background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

22

The Main Menu provides access to operating parameters of the furnace

control including airflows as well as other diagnostics. See 

Fig. 26

 for

the location of the pushbuttons. Scroll through Main Menu by pressing

MENU/SELECT  button.  Press  NEXT/OPTION  to  display  the  current

setting of the parameter (value will flash). Additional presses will scroll

through  setting  options.  Press  MENU/SELECT  button  to  save  a  new

setting and return to the Main Menu. The display will flash three times to

confirm a new setting selection has been saved. 

Fig. 34

 shows the flow

of the menu and settings. 

Table 12

 provides additional information on

parameter adjustment and applicability.

NFC and Supported App Method

This  furnace  control  board  is  also  equipped  with  NFC  (Near  Field

Communication) technology which allows the adjustment of operating

parameters, diagnostics, and service via a field-supplied mobile device

with NFC capability and supported mobile app. Remove 115-V power

from the furnace control board to use this method. See 

Fig. 26

 for the

location  of the NFC antenna. Additional instructions and help may be

available through the supported mobile app.
Scan  the  mobile  app  QR  Code  on  page 1  of  this  manual  for  more

information and a link to download the mobile app.

Control Board Replacement

If  the  control  board  must  be  replaced,  the  new  board  must  be

programmed with the correct Model Program Number before the furnace

will operate. Do NOT program the control board with a Model Program

Number different than what is specified on the rating plate. The control

may be programmed by either of these approved methods:

1. Use the supported mobile app to flash the model program onto the

board using Near Field Communication (NFC). Scan the QR code

on  page 1  of  this  manual  for  more  information  and  a  link  to

download the mobile app.

2. Use the correct Super Plug (available from distributor / replacement

component)  for  the  control  board  to  copy  the  correct  model

program onto the new board.

Further  details  and  instructions  for  these  programming  methods  are

provided with the replacement control board.

Table 12 – Main Menu Options

Display

Operating Mode

Use

FLt

Last 7 faults that occurred

Faults code menu stores the 7 latest faults in memory. If no faults, None (

non

) will be 

displayed. To clear fault history, scroll to Clear (

Clr

) and press MENU/SELECT. See 

Fig. 35

 

or Furnace Service Label for codes.

Ht

Heating blower speed

Heating Airflow Setting. Adjust higher to lower Temp. Rise; lower to increase Temp. Rise. See 

Start-Up Procedures. See 

Fig. 34

 for allowable selections and 

Table 9

 for airflows.

CL1

Low Cooling Mode

Low Cooling and High Heat Pump speed.

CL2

High Cooling Mode

High Cooling and High Heat Pump speed.

Cfn

Constant Fan blower speed Constant Fan Airflow Setting. See 

Fig. 34

 for allowable selections and 

Table 9

for airflows. 

HoD

Heat OFF Delay

Value shown in seconds. Shorter delays may leave unused heat in ducts. Longer delays may 

blow cold air at the end of heating demands.

Cod

Cool OFF Delay

Value shown in seconds. Shorter delays may leave unused energy in furnace coil. Longer 

delays may re-evaporate condensate.

dir

Direction

Adjusts display orientation 180 degrees between up flow (

UPF

) and down flow (

dnF

).

tnn

Twinning

Primary (

Pri

) or Secondary (

SEC

) furnace selection. Adjust only if furnace is used in a 

twinned furnace system. Use of accessory kit required. See kit instructions.

inF

Program # and Software

Do NOT program the control board with a Model Program Number different than what is 

specified on the rating plate. Alternates displaying the saved Model Program Number (

pRG

and Software Version (

uEr

). 

Ct

Component Test

Use to validate components are functioning as intended. See Component Self-Test 

instructions in the Start-Up Procedures section.

rSt

Reset

Reset settings to Factory Default by selecting Yes (

YEs

).

CAUTION

!

FURNACE OVERHEATING HAZARD

Failure to follow this caution could result in reduced furnace life.
Do  NOT  program  the  control  board  with  a  Model  Program  Number

different than what is specified on the rating plate. Parameter options

will not match design values.

Содержание PG80MSU

Страница 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Страница 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Страница 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Страница 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Страница 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Страница 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Страница 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Страница 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Страница 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Страница 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Страница 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Страница 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Страница 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Страница 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Страница 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Страница 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Страница 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Страница 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Страница 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Страница 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Страница 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Страница 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Страница 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Страница 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Страница 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Страница 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Страница 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Страница 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Страница 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Страница 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Страница 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Страница 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Страница 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Страница 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Страница 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Страница 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Страница 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Страница 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Страница 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Страница 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Отзывы: