background image

TO SELECT:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 13.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between -5 and +5 in 1°

steps on large display. Factory default is 0.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 15—Enable Auto Mode

This option allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE
button are used to move between OFF, HEAT, COOL, and
EHEAT (in heat pump systems). Factory default is ON (AUTO
enabled).

TO SELECT:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 15.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up or down button to move between ON and OF on large

display. Factory default is ON (AUTO enabled).

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option or press END to exit
configuration mode.

Step 5—Check Thermostat Operation

Before doing the checkout, press HOLD button to turn on HOLD
icon, locking the thermostat in hold mode. This will assure set
points do not change during the checkout. Outputs for each stage
of operation are listed in Table 2.

TO TEST FAN:

1. Press FAN button. Fan ON icon and the G output will go on

within a few seconds, causing fan to operate.

2. Pressing FAN button again will turn off the G output and turn

on Fan AUTO icon.

TO TEST COOLING:

Press MODE button until COOL icon under it turns on. Press
down button until cool set point (upper right 2 digit display with
COOL now flashing under it) is 2° or 3° below room temperature.
This will create a cooling demand. A small triangle to the left of
this COOL icon will flash or come on continually. Flashing means
the equipment is going to turn on but is presently being held off by
a system timer. (See "Operational Information" on page 11 for
timer descriptions.) Defeat timer by pressing UP and FAN buttons
together. This will make the triangle stay on and turn cooling
equipment on. To turn off, raise cooling set point above room
temperature. The cooling and the triangle will turn off within a few
seconds.

If system has a 2-speed compressor, it will start on low and
proceed to high 15 minutes later due to a staging timer which
requires 15 minutes of low before high comes on. The UP and
FAN buttons cannot be used to defeat this timer. This timer can be
defeated by reducing the set point to more than 5° below room
temperature, bringing on a high speed demand within 5 seconds.
Remember—2-speed units have a 1 minute off time between lo
and high speed, so the thermostat’s demand will not show
immediately as a speed change in the outdoor unit. It will show
immediately as an increase in the indoor fan speed.

TO TEST HEAT PUMP HEATING:

Press MODE button until HEAT icon under it turns on. Press up
button until HEAT set point (LOWER right 2-digit display with
HEAT now flashing under it) is 2° or 3° (not more) above room
temperature. This will create a first stage heating demand. A small
triangle to the left of this HEAT icon will flash or come on
continually. Flashing means the equipment is going to turn on but
is presently being held off by a system timer. (See "Operational
Information" on page 11 for timer descriptions.) Defeat timer by
pressing UP and FAN buttons together. This will make the triangle
stay on and turn on the heat pump. To turn off, reduce the heating
set point below the room temperature. The heating and the triangle
will turn off within a few seconds.

If the system has a 2-speed compressor, it will start on low and
proceed to high 15 minutes later due to a staging timer which
requires 15 minutes of low before high comes on. The UP and
FAN buttons cannot be used to defeat this timer. If set point is
raised to more than 5° above room temperature, the staging timer
is defeated and the thermostat will call for high speed heat pump
heating within 5 sec. This is not recommended because once the
demand exceeds 5°, the thermostat may jump to furnace heating at
any time. Use the method below to test the furnace.

TO TEST FURNACE HEATING:

To test, press MODE button until EHEAT icon turns on. This will
allow operation of the furnace only. Raising set point above room
temperature will turn on the furnace. Reducing set point below
room temperature will turn it off.

If the heat pump is single speed and the furnace is 2-stage, the
thermostat can be used to control the second stage. (See Fig. 4, 6,
and 8.) To test second stage, raise set point to more than 5° above
room temperature (defeating 15-minute staging timer). Within 5
sec, the thermostat will bring on the furnace second stage.

Table 2—Active Outputs for Each Operating State

1-SPEED HEAT PUMP

2-SPEED HEAT PUMP

Fan

G

Fan

G

Cool

Y/Y2, O/W2, G

Lo Cool

Y1/W2, O/W2, G

Hi Cool

Y1/W2, Y/Y2, O/W2, G

HP Heat

Y/Y2, G

Lo HP Heat

Y1/W2, G

Hi HP Heat

Y1/W2, Y/Y2, G

Furnace Lo

W/W1

Furnace Hi

W/W1, Y1/W2

Furnace

W/W1

6

Содержание Programmable Dual Fuel Thermostats

Страница 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Страница 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Страница 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Страница 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Страница 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Страница 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Страница 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Страница 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Страница 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Страница 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Страница 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Страница 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Отзывы: