background image

– 7 –

5

Drain piping work

CAUTION

Following the Installation Manual, perform the 
drain piping work so that water is properly 
drained, and apply a heat insulation so as not to 
cause a dew drop.
Inappropriate piping work may result in water 
leakage in the room and wet of furniture.

Piping/Heat insulating material

Require the following materials for piping and heat 
insulating at site.

Flexible hose

Use the attached flexible hose to adjust center 
discrepancy of the hard vinyl chloride pipe or to adjust 
the angle.
• Do not use the flexible hose as stretched, or do not 

deform it more extent than that in the following figure.

• Fix the soft end of the flexible hose with the attached 

hose band.

• Use the flexible hose on a horizontal level.

REQUIREMENT

• Perform heat insulation of the drain pipes of the indoor 

unit.

• Perform heat insulation of the connecting part with the 

indoor unit. 
An incomplete heat insulation causes dew drop.

• Set the drain pipe with downward slope (1/100 or 

more), and do not make swelling or trap on the piping. 
It may cause an abnormal sound.

• For length of the traversing drain pipe, restrict to 65’7” 

(20 m) or less.
In case of a long pipe, provide support brackets with 
interval of 4’11” - 6’7” (1.5 - 2 m) in order to prevent 
waving.

• Set the collective piping as shown in the below figure.

• Do not apply force to the connecting part of the drain 

pipe.

• The hard vinyl-chloride pipe cannot be directly 

connected to the drain pipe connecting port of the 
indoor unit.
For connection with the drain pipe connecting port, fix 
the attached flexible hose with the hose band, 
otherwise a damage or water leak is caused on the 
drain pipe connecting port.

Piping

Hard vinyl chloride pipe VP25 

(Outer dia.: Ø1.3" (32 mm))

Heat insulator

Foam polyethylene: 

Thickness 0.4" (10 mm) or more

OK

NO GOOD

Max

45°

Max

45°

90° Bend

Riser (Trap)

Support 

bracket

1/100 or more 

downward

Heat insulator

4’11” - 6’7” (1.5 - 2 m)

Arched

shape

Trap

NO 

GOOD

VP25

As long as possible (3.9” (100 mm))

Downward slope 

1/100 or more

VP30 or more

VP25

VP25

Connecting drain pipe

• Connect a hard socket (locally procured) to the hard 

socket of the attached supplied flexible hose.

• Connect a drain pipe (locally procured) to the 

connected hard socket.

REQUIREMENT

• Connect hard vinyl chloride pipes securely using an 

adhesive for vinyl chloride to avoid water leakage.

• It takes some time until the adhesive is dried and 

hardened (refer to the manual of the adhesive). Do not 
apply stress to the joint with the drain pipe during this 
time period.

Drain up

When a down-gradient cannot be secured for the 
drainpipe, drain-up piping is possible.
• The height of the drain pipe must be 33.5" (850 mm) 

or less from the bottom of the ceiling. 

• Take the drain pipe out of the drain pipe joint with the 

indoor unit in 11.8" (300 mm) or less, and bend up 
the pipe vertically. 

• Immediately after the pipe is bent up vertically, lay 

the pipe making a down-gradient. 

• Set downward grading immediately after raising up 

vertically. 

Check the draining

In the test run, check that water drain is properly 
performed and water does not leak from the connecting 
part of the pipes.
Check draining also when the unit is installed in heating 
period.
By using a pitcher or hose, pour water (0.4 - 0.5 gal 
(1500 - 2000 cc)) into the discharge port before 
installation of the ceiling panel.
Pour water gradually so that water does not spread on 
the motor of the drain pump.

CAUTION

Pour water gently so that it does not spread around 
inside the indoor unit, which may cause a malfunction.

Adhesive inhibited:

Use the attached flexible hose and hose band for 

connecting the drain hose to the clear drain socket.

If applying the adhesive, socket will be damaged and 

cause water leakage.

Drain pipe 

connecting port 

(Hard socket)

VP25 vinyl chloride pipe 

(locally procured)

Attached hose 

band

Attached flexible hose

Soft socket

Hard socket

Socket for VP25 

(locally procured)

In

doo

r un

it

Drain pipe 

connecting port 

(Transparent)

Flexible hose 

(Accessory)

Socket for VP25 vinyl 

chloride pipe 

(Locally procured)

VP25 vinyl chloride 

pipe 

(Locally procured)

In

do

or

 u

n

it

5 mm or less

10 mm

hose band tightening 

margin

Heat 

insulator

10 to 12 mm

Ris

ing up 26

.0

” 

(6

61

 mm

) or

 le

ss

Underside of ceiling

Indoor unit

11.8” (300 mm) 

or less

Ris

ing

 u

p 33

.5

” (8

50

 m

m

) or

 le

ss

13-EN

14-EN

+00EH99876001-3.book  Page 7  Wednesday, May 27, 2015  10:08 AM

Содержание MMU-AP0072H2UL

Страница 1: ...UL MMU AP0182H2UL MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL MMU AP0362H2UL MMU AP0422H2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial Installation Manual 1 English Manuel d installation 19 Français 00EH99876001 3 book Page 1 Wednesday May 27 2015 10 08 AM ...

Страница 2: ...y For the installation of these products follow the Installation Manuals supplied with them The wireless type remote control is designed to be installed by attaching a wireless remote control kit sold separately to the standard panel The wireless remote control kit consists of a wireless remote control and adjust corner caps with a signal receiving unit Part name Qty Shape Usage Installation Manua...

Страница 3: ...is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure ...

Страница 4: ...e the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter type fluorescent light is installed...

Страница 5: ...ng can be raised Refer to 8 Applicable controls in this manual for the setting procedure Discharge direction As shown in the figure below air discharge directions can be selected according to the shape of the room and the location of the indoor unit installation Model MMU Possible installed ceiling height AP007 to AP030 Type Up to 12 6 3 8 m AP036 AP042 Type Up to 15 1 4 6 m Model MMU AP007 AP009 ...

Страница 6: ... of the indoor unit installation and orientation After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe control wires and remote control wire...

Страница 7: ...use water leakage Hanging bolt Level Hanging bracket Washer Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bol...

Страница 8: ...ocally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket REQUIREMENT Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage It takes some time until the adhesive is dried and hardened refer to the manual of the adhesive Do not apply stress to the joint with the drain ...

Страница 9: ... 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Remov...

Страница 10: ... be faced upward ceiling side Banding band Locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes ...

Страница 11: ... control wiring remote control inter unit wiring Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor u...

Страница 12: ...ck Conduit connection hole Piping Knockout Bushing of control and remote control wires Lock nut Conduit pipe Conduit plate Remote control terminal block Cord clamp Side D Space 0 33 8 5 mm Side C Space 0 16 4 mm Insert the wire to Side C Ground screw Ground screw for shielded wire control wire Power supply wires and ground wire 1 Strip the wire ends Power supply wire 0 4 10 mm Ground wire 0 8 20 m...

Страница 13: ...nit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor ...

Страница 14: ...ion is selected ceiling contamination is less reduced SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA Louver direction setting 0000 Smudge reducing position Air direction to...

Страница 15: ...er indoor unit Non polarity For address setup refer to the Installation Manual attached to the outdoor unit UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA 0001 0005 SET DATA SET DATA 0000 0001 Remote control sensor Not used factory default Used 0000 SET DATA 9 Test run Before test run Before turning on the circuit breaker carry out the following procedu...

Страница 16: ...test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and ...

Страница 17: ...I F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error i...

Страница 18: ...red remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valv...

Страница 19: ...EH99876001 3 00EH99876001 3 book Page 39 Wednesday May 27 2015 10 08 AM ...

Отзывы: