12
kPa
kPa
4.3 - Menus
4.3.1 - Selecting a menu
The MENU button authorises you to select a menu from the 10
main menus that are available. Each time you press this button
one of the 10 LEDs lights up in turn alongside each of the
icons representing a main menu. The active menu is the one
against which the LED is lit. If a menu is empty then its LED
is not lit. To scroll quickly through the menus, hold the MENU
button down.
4.3.2 - Selecting a menu item
The up and down Arrow buttons let you scroll through the
menu items. Menu item numbers are displayed in the two-digit
display. The item number increases or decreases every time
you press the up or down Arrow button. The menu items that are
not in use or incompatible with the configuration are not
displayed. The value or status associated with the active item
is displayed in the four-digit display. To scroll quickly through
the items, hold the up or down Arrow button down.
The following example shows how to access item 3 in the
Pressures menu.
SELECTING A MENU ITEM
OPERATION
PRESS
MENU LED
ITEM NUMBER
BUTTON
2-DIGIT
DISPLAY
Press the MENU button until the
LED marked PRESSURE lights.
0
0
Press one of the Arrow buttons
1
until the two-digit display shows 3
(item number 3).
2
3
4.3.3 - Modifying the value of a parameter/access to a sub-
menu
Press the Enter button for more than 2 seconds to enter the
modification mode or to select a sub-menu. This lets you correct
the value of an item or select a sub-menu with the aid of the up
and down Arrow buttons (if you are authorised to overwrite the
item concerned). When modification mode is activated, the
LED for the main menu to which the item belongs flashes in
menu block. Once the required value is obtained, press the
Enter button again to validate the change or to access the sub-
menu. The LED for the menu to which the item belongs then
stops flashing, indicating that modification mode no longer
applies.
In modification mode, the value to be modified increases or
decreases in steps of 0.1 every time you press the Arrow
buttons. Holding one of these buttons down increases the rate
of increase or decrease.
NOTE: The access to a sub-menu may require entering a
password. This is automatically requested. See section 4.5.7.2.
The example below shows how to modify the value of item 1
in the Setpoint menu.
MODIFYING THE VALUE OF A PARAMETER
OPERATION
PRESS MENU LED
ITEM
ITEM
button
NUMBER
NUMBER
2-DIGIT
4-DIGIT
DISPLAY
DISPLAY
Hold on the MENU button until
0
the LED for SETPOINT lights.
0
Press one of the Arrow buttons
1
until the two-digit display shows 1
item number 1- cooling setpoint 2).
The value for setpoint 2 is
displayed in the four-digit display
1
6.0
(6.0°C in this example).
Press the Enter button for more
than 2 seconds to enable the
value associated with item 1 to be
1
6.0
modified. The Setpoint menu LED
flashes indicating that modification
mode is active.
Keep pressing the Down Arrow
1
5.9
button until the value 5.7 is
displayed in the four-digit display.
The Setpoint menu LED keeps
flashing.
1
5.8
1
5.7
Press the Enter button again to
validate the change. The new
setpoint is 5.7°C. The Setpoint
1
5.7
menu LED stops flashing, indicat-
ing that modification mode no
longer applies.
4.3.4 - Expand display
Pressing the Enter button causes a 23 character text expansion
to be scrolled across the four-digit display. All user menus
provide an expansion of the current displayed parameters. If
the expansion is complete the four-digit display reverts to item
value. This function can be inhibited through the User
Configuration menu.