Carrier Performance 52ME-U07-3 Скачать руководство пользователя страница 6

6

ELECTRICAL DATA

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage
DO NOT alter cord or plug or use an extension cord.

!

WARNING

POWER CONNECTION OPTIONS

Appropriate power cord accessory kit is determined

by the voltage, and amperage of the branch circuit.

The unit does not come with a power cord (or

hard wire kit).

An accessory power cord kit must

be ordered to connect the unit to the outlet. If the

unit is to be hard wired, an accessory hard wire kit

must be ordered.

IMPORTANT: For 265V units, if power cord

accessory option is selected, the cord is only 18”

long and must plug into the accessory electrical

265V subbase.

Be sure that your outlet matches the appropriate blade

configuration of the plug and that it is within reach of

the service cord.
All wiring, including installation of the receptacle,

must be in accordance with the NEC and local codes,

ordinances and regulations. National codes require

the use of an arc fault or leakage current detection

device on all 208/230V power cords. Be sure to select

the correct cord for your installation.

ALL UNITS

Wire Size

Use recommended wire size given in Table 1 and

install a single branch circuit. All wiring must

comply with local and national codes.

All units are

designed to operate off ONE single branch circuits

only.
NOTE

: Use copper conductors only.

Table 1—SUGGESTED BRANCH CIRCUIT WIRE SIZES*

NAMEPLATE AMPS

AWG WIRE SIZE

{

7.0 to 12

14

12.1 to 16

12

16.1 to 24

10

LEGEND

AWG --- American Wire Gauge
* Single circuit from main box.

{

Based on copper wire at 60

_

C temperature rating.

Grounding

For safety and protection, the unit is grounded

through the service cord plug or through separate

ground wire provided on hard wired units. Be sure

that the branch circuit or general purpose outlet is

grounded.

VOLTAGE SUPPLY

Check voltage supply at outlet. For satisfactory

results, the voltage range must always be within the

ranges found on the data information plate.

Cord--connected Units

The 250--v field supplied outlet must match the plug

for the standard 208/230--v units and be within reach

of the service cord. The standard cord--connected

265--v units require an accessory electrical subbase

for operation. Refer to Table 2 for proper receptacle

and fuse type.

Power Cord Protection

The power cord for 230/208v units provide power

cord fire protection

.

Unit power automatically

disconnects when unsafe conditions are detected.

Power to the unit can be restored by pressing the reset

button on plug head.
Upon completion of unit installation for 230/208V

models, an operational check should be performed

using the TEST/RESET buttons on the plug head.

NOTE

: The 265v models do not incorporate this

feature as they require use of the electrical subbase

accessory.

Table 2—RECEPTACLES AND FUSE TYPES -- 250, 265 VOLTS

RECEPTACLE

AMPS

15

20

30

15

20

30

RATED VOLTS

250

250

250

265

265

265

TIME---DELAY TYPE FUSE

(or HACR Circuit Breaker)

15

20*

30

15

20

30

LEGEND
HACR

--- Heating, Air Conditioning, Refrigeration

* May be used fro 15---amp applications

Содержание Performance 52ME-U07-3

Страница 1: ...ded This information along with the installation data and dealer contact information will be helpful should your system require maintenance or service UNIT INFORMATION Model ________________________________ Serial ________________________________ INSTALLATION INFORMATION Date Installed ___________________________ DEALERSHIP CONTACT INFORMATION Company Name __________________________________ Addres...

Страница 2: ...l Sleeve Using Non Carrier Grille 8 Install Unit Into Wall Sleeve 9 HOW TO CONNECT 10 SYSTEM CONFIGURATION Ventilation Control 11 Adjusting Air Direction 11 Dipswitches 12 Keypad Configuration 13 AUXILIARY CONTROLS Wall Thermostat Terminal 14 15 Energy Management Input 15 Intelligent Self Checking Control 15 OPERATION 16 CARE AND CLEANING 17 PREVENTATIVE MAINTENANCE 18 TROUBLESHOOTING 19 WARRANTY ...

Страница 3: ...any servicing be performed by a qualified individual GENERAL Thank you for choosing Carrier s best PTAC ever You can feel confident in your selection because the same pride in craftsmanship and engineering knowledge that goes into Carrier equipment at the Astrodome in Texas the Sistine Chapel in Rome the US Capitol Hall of Congress and thousands of other installationsworldwidehasgoneintotheconstru...

Страница 4: ... a minimum compressor run time of 3 minutes Automaticroom freezeprotection automatically will keep the temperature in the room from getting too cold where water pipes might freeze If the unit is configured for the freeze protection feature to be active which is the default condition then whenever power is supplied to the unit if the unit senses temperature below 40 F the fan motor and electric hea...

Страница 5: ...d to limit thecontrolling setpoint range The display will always showthecompletesetpointrange but the controlling setpoint will be limited to the configuredminimumandmaximumsetpointselected See section on unit configuration for more details Energy Management Sometimes known as Front Desk Control an input is provided so that the unit can be manually disabled from a different location If the unit de...

Страница 6: ...NAMEPLATE AMPS AWG WIRE SIZE 7 0 to 12 14 12 1 to 16 12 16 1 to 24 10 LEGEND AWG American Wire Gauge Single circuit from main box Based on copper wire at 60_C temperature rating Grounding For safety and protection the unit is grounded through the service cord plug or through separate ground wire provided on hard wired units Be sure that the branch circuit or general purpose outlet is grounded VOLT...

Страница 7: ...aving air from mixing with the outdoor incoming air known as air recirculation UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation For retrofit applications foam seals on outdoor coil tube sheets must make a seal between the coil and the grille or loss of performance and premature damage to the major components can result CAUTION ...

Страница 8: ...g 6 GE Plastic Sleeve Remove bottom seal from plastic sleeve See Fig 7 INSTALLATION OF A CARRIER WALL SLEEVE USING A NON CARRIER GRILLE This application has become more common due to pre manufactured windows with built in grilles or renovations where a Carrier sleeve is used with an existing non Carrier grille Use of a Carrier wall sleeve with a non Carrier grille requires installation of an Acces...

Страница 9: ...e Fig 13 UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Failure to remove shipping tape and screw will prevent fresh air vent door from opening and may result in damage to vent door cable CAUTION Shipping tape A07066 Fig 9 Shipping Tape Location Remove shipping screw if present A07067 Fig 10 Shipping Screw Location Pull out at the bottom to r...

Страница 10: ...t Remove junction box by taking out top rear and side screws See Fig 14 3 Connect accessory power supply cord or hard wire connector to unit connector See Fig 15 S Units must be installed using the appropriate power supply kit See Table 4 POWER CONNECTION CHART These connections must be followed 4 Reinstall junction box and cover S Use wire clamp to attach power cord to basepan Secure with screws ...

Страница 11: ...y Energy Tip Keep the vent control at CLOSE Room air will be filtered and circulated Open Close Vent Control Pull lever through label to operate A07068 Fig 17 Ventilation Control Location ADJUSTING AIR DIRECTION To adjust air direction 1 Remove front panel See Fig 11 2 Remove louver screws that hold louver insert in place from back side of front panel See Fig 18 3 Turn louver insert and rotate 180...

Страница 12: ... combine to select set point range When set point limit set dis play always shows full range DOWN DOWN 61 86 _F 16 30 _C 7 Freeze Guard Disable Freeze Guard Enable DOWN Electric Heating Only Emergency Heat For Heat Pump Units Only This setting is typically used for Emergency Heating Wall Thermostat Enable A wired wall thermostat can be connected to the unit If it is this dipswitch must be moved to...

Страница 13: ... the air temperature sensor bias is used to adjust the room air temperature reading when in cooling mode Not normally required Indoor Air Temperature Sensor Biasing for Heating mode Sometimes known as an anticipator the air temperature sensor bias is used to adjust the room air temperature reading when in heating mode Not normally required Indoor Temperature Display Changebetween showing setpoint ...

Страница 14: ...g from the wall thermostat the unit will automatically switch over to electric heating R W Y O Gh Gl C A07073 Fig 23 Terminal Connector Removal and Replacement Install Thermostat Wiring 1 Check to be sure power to unit is disconnected 2 Pull terminal connector to remove NOTE Terminal connector can be removed and replaced to simplify thermostat wiring 3 Connect wires from the thermostat to terminal...

Страница 15: ...be disabled under Freeze Guard protection See Fig 25 and Fig 26 for terminal connections INTELLIGENT SELF CHECKING CONTROL Your Carrier PTAC has a computer board that continuously checks key components of the unit to ensure they are operating properly Under normal operation unit status indicator STATUS on main PCB light is steadily ON If there is a major problem the unit will shut down and display...

Страница 16: ...ep room at the requested level of comfort COOLER Lowers temperature Minimum temperature setting is 61_F 16_C WARMER Raises temperature Maximum temperature setting is 86_F 30_C 2 FAN SPEED MODE ON OFF FAN SPEED Set fan operation for HI MED or LO speed MODE COOL For cooling MODE HEAT For heating NOTE If unit is a heat pump raising the heat setting 5_F will cause unit to use its electric heating elem...

Страница 17: ...ssary AIR FILTERS IMPORTANT TURN UNIT OFF BEFORE CLEANING UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not operate unit without filters in place If a filter becomes torn or damaged it should be replaced immediately Operating without filters in place or with damaged filters will allow dirt and dust to reach indoor coil and reduce cooling ...

Страница 18: ...Clean both sides of outdoor coil Never use high pressure spray on coils S Clean basepan and outdoor vent filter S Clean outdoor orifice and fan S Clean indoor coil Never use high pressure spray on coils S Clean indoor fan wire screen and front panel S Clean or install new indoor air inlet filter s S Clean wall sleeve and outdoor grille S Inspect cord and receptacle S Secure electrical connections ...

Страница 19: ...ing heat or gatherings of people make room uncomfortable S Close vent door S Check dipswitch settings for desired comfort Wait approximately 3 minutes for compressor to start DISPLAY HAS STRANGE NUMBERS CHARACTERS ON IT The unit may be in a diagnostic condition Check Intelligent Self checking Control section to determine if unit has had a failure The unit may be set for _C instead of _F see the ke...

Страница 20: ...20 NOTES ...

Страница 21: ...21 NOTES ...

Страница 22: ...22 NOTES ...

Страница 23: ... WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY CARRIER WILL NOT BE RESPONSIBLE FOR 1 CLEANING REQUIRED PRIOR TO WARRANTY REPAIR 2 Standard maintenance cleaning or damage resulting from failure to perform normal maintenance as outlined in the ownerÕ s manual ...

Страница 24: ... S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 52M 1SI Replaces NEW Printed in U S A Edition Date 03 07 ...

Отзывы: