PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
e. Multiply gas rate (cu ft./hr) by heating value (BTUh/cu ft.) to
obtain input.
If clocked rate does not match required input from Step 1, increase gas
valve outlet pressure to increase input or decrease gas valve outlet
pressure to decrease input. Repeat steps b through e until correct input is
achieved. Reinstall regulator seal cap on gas valve.
Table 16 – Gas Valve Outlet Pressure for Gas Heat Values at
Altitude - 40,000
Table 17 – Gas Valve Outlet Pressure for Gas Heat Values at
Altitude - 60,000
Tabulated Data Based on 40,000 BTUh Input for 0-ft (0 M)
to 5400-ft (1646 M) above sea level
ALTITUDE
RANGE
ft (m)
AVG. GAS
HEAT
VALUE AT
ALTITUDE
(Btu/cu ft)
SPECIFIC GRAVITY OF
NATURAL GAS
0.58
0.60
0.62
0.64
Manifold Pressure (in. w.c.)
U
.S
.A
.
900
3.0
3.1
3.2
3.3
0
925
2.8
2.9
3.0
3.1
(0)
950
2.7
2.8
2.9
3.0
975
2.6
2.6
2.7
2.8
to
1000
2.4
2.5
2.6
2.7
1025
2.3
2.4
2.5
2.5
2000
1050
2.2
2.3
2.4
2.4
(610)
1075
2.1
2.2
2.2
2.3
1100
2.0
2.1
2.1
2.2
U
.S
.A
.
800
3.2
3.3
3.5
3.6
2001
825
3.0
3.1
3.3
3.4
(611)
850
2.9
3.0
3.1
3.2
875
2.7
2.8
2.9
3.0
to
900
2.6
2.6
2.7
2.8
925
2.4
2.5
2.6
2.7
3000
950
2.3
2.4
2.5
2.5
(914)
975
2.2
2.3
2.3
2.4
1000
2.1
2.1
2.2
2.3
U
.S
.A
. O
nl
y
775
3.2
3.3
3.4
3.5
800
3.0
3.1
3.2
3.3
3001
825
2.8
2.9
3.0
3.1
(915)
850
2.6
2.7
2.8
2.9
to
875
2.5
2.6
2.7
2.8
900
2.4
2.4
2.5
2.6
4000
925
2.2
2.3
2.4
2.5
(1219)
950
2.1
2.2
2.3
2.3
975
2.0
2.1
2.2
2.2
1000
1.9
2.0
2.0
2.1
U
.S
.A
. O
nl
y
750
3.1
3.2
3.4
3.5
775
2.9
3.0
3.1
3.2
4001
800
2.8
2.9
2.9
3.0
(1220)
825
2.6
2.7
2.8
2.9
850
2.4
2.5
2.6
2.7
to
875
2.3
2.4
2.5
2.5
900
2.2
2.3
2.3
2.4
5000
925
2.1
2.1
2.2
2.3
(1524)
950
2.0
2.0
2.1
2.2
975
1.9
1.9
2.0
2.0
1000
1.8
1.8
1.9
1.9
U
.S
.A
. O
nl
y
725
3.2
3.3
3.4
3.5
750
2.9
3.0
3.1
3.3
5001
775
2.8
2.8
2.9
3.0
(1220)
800
2.6
2.7
2.8
2.9
825
2.4
2.5
2.6
2.7
to
850
2.3
2.4
2.4
2.5
875
2.1
2.2
2.3
2.4
5400
900
2.0
2.1
2.2
2.2
(1646)
925
1.9
2.0
2.1
2.1
950
1.8
1.9
1.9
2.0
975
1.7
1.8
1.8
1.9
1000
1.8
1.8
1.8
1.8
Tabulated Data Based on 60,000 BTUh Input for 0-ft (0 M)
to 5400-ft (1646 M) above sea level
ALTITUDE
RANGE
ft (m)
AVG. GAS
HEAT
VALUE AT
ALTITUDE
(Btu/cu ft)
SPECIFIC GRAVITY OF
NATURAL GAS
0.58
0.60
0.62
0.64
Manifold Pressure (in. w.c.)
U
.S
.A
.
900
2.7
2.8
2.9
2.9
0
925
2.5
2.6
2.7
2.8
(0)
950
2.4
2.5
2.6
2.6
975
2.3
2.3
2.4
2.5
to
1000
2.2
2.2
2.3
2.4
1025
2.0
2.1
2.2
2.3
2000
1050
1.9
2.0
2.1
2.2
(610)
1075
1.9
1.9
2.0
2.1
1100
1.8
1.8
1.9
2.0
U
.S
.A
.
800
2.9
3.0
3.1
3.1
2001
825
2.7
2.8
2.9
3.0
(611)
850
2.6
2.6
2.7
2.8
875
2.4
2.5
2.6
2.7
to
900
2.3
2.4
2.4
2.5
925
2.1
2.2
2.3
2.4
3000
950
2.0
2.1
2.2
2.2
(914)
975
1.9
2.0
2.1
2.1
1000
1.8
1.9
2.0
2.0
U
.S
.A
. O
nl
y
775
2.8
2.9
3.0
3.1
800
2.7
2.8
2.9
2.9
3001
825
2.5
2.6
2.7
2.8
(915)
850
2.4
2.4
2.5
2.6
to
875
2.2
2.3
2.4
2.5
900
2.1
2.2
2.2
2.3
4000
925
2.0
2.0
2.1
2.2
(1219)
950
1.9
1.9
2.0
2.1
975
1.8
1.8
1.9
2.0
1000
1.8
1.8
1.8
1.9
U
.S
.A
. O
nl
y
750
2.8
2.9
3.0
3.1
775
2.6
2.7
2.8
2.9
4001
800
2.5
2.5
2.6
2.7
(1220)
825
2.3
2.4
2.5
2.5
850
2.2
2.2
2.3
2.4
to
875
2.0
2.1
2.2
2.3
900
1.9
2.0
2.1
2.1
5000
925
1.8
1.9
2.0
2.0
(1524)
950
1.8
1.8
1.8
1.9
975
1.8
1.8
1.8
1.8
1000
1.8
1.8
1.8
1.8
U
.S
.A
. O
nl
y
725
2.8
2.9
3.0
3.0
750
2.6
2.7
2.8
2.8
5001
775
2.4
2.5
2.6
2.7
(1524)
800
2.3
2.3
2.4
2.5
825
2.1
2.2
2.3
2.3
to
850
2.0
2.1
2.1
2.2
875
1.9
1.9
2.0
2.1
5400
900
1.8
1.8
1.9
2.0
(1646)
925
1.8
1.8
1.8
1.9
950
1.8
1.8
1.8
1.8
975
1.8
1.8
1.8
1.8
1000
1.8
1.8
1.8
1.8