background image

FN1AAF: Operation and Maintenance Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

Unpacking Your System

Carefully remove your unit from its packaging. Inspect for damage. If

damage is noted, contact your shipping carrier and file a claim.

Assemble the Unit

1. Remove the parts bags and/or box from the lower compartment.
2. Lay the unit on  its back,  as near as possible to  its intended  final

location.

NOTE: 

The  unit  can  be  operated  without  casters,  on  its  back  in  a

horizontal orientation, as long as there is sufficient space at either end for

air intake and output. Make sure to properly strap or otherwise secure it

to a base to avoid unintentional movement.

3. Attach the caster assemblies (ref 

Fig. 2

) to the bottom of the unit.

a. Remove the screws from the outer corners of the cabinet bottom.

b. Position the caster assembly along the outer edge of the unit and 

line up the screw holes.

c. Use the removed screws to attach the caster assembly.

d. Repeat for the other side.

A200233

Fig. 2 – Boxed Casters and Duct Transition (10-inch round shown)

4. Use the included screws to attach the round or oval duct transition

plate  to  the  top  of  the  unit  (

Fig. 3

). 

NOTE

: The  transition  plate

must

 be installed even if the unit is being used as an air scrubber.

5. Carefully  lift the  unit  to  a vertical position  on  its casters. HINT:

Lock the casters before lifting or tilting up the unit.

6. Move the unit in its final position and lock all four casters.
7. For negative-air setup, do these steps. If used as an  air scrubber,

skip to step 8.

a. Use a compression clamp to attach 10- or 12-inch round flexible 

ducting (supplied by others) to the transition plate on top of the 

unit.

b. Run the flexible ducting as recommended by the mechanical plan 

and attach to a transition piece (ceiling register box, etc., 

purchased or fabricated on site) to complete a path for the air to 

exhaust from the negative-air area. Caulk or tape all seams. Run 

the flexible duct per applicable codes and requirements, with no 

hard bends or obstructions.

8. Remove the bottom front door, then the top door over the blower

section.  Inspect  the  HEPA  filter  and  make  sure  it  has  not  been

dislodged or damaged during shipping, that the side bolts and nuts

near each corner are tight and the HEPA filter is held securely in

place, and the seal around the top edge of the filter is in place.

9. Make sure the first-stage pre-filter is in place and not damaged.
10. Replace the top door over the blower, then the bottom front door.

11. Plug the unit into a grounded 115V outlet.

A200218

Fig. 3 – Typical Duct Transition Installation

Operating Instructions

IMPORTANT: 

Always lock the casters during operation. 

IMPORTANT: 

Make sure there are no paper or lightweight loose 

objects near the floor by the unit that could be sucked into the bottom air 

intake or front opening of the bottom front door. We recommend that you 

regularly clean or sweep the floor around the unit to extend the life of the 

pre-filter.

• Locate the control panel on the front upper left (

Fig. 4

).

• Rock  the  green  ON/OFF  switch  up  to  the  ON  position.  It  should

illuminate. There will be a slight delay before air begins to move as

the blower motor has a built-in 3-second operational delay. 

• For the 015 model, select the fan speed desired.

• Observe the unit running for a short time to make sure there are no

unusual  noises,  that  air  is  freely  flowing  through  the transition  and

ducting, and the unit is not shifting position. Make sure the casters are

locked!

A200222

Fig. 4 – Control Panels

Routine Maintenance

Daily

Inspect the unit: 

• power  cord  is  not  broken,  frayed  or  worn,  and  the  plug  is  fully

engaged at the wall outlet

• casters are locked

• red filter/obstruction indicator is not illuminated

• unit operates without excessive vibration or unusual noises

• flexible  exhaust  ducting  (if  used)  is  not  kinked  or  damaged,  and

securely attached at both ends

Cleaning

Routinely clean any dust and contaminants from the exterior of the unit

and  power  cord  with  a  mild  cleaner.  Do  not  use  excessive  liquid.

Decontaminate  as  necessary  with  a  facility-  and  EPA-approved

disinfectant.

WARNING

!

TIP OVER HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  and/or

property damage.

Unit must be  on a smooth and solid surface. When  moving the unit,

make sure the path is free of obstacles. 

005

015

Содержание OptiClean FN1AAF 005

Страница 1: ...rd MERV 7 or higher pre filter Minimum 500 CFM and Maximum 1500 CFM Meets or exceeds ASHRAE Standard 170 Ventilation of Health Care Facilities Vertical design for smaller footprint compared to many competitors and can be mounted and operated horizontally when necessary Portable and adaptable to nearly any location Heavy duty locking casters for easy and smooth transport HEPA filter rack and sealin...

Страница 2: ... Remove the bottom front door then the top door over the blower section Inspect the HEPA filter and make sure it has not been dislodged or damaged during shipping that the side bolts and nuts near each corner are tight and the HEPA filter is held securely in place and the seal around the top edge of the filter is in place 9 Make sure the first stage pre filter is in place and not damaged 10 Replac...

Страница 3: ...se a 1 2 inch open end or adjustable wrench to remove the bottom nuts from the all thread bars on both sides four nuts total 7 Slide the bottom HEPA filter supports down along with the filter and out of the unit 8 Remove the HEPA filter and immediately put it inside an approved containment bag Dispose per facility guidelines for hazardous materials 9 Position the new HEPA filter into the unit with...

Страница 4: ...ting and or repairs be sure to have the model and serial numbers of your equipment available Specifications A200223 Fig 7 005 Model Wiring Diagram A200258 Fig 8 015 Model Wiring Diagram Switch Setting Motor Lead Motor Tap Options LOW Red 1 2 3 Switch Setting Motor Lead Motor Tap Options MED Blue 2 3 4 Switch Setting Motor Lead Motor Tap Options HIGH Gray 5 Table 2 Electrical Specifications 005 Mod...

Страница 5: ...103 342890 75105 6 2 Gasket 6 152 mm 346295 402 7 2 Gasket 16 408 mm or 20 506 mm 346295 401 346295 403 8 2 Caster Assembly 346285 701 346285 702 9 1 HEPA Filter 346345 75101 346345 75102 10 1 Pre filter MERV 7 KH01AZ500 KH01AZ501 11 1 Lower Door Assembly 346279 701 346279 702 12 1 Upper Door Assembly 346277 701 346277 702 13 1 Indicator red 346299 401 14 1 Power Switch green lighted 346300 401 15...

Страница 6: ...dition Date 06 20 Catalog No OM FN1AAF 02 Replaces OM FN1AAF 01 FN1AAF Operation and Maintenance Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Notes Page ...

Отзывы: