
Sequence of Operation
RTU Open v3
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2016
Integration Guide
All rights reserved
25
Dehumidification
The RTU Open provides occupied and unoccupied dehumidification on units that are equipped with the Carrier
Humidi-MiZer™ option from the factory. This requires a space relative humidity sensor or a humidistat for control.
The following conditions must be true for the dehumidification control to operate:
•
The
Outside Air Temperature
is greater than the
Cooling Lockout Temperature
setpoint
•
The
Indoor Fan
has been on for at least 30 seconds
•
The unit has a valid
Supply Air Temperature
input
•
The unit has a valid
Space Temperature
input
•
The unit has a valid
Space Relative Humidity Sensor
or
Humidistat
input
•
Heat mode is not active and the time guard between modes has expired
When using a relative humidity sensor to control dehumidification, occupied and unoccupied dehumidification
setpoints are used.
When using a humidistat, the setpoints are not used. The humidistat indicates a high-humidity condition.
When a high indoor relative humidity condition is indicated and the above conditions are satisfied, the RTU Open
enters the dehumidification mode, energizing the Humidi-MiZer™ output.
The mode continues until the space relative humidity falls below the active setpoint by a 5% fixed Hysteresis when
a humidity sensor is used, or when there is no longer a call for dehumidification where a humidistat is used.
See the base unit / Humidi-MiZer™ operations manual for additional information.
Demand Limiting
The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint
expansion. The controller’s heating and cooling setpoints are expanded in steps or levels. The degree to which the
setpoints are expanded is defined by the
Demand Level Setpoints
.
Each
Demand Level
(1 through 3) adjusts the heating and cooling setpoints outwards. By default,
Demand 1
yields a 1 °F (.5 °C) expansion,
Demand 2
yields a 2 °F (1.1 °C) expansion, and
Demand 3
yields a 4 °F
(2.2 °C) expansion.
The BACnet
Demand Limit
variable sets the desired level of setpoint expansion in the receiving controller.
Level 0
leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1 through 3 expands
occupied heating and cooling setpoints.
Door switch
A
Door Contact
may be configured on any unused binary input. A typical application is a door or window contact
mounted within the space served by a single zone rooftop. The
Door Contact
disables mechanical cooling and any
heating, when active (an open door or window is detected). Economizer cooling, if available, continues to operate.
The input provides a configurable alarm delay (60 second default) before heating and cooling is disabled.