N92ESN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
condensate and compatible with mineral and vegetable oils, such as
Carolan oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down and
away from the furnace in horizontal sections of drain line.
A11582
Fig. 18 – Horizontal Drain Trap Grommet
INSTALLATION
Upflow Installation
N Coil Installation
When a 17-1/2-in. wide upflow N coil is used with a 0601714 furnace,
the N coil must either be raised using a transition piece at least 3-in. (76
mm) high or if a transition piece is not used, the refrigerant lines of the N
coil must point to the front of the furnace casing. Factory accessory
4-3/4-in. transitions are available. Refer to the Specification Sheet for
the current accessory transition part number.
NOTE:
The furnace must be pitched as shown in
for proper
condensate drainage.
A11237
Fig. 19 – Furnace Pitch Requirements
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that
the heat exchanger can be viewed for possible openings using light
assistance or a probe can be inserted for sampling the air stream. The
cover attachment shall prevent leaks.
Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90°° with wide duct pliers. See
. The supply-air
duct must be connected to ONLY the furnace supply-outlet-air duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace casing side to attach supply air duct, humidifier, or other
accessories. All supply-side accessories MUST be connected to duct
external to furnace main casing.
Return Air Connections
The return-air duct can only be connected to bottom of the furnace. sides
(left or right), or a combination of bottom and side(s) of main furnace
casing. Bypass humidifier may be attached into unused return air
side of the furnace casing. See
, and
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, see
A10493
Fig. 20 – Duct Flanges
NOTICE
!
This furnace is certified to leak 2% or less of nominal air conditioning
CFM delivered when pressurized to 1-in. water column with all present
air inlets, including bottom closure in upflow and horizontal
applications, air outlets, and plumbing and electrical ports sealed.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in nuisance limit switch
cycling and unit component damage.
When a 17-1/2-in. wide upflow N coil is used with a 0601714 furnace,
the N coil must either be raised using a transition piece at least 3-in. (76
mm) high or if a transition piece is not used, the refrigerant lines must
point to the front of the furnace casing.
Remove knockout.
Install grommet before
relocating condensate
trap.
NOTE: Trap grommet is required only for direct-vent
applications.
WARNING
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death
and/or property damage.
Never connect return-air ducts to the back of the furnace. Follow
instructions below.
LEVEL 0-IN. (0 MM) TO
1/2-IN. (13 MM) MAX
UPFLOW OR
DOWNFLOW
HORIZONTAL
MIN 1/4-IN. (6 MM) TO
1/2-IN. (13 MM) MAX
UPFLOW
DOWNFLOW
HORIZONTAL
YES
NO
NO
YES
YES
YES
NO
120
°
MIN
YES
120
°
MIN
YES
120
°
MIN
90
°
90
°
PERFORATED
DISCHARGE DUCT
FLANGE