VVT Zone Controller
51
NOTE
Engineering units shown in this document in the defaults and ranges are strictly for reference. You
must enter an integer only.
Status
i-Vu / Field Assistant:
Navigation:
BACview:
Properties
>
Equipment
>
Status
HOME
>
STATUS
Point Name/Description
Range
Terminal Mode
R:
– The controller's current operating status.
OFF
HEATING
WARM-UP
VENT
COOLING
DEHUMIDFY
REHEAT
PRESSURIZE
EVACUATE
SHUTDOWN
IAQ OVERRIDE
AIR BALANCING
Term Type
R:
– The type of zone terminal that the controller is installed on.
Single Duct
Parallel Fan
Series Fan
Space Temperature
- Prime Variable
R:
– The space temperature value currently used for
control.
-56 to 245°F
Damper Position
R:
– The current damper position.
0 to 100%
Supply Air Temperature
R:
– The current supply air temperature.
-56 to 245°F
Heating Capacity
R:
– The current reheat capacity when the zone is configured for reheat.
0 to 100%
Baseboard Heating Capacity
R:
– The current modulating baseboard heat capacity when
the zone is configured for Combination Baseboard and Ducted Heat.
0 to 100%
Outdoor Air Temperature
R:
– The current outdoor air temperature from a linked air
source, if available, or from another network source.
-56 to 245°F
Fan
– The status of the terminal fan if
Term Type
is
Parallel Fan
or
Series Fan
R:
.
On/Off
CO2 (ppm)
– The current IAQ value if
Optional Sensor Type
is set to
IAQ Control
R:
.
0 to 5000ppm
Space Relative Humidity
– The current space relative humidity if
Optional Sensor Type
is set to
RH Control
R:
.
0 to 100%rh
Shutdown
– When
Active
D:
, disables all control functions, at normal equipment time
delays and close the damper.
R:
Inactive
Inactive/Active
Appendix A: VVT Zone Controller Points/Properties
Содержание OPN-VVTZC
Страница 2: ......
Страница 27: ...VVT Zone Controller 23 Single duct 2 position hot water Single duct modulating hot water...
Страница 29: ...VVT Zone Controller 25 Fan box 2 position hot water Fan box modulating hot water ducted or baseboard...
Страница 30: ...Installation 26 VVT Zone Controller Fan box combination baseboard and ducted heat Fan box 2 stage electric heat...
Страница 79: ......