Guide specifications

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner 

unit suitable for ground or rooftop installation. Unit consists 
of a hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil 
or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of 

ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed 

in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have c-UL 
approval.

Unit cabinet will be capable of withstanding Federal Test 

Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.

Air-cooled condenser coils will be leak tested at 150 psig 

and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner 

unit. Contained within the unit enclosure is all factory 
wiring, piping, controls, compressor, refrigerant charge 
Puron® (R-410A), and special features required prior to field 
start-up.

Refrigerant

Refrigerant will be Puron® (R-410A) HFC refrigerant with 

zero ozone depletion potential. R-410A is approved under 
the EPA’s Significant New Alternatives Program (SNAP).

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Air-Cooled, Split-System

Air Conditioner

38TZA

1-1/2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase 

type with class B insulation and permanently lubricated 
bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated 

steel wire safety guards.

Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 

bonded to copper tubes which are then cleaned, dehydrated, 
and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line 

shutoff valve with sweat connections, vapor-line shutoff 
valve with sweat connections, system charge of Puron® 
(R-410A) refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at 

a suction temperature of _____ °F. The power consumption 
at full load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of _____ Btuh or 
greater at conditions of _____ CFM entering air temperature 
at the evaporator at _____ °F wet bulb and _____ °F dry 
bulb, and air entering the unit at _____ °F.

The system will have a SEER of _____ Btuh/watt or greater 

at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, 

single phase, 60 hz. The unit will be capable of satisfactory 
operation within voltage limits of _____ v
to _____ v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories 

and descriptions for specific features and available 
enhancements.

Содержание Performance 12

Страница 1: ...en Puron refrigerant is in service in thousands of systems providing highly reliable environmentally sound performance For specific R 22 phase out information see your Carrier distributor Carrier s Infinity Controls These industry leading controls when installed with Carrier s Ideal Humidity variable speed furnaces or fan coils provide the homeowner with unparalleled control of temperature humidit...

Страница 2: ...essor to eliminate sound transmission to the rest of the system Application Versatility Carrier s systems utilizing Puron refrigerant have the same application guidelines as other systems Applications which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F 12 8 C are approved under Carrier s standard guidelines Carrier Co...

Страница 3: ... with Ring Charge Lb 5 22 5 20 5 19 5 43 5 43 5 75 8 00 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 1700 2000 2400 2400 2800 2800 3300 Motor HP 1 12 1 10 1 8 1 8 1 5 1 5 1 4 Motor RPM 1100 1100 825 825 825 825 1100 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 10 9 10 9 12 2 12 2 12 2 12 2 18 2 Fins per In 25 25 25 25 25 25 25 Rows 1 1 1 1 1 1 1 Circuits 2 2 ...

Страница 4: ...4 33 060 THERMOSTAT SUBBASE PKG DESCRIPTION TSTATCCPRH01 B Thermidistat Control Non Programmable Programmable Thermostat with Humidity Control TSTATCCPAC01 B Thermostat Auto Changeover 7 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCNAC01 B Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCSAC01 Thermostat Manual Changeover 5 2 Day Programmable F C 1 Stage He...

Страница 5: ...rature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required when low ambient kit has been added 7 Liquid Line Solenoid Valve LLS This device serves two purposes It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation It maintains a column of refrigerant liquid ready fo...

Страница 6: ... 0 64 0 60 5 53 0 060 33 78 61 5 69 5 71 0 71 5 69 0 66 0 59 5 9 Outdoor Air Temperature Sensor Designed for use with Carrier Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is required to enable special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Carrier thermostats listed in th...

Страница 7: ...on is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 33 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 024 34 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 030 33 ...

Страница 8: ...RNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 75 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 85 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK3BA024 17 500 TDR 13 00 13 00 12 00 CK5A CK5BA018 17 200 TDR 13 00 13 00 11 75 CK5A CK5BA024 17 500 TDR 13...

Страница 9: ...W030 22 600 TDR 13 00 13 00 11 70 CE3AA024 22 200 TDR 13 00 13 00 11 50 CE3AA030 22 600 TDR 13 00 13 00 11 75 CK3BA024 22 200 TDR 13 00 13 00 11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13 00 13 00 11 80 CK5PW024 22 200 TDR TXV 13 00 11 60 CK5PW030 22 600 TDR TXV 13 00 11 75 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CE3AA024 22...

Страница 10: ... NONE 12 00 12 00 10 55 CK3BA030 28 000 NONE 11 70 11 70 10 35 CK3BA036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BA030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BT036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BW030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BW036 29 000 NONE 12 00 12 00 10 65 CK5PA030 28 000 TXV 11 70 10 35 CK5PA036 29 000 TXV 12 00 10 65 CK5PT036 29 000 TXV 12 00 10 65 CK5PW030 28 000 TXV 11 70 ...

Страница 11: ...6 28 800 TDR TXV 13 00 11 60 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 600 TDR 13 00 13 00 11 60 CE3AA030 27 800 TDR 12 50 12 50 11 30 CE3AA036 28 200 TDR 13 00 13 00 11 45 CK5A CK5BW036 28 800 TDR 13 00 13 00 11 65 CK5PW036 28 800 TDR TXV 13 00 11 65 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 200 TDR 13 00 13 00 11 65 CE3AA030 27 800 TDR 12 50 12 50 11 35 CE...

Страница 12: ...0 11 00 FE4ANF003 34 200 TDR TXV 13 00 11 50 FE4ANF005 35 000 TDR TXV 13 70 11 95 FE4ANB006 35 800 TDR TXV 14 00 12 25 FG3AAA036 34 000 NONE 11 50 11 50 10 35 FK4 C D NB006 35 400 TDR TXV 14 00 12 25 FK4 C D NF001 33 800 TDR TXV 12 50 10 95 FK4 C D NF002 34 000 TDR TXV 12 50 11 05 FK4 C D NF003 34 200 TDR TXV 13 00 11 50 FK4 C D NF005 35 000 TDR TXV 13 50 11 95 FV4 A B NB006 35 800 TDR TXV 14 00 1...

Страница 13: ... 11 35 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 TDR 13 00 13 00 11 55 CC5A CD5AW036 34 600 TDR 13 00 13 00 11 35 CC5A CD5AW042 34 400 TDR 13 00 13 00 11 50 CE3AA036 34 200 TDR 12 50 12 50 11 25 CE3AA042 34 600 TDR 13 00 13 00 11 55 CK3BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BT042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BW036 34 60...

Страница 14: ... 11 50 9 90 FC4 B C N F B 048 39 500 TDR TXV 11 70 10 05 FC4 B C NB054 40 500 TDR TXV 12 20 10 65 FE4ANB006 40 500 TDR TXV 13 70 11 60 FE4ANF003 38 500 TDR TXV 12 70 10 85 FE4ANF005 40 500 TDR TXV 13 20 11 30 FG3AAA048 40 000 NONE 11 70 11 70 10 20 FK4 C D NB006 40 500 TDR TXV 13 50 11 60 FK4 C D NF003 38 500 TDR TXV 12 50 10 85 FK4 C D NF005 40 000 TDR TXV 13 00 11 30 FV4 A B NB006 40 500 TDR TXV...

Страница 15: ...8 39 500 TDR 12 50 12 50 11 15 CE3AA042 39 000 TDR 12 50 12 50 11 05 CE3AA048 39 500 TDR 12 50 12 50 11 10 CK3BA042 39 000 TDR 12 50 12 50 11 00 CK3BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BA042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BT042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BT048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 15 CK...

Страница 16: ...CK5PA060 46 000 TXV 12 00 10 40 CK5PT048 45 000 TXV 11 70 10 20 CK5PT060 46 000 TXV 12 00 10 40 CK5PW048 45 000 TXV 11 70 10 20 CK5PX060 46 500 TXV 12 00 10 50 F A B 4 A B N F B C 048 45 000 TDR 11 70 11 70 10 10 F A B 4 A B N F B C 060 46 000 TDR 11 70 11 70 10 10 FB4 A B NB070 46 500 TDR 12 00 12 00 10 45 FC4 B C N F B 048 44 500 TDR TXV 11 50 10 00 FC4 B C N F B 060 45 000 TDR TXV 11 50 9 95 FC...

Страница 17: ...0 13 00 11 15 CD5AA048 44 500 TDR 12 50 12 50 10 90 CE3AA048 44 500 TDR 12 00 12 00 10 85 CE3AA060 45 000 TDR 12 50 12 50 11 15 CK3BA048 44 500 TDR 12 00 12 00 10 85 CK3BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BA048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BT048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BT060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BW048 44 500 TDR...

Страница 18: ...0 56 000 TDR TXV 12 00 10 15 COILS 58CV A X 110 20 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 11 50 11 50 10 00 CD5PX060 58 500 TDR TXV 12 00 10 35 CE3AA060 58 000 TDR 12 00 12 00 10 35 CK3BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BT060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BX060 58 000 TDR 12 00 12 00 10 50 CK5PA060 58 000 TDR TXV 12 00 10 35 CK5PT0...

Страница 19: ...e Delay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for central air conditioners Ratings for other combinations are determined under DOE computer simulation procedures 3 Determine...

Страница 20: ...9 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19 01 14 46 1 50 18 03 14 23 1 67 16 84 13 82 1 87 15 67 13 36 2 06 14 45 12 88 2 27 63 18 47 14 29 1 34 17 56 14 08 1 49 16 44 13 62 1 66 15 36 13 17 1 83 14 23 12 70 2 02 13 04 12 19 2 23 62 18 40 17 89 1 34 17 56 17 56 1 49 16 67 16 67 1 67 15 80 15 80 1 85 14 90 14 90 2 04 13 97 13 97 2 26 57 18 34 18 34 1 33 17 56 17 56 ...

Страница 21: ...8 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 0 99 1 01 CK5A CK5BA 024 0 97 0 89 030 1 00 1 01 030 0 98 0 90 CC5A CD5AW 024 0 99 1 01 CK5A CK5BW 024 0 97 0 89 030 1 00 1 01 030 0 98 0 89 CE3AA 024 0 99 1 00 CK5PA 024 0 97 0 89 030 1 00 1 ...

Страница 22: ... 23 62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 72 26 66 14 25 1 73 26 38 14 46 1 96 25 42 14 30 2 21 24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Co...

Страница 23: ... 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 CE3AA 030 0 97 0 92 036 1 00 1 00 036 0 97 0 91 CC5A CD5AW 030 0 97 1 00 CK3BA 030 0 96 0 92 036 1 00 1 00 036 0...

Страница 24: ... 2 27 28 6 23 0 2 49 26 2 22 0 2 73 23 7 21 0 3 00 22 2 20 4 3 32 20 1 19 4 3 67 62 30 3 30 0 2 26 29 0 29 0 2 49 27 0 27 0 2 74 25 7 25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capaci...

Страница 25: ...liers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CK5A CK5BE 042 0 99 0 92 042 1 00 1 00 CK5A CK5BT 036 0 99 0 94 CC5A CD5AW 036 1 00 1 00 CK5PA 036 0 99 0 94 042 0 99 1 00 CK5PE 042 0 99 0 93 CE3AA 036 0 99 1 00 CK5PT 036 0 99 0 94 042 1 00 1 00 COILS 58CV A X 090 16 VARIA...

Страница 26: ...53 57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CK3BA 036 0 99 0 94 CC5A CD5AA 042 0 99 0 91 042 0 99 0 93 CC5A CD5AW 036 0 99 0 92 CK5A CK5BA 036 0 9...

Страница 27: ...1 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 99 1 00 CE3AA 042 0 98 0 92 CC5A CD5AW 042 0 99 1 00 048 0 99 0 92 048 1 00 1 00 CK3BA 042 0 98 0 92 CD5AA 048 1 00 1 00 048 0 99 0 92 CE...

Страница 28: ... 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CE3AA 042 0 98 0 91 COILS 58MVP060 14 VARIABLE SPEED FURNACE 048 0 99 0 92 CK3BA 042 0 98 0 94 CK3BA 042 0 98 0 91 CK5A CK5BE 042 0 99 0 96 048 0 99 0 91 CK5PE 042 0 99 0 96 CK5A CK5BA 042 0 9...

Страница 29: ...3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 00 CE3AA 048 0 97 0 95 CC5A CD5AC 048 0 96 0 99 060 0 98 0 93 CC5A CD5AW 048 0 98 1 00 CK3BA 048 0 97 0 95 060 1 01 1 02 CK5A CK5BA 048 0 97 0 95 CD5AA 048 0 98 1 0...

Страница 30: ...94 62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 0 97 0 94 CK5A CK5BA 048 0 97 0 97 060 ...

Страница 31: ...3 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 54 7 54 7 4 39 51 8 51 8 4 88 50 2 50 2 5 45 48 5 48 5 6 10 45 6 45 6 6 79 41 6 41 6 7 55 2000 72 67 6 34 3 4 68 65 3 33 7 5 21 62 4 32 9 5 79 58 6 31 6 6 42 55 0 30 5 7 13 50 9 29 2 7 92 67 63 6 45 4 4 61 60 7 4...

Страница 32: ... 52 1 73 1 94 2 15 2 37 40 TCG 29 5 24 9 23 2 21 3 19 4 17 3 15 0 12 4 SDT 74 5 83 7 92 8 102 0 111 2 120 4 129 3 138 2 KW 1 00 1 18 1 36 1 55 1 77 2 0 2 23 2 46 45 TCG 32 3 29 0 26 0 23 9 22 0 19 9 17 6 15 0 SDT 76 1 85 3 94 5 103 7 112 9 121 9 130 8 139 6 KW 1 02 1 20 1 39 1 60 1 82 2 05 2 29 2 54 50 TCG 37 7 35 9 30 0 27 2 24 8 22 6 20 3 17 9 SDT 77 7 86 7 95 9 105 1 114 2 123 2 132 1 140 8 KW ...

Страница 33: ...142 0 4 61 40 TCG SDT KW 44 7 78 4 2 01 42 3 87 7 2 28 39 9 97 0 2 58 37 5 107 0 2 92 35 0 116 0 3 29 32 5 125 0 3 70 29 9 134 0 4 15 27 1 144 0 4 65 45 TCG SDT KW 48 7 80 3 2 06 46 1 89 4 2 32 43 6 98 7 2 62 40 9 108 0 2 96 38 2 118 0 3 34 35 5 127 0 3 75 32 6 136 0 4 20 29 5 145 0 4 69 50 TCG SDT KW 52 9 82 3 2 11 50 2 91 3 2 37 47 4 101 0 2 67 44 5 110 0 3 01 41 6 119 0 3 39 38 6 128 0 3 80 35 ...

Страница 34: ...ided 9 Do not apply capillary tube indoor coils to these units 10 Factory supplied filter drier must be installed This must be replaced each time the refrigeration system is opened for service 11 Do not deviate from factory supplied TXV s and Liquid Line Solenoids Condenser only ratings continued ARI listing applies only to systems shown in Combination Ratings table KW Outdoor Unit Kilowatts Only ...

Страница 35: ...35 ...

Страница 36: ...pletion potential R 410A is approved under the EPA s Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TZA 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclose...

Отзывы: