background image

3

C

TDR

LPS

LPS

C

TDR

T

LOW-PRESSURE SWITCH
CONTACTOR COIL
TIME DELAY RELAY
RELAY COIL

FACTORY WIRING
FIELD WIRING

T

A93165

Fig. 5

Low Voltage Wiring for Winter Start Control

START--UP

To start units equipped with the low--ambient pressure switch,

perform the following steps:

1. Turn power on to unit.
2. Set thermostat below room temperature.
3. Wait for the unit to start. There may be a 5--minute delay

in the thermostat or in the outdoor unit.

4. Observe unit operation as described below.

a. The fan will be off when compressor starts.

b. At outdoor temperatures around 0

_

F, fan may not run

at all.

c. At summer temperatures, fan will start after 10 to 30

sec of compressor operation and may not turn off until

thermostat is satisfied.

d. At outdoor ambients between 80

_

F and 20

_

F, fan will

turn on and off to maintain pressure as shown in Table

1.

KS

A

LA

Содержание KSALA0201R22

Страница 1: ...sories may be required Refer to the Required Changes for Cooling Units and Heat Pump Units section DESCRIPTION AND USAGE The low ambient pressure switch kit is a long life pressure switch which turns the fan on and off as shown in Table 1 It is wired in series with black fan lead Sleeve bearing motors can be used with this control INSTALLATION The pressure switch is mounted inside the outdoor unit...

Страница 2: ...ired to provide better airflow for moderate and high ambient temperatures Check pre sale literature for available support feet or unit risers CUT HAZARD Failure to follow this caution could result in personal injury To reduce risk of personal injury wear personal protective equipment when working with wind baffles Only experienced technicians should fabricate and install wind baffles CAUTION 5 For...

Страница 3: ...ow room temperature 3 Wait for the unit to start There may be a 5 minute delay in the thermostat or in the outdoor unit 4 Observe unit operation as described below a The fan will be off when compressor starts b At outdoor temperatures around 0_F fan may not run at all c At summer temperatures fan will start after 10 to 30 sec of compressor operation and may not turn off until thermostat is satisfi...

Страница 4: ...6 TYP G J K E D L 9 64 3 45 DIA HOLE 1 REQ D 7 32 5 56 DIA HOLE 3 REQ D 7 32 x 2 5 56 x 50 8 SLOT 1 4 6 3 TYP BAFFLE MAT L 20 GA STEEL SUPPORT MAT L 18 GA STEEL 9 64 3 45 DIA HOLE 2 REQ D OUTDOOR UNIT F AA SCREW 10 REQ D SUPPORT 4 REQ D BAFFLE 2 REQ D BAFFLE ASSEMBLY 1 4 6 3 TYP A95444 Fig 6 Carrier WeatherMaker Units KSALA ...

Страница 5: ...5 3 16 42 15 15 16 35 3 4 36 1 2 50 7 16 35 11 16 36 7 16 35 5 8 22 11 16 17 7 8 7 1 16 Wind Baffle Dimensions for Carrier WeatherMaker Units with Silencer System Top In Unit Size AA Unit Height A B C D E F G H J K L M Small 27 1 2 23 13 16 17 25 1 4 10 3 8 19 3 4 20 1 2 34 19 11 16 20 7 16 19 5 8 0 0 6 1 8 27 13 16 17 25 1 4 10 3 8 23 3 4 24 1 2 34 23 11 16 24 7 16 23 5 8 0 11 7 8 6 1 8 33 13 16 ...

Страница 6: ...L 1 8 3 45 DIA HOLE 1 REQ D 1 4 5 56 DIA HOLE 3 REQ D 1 4 x 2 5 56 x 50 8 SLOT 1 4 6 3 BAFFLE MAT L 20 GA STEEL SUPPORT MAT L 18 GA STEEL 1 8 3 45 DIA HOLE 2 REQ D 3 8 9 6 6 152 4 1 4 5 56 DIA HOLE 2 REQ D OUTDOOR UNIT BAFFLE ASSEMBLY SCREW 10 REQ D SUPPORT 4 REQ D BAFFLE 2 REQ D AA A95445 Fig 7 Bryant Reliant Units KSALA ...

Страница 7: ... 14 7 8 37 7 8 25 5 16 39 3 4 10 1 4 35 3 4 36 1 2 50 9 16 35 5 8 36 3 8 35 5 8 21 11 16 17 7 8 Wind Baffle Dimensions for Bryant Reliant Units with AeroQuiet Top In Unit Size AA Unit Height A B C D E F G H J K L Small 26 3 16 23 13 16 17 1 4 24 5 16 10 1 4 19 3 4 20 1 2 34 1 2 19 5 8 20 3 8 19 5 8 0 0 27 13 16 17 1 4 24 5 16 10 1 4 23 3 4 24 1 2 34 1 2 23 5 8 24 3 8 23 5 8 0 11 7 8 33 13 16 17 1 ...

Страница 8: ...5 56 DIA 2 REQ D 25 64 10 0 E 7 7 8 200 0 3 16 4 6 1 8 3 45 DIA 2 REQ D BAFFLE LEFT MAT L 20 GA STEEL F C 5 3 64 128 0 1 2 12 7 TYP E 7 29 32 200 8 BAFFLE RIGHT MAT L 20 GA STEEL A D 1 21 32 42 1 25Ú64 10 0 2 1 2 63 5 G 1 4 5 56 DIA 4 REQ D J C AA H J 1 4 6 4 23 64 9 2 1 2 12 7 TYP 8 5 64 205 3 TYP 4 57Ú64 124 2 TYP 2 5 64 52 6 4 9 64 105 2 45 TYP 1 8 3 45 DIA 4 REQ D 1 4 5 56 DIA 2 REQ D 23 64 9 ...

Страница 9: ...1 16 24 3 4 16 3 16 8 1 4 25 13 16 23 13 16 29 15 16 27 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 27 13 16 25 13 16 31 15 16 29 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 29 13 16 27 13 16 33 15 16 31 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 31 13 16 29 13 16 37 15 16 33 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 33 13 16 31 13 16 39 15 16 35 7 8 18 5 16 32 5 8 10 11 16 ...

Страница 10: ... 2 REQ D 1 8 3 45 DIA HOLE 3 REQ D WIND BAFFLE 1 2 12 7 1 25 4 5 5 16 134 2 7 16 11 8 3 8 10 3 G H 7 16 11 8 3 8 10 3 1 2 12 7 1 4 6 35 x 1 2 12 7 SLOT 2 REQ D 1 8 3 45 DIA HOLE 3 REQ D SUPPORT B RIGHT AND LEFT HAND REQ D J 3 76 2 1 25 4 x 3 76 2 NOTCH THIS SIDE BAFFLE SUPPORT B BAFFLE SUPPORT A WIND BAFFLE BAFFLE ASSEMBLY SUPPORT A A95447 Fig 9 Payne Units Models PA10 PA12 and PH10 PH12 KSALA ...

Страница 11: ... 16 17 5 16 10 13 16 37 15 16 36 11 16 18 5 16 107 1 16 86 9 16 54 11 16 22 3 4 24 11 16 18 5 16 10 13 16 Wind Baffle Dimensions for Payne PH10 PH12 Heat Pump Units In Unit Size AA Unit Height A B C D E F G H J Medium 22 1 2 21 15 16 18 11 16 9 5 16 81 1 2 67 7 8 41 13 16 15 13 16 18 11 16 9 5 16 14 13 16 23 15 16 20 11 16 10 5 16 81 1 2 67 7 8 41 13 16 15 13 16 18 11 16 10 5 16 14 13 16 25 15 16 ...

Страница 12: ...12 A06235 Fig 10 Base Comfortt Legacyt Units Baffle Assembly KSALA ...

Страница 13: ...16 5 16 11 9 16 47 3 8 28 15 16 23 13 16 11 3 4 9 3 8 16 5 16 11 9 16 47 3 8 32 5 16 27 3 16 13 1 2 9 3 8 16 5 16 11 9 16 47 3 8 35 3 4 30 5 8 15 3 16 9 3 8 16 5 16 11 9 16 47 3 8 39 1 8 34 16 7 8 9 3 8 16 5 16 11 9 16 47 3 8 42 1 2 37 3 8 18 9 16 9 3 8 16 5 16 11 9 16 47 3 8 45 15 16 40 13 16 20 1 4 9 3 8 16 5 16 11 9 16 47 3 8 Large 35 25 1 2 20 3 8 10 1 16 13 3 16 20 1 8 15 3 8 51 1 8 28 15 16 ...

Страница 14: ...14 BAFFLE 1 MATL 20 GA STEEL A06231 BAFFLE ASSEMBLY A06230 Fig 11 Performancet and Preferredt Series Baffle Assemblies KSALA ...

Страница 15: ...15 BAFFLE 2 MATL 20 GA STEEL A06232 BAFFLE 3 MAT L 20 GA STEEL A06234 Fig 12 Performancet and Preferredt Series Baffle Assemblies continued KSALA ...

Страница 16: ...16 SUPPORT MAT L 20 GA STEEL A06233 Fig 13 Performancet and Preferredt Series Baffle Assemblies continued KSALA ...

Страница 17: ... 5 16 80 2 16 11 16 78 8 17 3 8 51 1 16 49 15 16 40 13 16 20 3 8 22 5 16 80 2 16 11 16 78 8 17 3 8 51 1 16 Wind Baffle Dimensions for Preferredt Series Units Unit Size AA Unit Height A In B In C In D degrees E In F degrees G In H In Medium 33 30 23 13 16 11 7 8 16 81 9 16 3 8 80 3 12 3 4 45 7 8 33 7 16 27 3 16 13 5 8 16 81 9 16 3 8 80 3 12 3 4 45 7 8 36 13 16 30 5 8 15 5 16 16 81 9 16 3 8 80 3 12 ...

Страница 18: ...Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No AG SALA 07 Replaces AG SALA 05 Printed in U S A Edition Date 5 06 KSALA ...

Отзывы: