C ambient temperature (size 07 and 09

up to –5

°

C).

d.b. - dry bulb w.b. - wet bulb

Once all connections have been completed, check for leaks by
using a leak detector specific for HFC refrigerants.
Finally wrap the valves and pipes with anti-condensate insulation
and tighten this with tape, without exerting too much pressure on
the insulation.
Repair and cover any possible cracks in the insulation.
Fix the pipes to the wall with hooks or conduits.

Содержание Puron 38GLS-07G-703EC-40

Страница 1: ...38GLS G 38YL G 001 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E ISO9001 INSTALLATION MANUAL ...

Страница 2: ... before it enters in the unit R 410A as other HFCs is only compatible with oils selected by the compressor manufacturer A vacuum pump is not enough to remove moisture from oil POE oils absorb moisture rapidly Do not expose oil to atmosphere Never open system to atmosphere while it is under vacuum When the system must be opened for service break vacuum with dry nitrogen and replace filter driers Do...

Страница 3: ... 3 1 2 햲 Outdoor unit 햳 Indoor unit 햴 Height Connections Model 07 09 12 18 24 Max height difference 5 m 5 m 10 m 15 m Max pipe length 15 m 15 m 30 m 40 m Minimum nom thickness Pipe diameter Minimum nominal inches mm thickness mm 1 4 6 35 0 80 3 8 9 52 0 80 1 2 12 77 0 80 Table II Connections 3 1 2 07 9 52 6 35 3 8 1 4 09 12 12 77 6 35 1 2 1 4 18 24 12 77 6 35 1 2 1 4 Pipe diameter Gas Liquid Sucti...

Страница 4: ...15 Cooling only 09 545 6 15 50 Cooling only 12 565 8 15 Cooling only 18 1090 8 15 Cooling only 24 1265 8 15 220 150 Heat pump 07 610 6 15 Heat pump 09 725 6 15 Heat pump 12 705 8 15 50 Heat pump 18 1530 8 15 Heat pump 24 1900 8 30 220 150 Mod 07 09 12 18 24 A mm 50 50 50 50 100 B mm 100 100 250 250 250 C mm 400 400 400 500 500 D mm 50 50 50 50 50 E mm 670 670 670 470 470 F mm 400 400 400 400 400 ...

Страница 5: ...lated seamless refrigeration grade pipe only Cu DHP type according to ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used After installation thoroughly test the system operation and explain all system functions to the owner Leave this manual with the owner f...

Страница 6: ... to get wet before connection Disconnecting the refrigerant connections after installation this will cause refrigerant leaks Connecting the condensate drain pipe to the outdoor unit Predominant head winds Multiple unit installation with units facing each other Insulating the connecting pipes only partially which will cause dripping Dripping into passageways Any obstruction of the unit air outlet a...

Страница 7: ...5 Flaring the ends of the tubing Remove protective caps from copper tube ends Position tube end downward cut the tube to the requested length and remove the burrs with a reamer Do not leave system open to atmosphere any longer than minimum required for installation Oil in the compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed during installation The maximu...

Страница 8: ... d b 23 C w b Minimum conditions outdoor temperature 15 C 4 indoor temperature 21 C d b 15 C w b Heating 3 Maximum conditions outdoor temperature 24 C d b 18 C w b indoor temperature 27 C d b Minimum conditions outdoor temperature 15 C d b 17 C w b Mains power supply Nominal single phase voltage 230V 50Hz Operating voltage limits min 198V max 264V Table III Operating limits 1 WARNING During heat p...

Страница 9: ...fuse or circuit breaker see table V Electrical data 햲 햳 햲 햳 IMPORTANT use a separate bipolar wire to connect S1 and S2 terminals Terminal box legend all models Earth L Live power supply N Neutral power supply R Live connection indoor outdoor unit C Neutral connection indoor outdoor unit Y Compressor interlocking contact O Reversing valve control Heat pump only W2 Outdoor fan signal Heat pump only ...

Страница 10: ... Unit is suitable for outdoor installation 2 Starting current duration is usually lower than 1 sec 3 Wire size shown applies to line length up to 15 m 4 If the indoor unit is provided with an electric heater consult indoor unit installation manual for correct sizing of the wires 5 Data referred to the outdoor unit only 6 The mains supply connecting cable must be H07 RN F type or higher synthetic r...

Страница 11: ...dry bulb temperature C 햴 Evaporator entering wet bulb temperature C R 410A refrigerant cylinders contain a dip tube which allows liquid refrigerant to flow from the cylinder in an upright position Charge R 410A units with cylinder in upright position and a commercial type metering device in manifold hose in order to vaporize the liquid refrigerant before it enters in the unit Charge refrigerant in...

Страница 12: ...ing for heat pump models only Energize the system by putting the main switch to ON without starting the unit Remote control must be in the OFF position Do not disconnect the main switch during the unit operating season Check the refrigerant charge and unit maintenance Refrigerant charge control Heat pump unit Cooling only unit Cooling cycle Heating cycle Gas Liquid Gas Liquid Te Ta 2 4 5 6 7 7 8 1...

Страница 13: ...ump operation faulty replace Refrigerant charge too high drain some refrigerant see note 1 Air or other non condensable gases in the circuit drain refrigerant see note 1 evacuate and recharge Discharge pressure too low Refrigerant charge too low add refrigerant Outdoor coil dirty or obstructed clean or remove obstructions Indoor unit air filter dirty clean filter Suction pressure too high Internal...

Страница 14: ...40 40GKX018 703IJ 40 Cassette 42VKX018 703IJ 40 Console 38GLS 24G 703EC 40 42HWX024 703IN 40 Hi Wall 40GKX024 703IJ 40 Cassette 42VKX024 703IJ 40 Console Heat Pump Models Outdoor unit Indoor unit 38YL 09G 703EJ 40 42HWS09G 703IJ 40 Hi Wall Accessories and IMQ certification Table V Accessoires Description Part number 38GLS G 38YL G 07 09 12 18 24 07 09 12 18 24 Wall bracket kit 38YL 900 002 40 앬 앬 ...

Страница 15: ...motor pressure sensor and interface relay The head pressure controller allows operation in cooling mode up to 5 C mod 007 009 and 10 C mod 012 018 024 ambient temperature keeping the condensing temperature always above 41 C 42 C The HPC automatically feels the possible heating mode working allowing in this case the outdoor unit fan motor to operate at full speed high LRPS Loss of refrigerant press...

Страница 16: ...ondensing pressure is above the high pressure limit the fan operates at high speed Low speed If the condensing pressure is below the low pressure limit the fan operates at low speed Hard start At each compressor starting the fan motor high speed is reached by the pressure sensor operation Head pressure controller wiring diagram Pressure setting High speed pressure set at 2323 kPa 23 2 bar 337 psig...

Страница 17: ...uit board PCB bare with insulation coating quick connection terminals Heat Pump select terminal The head pressure controller allows operation in cooling mode up to 15 C ambient temperature keeping the condensing temperature always above 41 C 42 C The HPC automatically feels the possible heating mode working allowing in this case the outdoor unit fan motor to operate at full speed LRPS Loss of refr...

Страница 18: ...o the motor is 97 or more of supply voltage Low voltage If the liquid line temperature is below set point minus half the proportional band the output voltage to the motor is fixed to 125V Hard start At each compressor starting the full voltage output to the fan motor is provided for 3 seconds Proportional band The controller directly senses the changes in liquid line temperature and varies the out...

Страница 19: ...io 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 13895 74M10 February 2001 Supersedes Order No 13895 74M10 July 2000 Printed in Italy ...

Отзывы: