Carrier PA17NA Скачать руководство пользователя страница 5

5

Airflow Selection for Variable Speed Furnaces

The variable speed furnaces provide blower operation to match the
capacities of the compressor during high and low stage cooling

operation. The furnace control board allows the installing

technician to select the proper airflows for each stage of cooling.
Below is a summary of required adjustments. See furnace

installation instructions for more details:

1. Turn SW1----5 ON for 400 CFM/ton airflow or OFF for 350

CFM/ton airflow. Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high

stage cooling operation. Select the A/C DIP switch setting
corresponding to the available airflow shown in the furnace
Installation Instructions that most closely matches the re-

quired airflow shown in the air conditioning Product Data
for HIGH speed.

3. The CF DIP switch setting determines airflow during low

stage cooling operation. Select the CF DIP switch setting
corresponding to the available airflow shown in the furnace

installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data

for LOW speed. If a higher or lower continuous fan speed is
desired, the continuous fan speed can be changed using the
fan switch on the thermostat. Refer to the furnace Installa-

tion Instructions for details of how to use this feature.

Airflow Selection for FV4C Fan Coils

The FV4 provides high-- and low--stage blower operation to match

the capacities of the compressor at high-- and low--stage.
To select recommended airflow, refer to the FV4C Installation
Instructions. The FV4C utilizes an Easy Select control board that

allows the installing technician to select proper airflows. This fan
coil has an adjustable blower--off delay factory set at 90 sec. for

high-- and low--stage blower operation.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.

Start--Up

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury,

equipment damage or improper operation.

S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Compressor dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader

valves.

Follow these steps to properly start up the system:

1. After system is evacuated, fully back seat (open) liquid and

vapor service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to
refrigerant flow (back seated). Replace caps finger-tight and
tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Ensure that set

point is below indoor ambient temperature and is set low
enough to energize desired stage. In order to start the system
in low stage, refer to the literature for the installed thermo-

stat and adjust the set point so that the differential between
the room temperature and the set temperature energizes Y1.

5. Set room thermostat to COOL and fan control to ON or

AUTO mode, as desired.

6. Operate unit for 15 minutes. Verify system refrigerant

charge by measuring the sub-cooling for low stage and
comparing with the published sub-cool on the rating plate.

7. In order to switch the the system to high stage, refer to the

literature for the installed thermostat and adjust the set point

to a lower value so that the differential between the room
temperature and the set temperature energizes Y2. Verify
system refrigerant charge by measuring the sub-cooling for

high stage and comparing with the published sub-cool on
the rating plate.

SYSTEM FUNCTIONS AND SEQUENCE

OF OPERATION

The PA17NA models utilize a 2-stage cooling indoor thermostat.

With a call for first stage cooling, the outdoor fan and low-stage

compressor are energized. If low-stage cannot satisfy cooling
demand, high-stage is energized by the second stage of indoor

thermostat. After second stage is satisfied, the unit returns to
low-stage operation until first stage is satisfied or until second stage

is required again.
When both first stage and second stage cooling are satisfied, the
compressor will shut off. Therefore, with first stage of cooling Y1

is powered on; and with second stage of cooling Y1 and Y2 are
powered on. When a 2-stage unit is operating at low-stage, system

vapor (suction) pressure will be higher than a standard single-stage
system or high-stage operation.

Compressor Operation

The basic scroll design has been modified with the addition of an

internal unloading mechanism that opens a by-pass port in the first
compression pocket, effectively reducing the displacement of the

scroll.
The opening and closing of the by-pass port is controlled by an

internal electrically operated solenoid. The modulated scroll uses a

single step of unloading to go from full capacity to approximately
67% capacity. A single speed, high efficiency motor continues to

run while the scroll modulates between the two capacity steps.
Modulation is achieved by venting a portion of the gas in the first

suction pocket back to the low side of the compressor, thereby

reducing the effective displacement of the compressor. Full
capacity is achieved by blocking these vents, thus increasing the

displacement to 100%.
A DC solenoid in the compressor controlled by a rectified 24 volt

AC signal in the external solenoid plug moves the slider ring that
covers and uncovers these vents. The vent covers are arranged in

such a manner that the compressor operates at approximately 67%

capacity when the solenoid is not energized and 100% capacity
when the solenoid is energized. The loading and unloading of the

two step scroll is done “on the fly” without shutting off the motor
between steps.

NOTE

: 67% compressor capacity translates to approximately

75% cooling capacity at the indoor coil.

PA

17N

A

Содержание PA17NA

Страница 1: ...electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 ...

Страница 2: ... 12 78_C and the maximum outdoor operating ambient in cooling mode is 125_F 51 67_C when operating voltage is 230v For 208v applications the maximum outdoor ambient is 120_F NOTE Units operating at high stage operation 208v or below line voltage and at an outdoor ambient 120_F or greater may experience compressor trip Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure...

Страница 3: ... Pumps using R 410A refrigerant Install Liquid Line Filter Drier Indoor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation 1 Installation of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liq...

Страница 4: ...than 100 ft 30 48 m from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power require...

Страница 5: ...et point is below indoor ambient temperature and is set low enough to energize desired stage In order to start the system in low stage refer to the literature for the installed thermo stat and adjust the set point so that the differential between the room temperature and the set temperature energizes Y1 5 Set room thermostat to COOL and fan control to ON or AUTO mode as desired 6 Operate unit for ...

Страница 6: ... periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file TROUBLESHOOTING If the compressor fails to operate with a cooling call the table below Resistance table can be used to verify if there is any damage to the compressor windings causing system malfunction Table 3 Winding Resistance Winding Winding resistance at 70_F 20_F 21 11_C ...

Страница 7: ...as a 24 volt coil and is controlled by Y1 input from the thermostat High and Low Pressure Switches High and low pressure switches are provided in line with the Y1 signal to the contactor for protection The high pressure switch mounted on the liquid tube is set to open at 670 psi and higher and the low pressure switch mounted on the suction tube opens at a pressure of 50 psi and lower CARE AND MAIN...

Страница 8: ...Two Stage Air Conditioner Thermidistat Variable Speed Fan Coil TWO STAGE AIR CONDITIONER THERMIDISTAT Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Fig 6 Thermidistat Wiring with 2 Stage R 410A refrigerant Air Conditioner A09278 Single Stage Furnace with 2 Stage Air Conditioner A09279 2 Stage Thermostat with Single Stag...

Страница 9: ... filter driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth whe...

Страница 10: ...ing S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM PA17NA 02 Replaces IM PA17NA 01 Edition Date 09 12 PA17NA ...

Отзывы: