Fig. 8 -- Horizontal Furnace External Trap with Condensate Trap Kit for Vent Above Floor

TURN UP TO
BOTTOM OF
FLOOR JOISTS

C

B

A

D & E

F

A: 1 ft. Max
B: 30˝ Max
C: Heat Tape Required
F: Elbow directly into trap

To Code Approved
Drain or Condensate Pump

D: Slope Back to Trap
E: 60 ft. Max Length

A05290

Fig. 9 -- Horizontal Furnace with ETK Under Furnace

FURNACE

PIPE DIAMETER

TRANSITION IN

VERTICAL SECTION

NOT IN

HORIZONTAL

SECTION

A99124

Fig. 10 -- Combustion--Air and Vent Pipe Diameter Transition Location and Elbow Configuration

Содержание KGAET0101ETK

Страница 1: ...rimers and cements from one manufacturer with a vent system from a different manufacturer Follow the manufacturer s instructions in the use of primer and cement and never use primer or cement beyond i...

Страница 2: ...kit contains the following items Condensate trap 1 Tee vent fitting 2 in 51 mm PVC 1 Bushing vent fitting 2 x 1 1 2 in 51 x 38 mm PVC 1 Adapter fitting 1 1 2 38 mm male x 1 1 2 38 mm female 1 INSTALLA...

Страница 3: ...fitting in place 7 Cement bushing supplied in kit in bottom tee vent fitting connection 8 Position condensate trap supplied in kit in bushing such that drain connection is positioned for suitable fie...

Страница 4: ...ondensate trap sides 4 Wrap field drain pipe with remaining heat tape approximately one wrap per ft 5 When using field supplied heat tape follow heat tape manufacturer s instructions for all other ins...

Страница 5: ...p and Trap Kit for Vent Above Floor A99082 Fig 4 Upflow Furnace Left Side Outlet with Blower Com partment Condensate Trap Location and Trap Kit for Vent Above Floor A99083 Fig 5 Downflow Furnace Left...

Страница 6: ...e Approved Drain A Restricted to maximum of 60 B Restricted to maximum of 24 below flooring D Pipe must slope back to external drain trap E Pipe must be insulated when exposed to freezing temperatures...

Страница 7: ...C Heat Tape Required F Elbow directly into trap To Code Approved Drain or Condensate Pump D Slope Back to Trap E 60 ft Max Length A05290 Fig 9 Horizontal Furnace with ETK Under Furnace FURNACE PIPE DI...

Страница 8: ...0 12 20 29 2 5 64 38 12 21 6 40 12 40 12 20 7 3 76 70 21 63 19 70 21 70 21 0 18 3 76 50 15 30 9 70 21 70 21 20 29 3 76 28 9 12 4 70 21 70 21 120 20 7 3 76 70 21 70 21 70 21 70 21 0 18 3 76 61 19 38 12...

Отзывы: