PHYSICAL DATA
UNIT SIZE
024
030
036
042
048
060
NOMINAL CAPACITY ton
2
2--1/2
3
3--1/2
4
5
OPERATING WEIGHT lb
(kg)
363
(165)
368
(167)
447
(203)
469
(213)
475
(215)
526
(239)
COMPRESSOR
Two--Stage Scroll
REFRIGERANT: PURON (R--410A) Quantity lb
(kg)
10.1
(4.6)
11.3
(5.1)
9.5
(4.3)
13.8
(6.3)
15.3
(6.9)
15.8
(7.2)
REFRIGERANT METERING DEVICE
TXV
Size
2 Ton
3 Ton
3 Ton
4 Ton
4 Ton
5 Ton
Part Number
EA36DY129
EA36DY139
EA36DY139
EA36DY149
EA36DY149
EA36DY159
OUTDOOR COIL
Rows
…
Fins/in.
2
…
21
2
…
21
2
…
21
2
…
21
2
…
21
2
…
21
Face Area (sq. ft.)
13.6
15.3
17.5
19.4
19.4
23.3
OUTDOOR FAN
Nominal Cfm
2700
2700
2800
2800
3300
3300
Diameter (in.)
(mm)
22
559
22
559
22
559
22
559
22
559
22
559
Motor HP (RPM)
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/4 (1100)
1/3 (1110)
INDOOR COIL
Rows
…
Fins/in.
3
…
17
3
…
17
3
…
17
3
…
17
3
…
17
4
…
17
Face Area (sq. ft.)
3.7
3.7
4.7
4.7
5.7
5.7
INDOOR FAN
Nominal Airflow (Cfm)
Comfort
Variable based on Comfort Settings (see User Interface instructions for more information).
Efficiency
700
875
1050
1225
1400
1750
Max
800
1000
1200
1400
1600
2000
Size in.
(mm)
10x10
(254x254)
10x10
(254x254)
11x10
(279x254)
11x10
(279x254)
11x10
(279x254)
11x10
(279x254)
Motor HP (RPM)
1/2
1/2
3/4
3/4
3/4
1
HIGH--PRESSURE SWITCH (psig)
Cutout
670
±
10
Reset (Auto)
470
±
25
HIGH--PRESSURE SWITCH 2 (psig)
(Compressor Solenoid
)
Cutout
565
±
15
Reset (Auto)
455
±
15
LOSS--OF--CHARGE/LOW--PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
23
±
5
Reset (Auto)
55
±
5
RETURN--AIR FILTERS
Throwaway
in.*
20x24x1
(508x610x25)
24x30x1
(610x762x25)
24x36x1
(610x914x25)
(mm)
*Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on
the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft (91.4 m) /minute for throwaway type
or 450 ft (137 m) /minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 in. wc.
A--Weighted Sound Power Level (dBA)
MODEL
50XL
Sound Ratings
(dBA)
Typical Octive Band Spectrum (dBA without tone adjustment)
125
250
500
1000
2000
4000
8000
024
75
58.8
63.5
67.2
66.9
63.7
58.3
50.0
030
75
58.8
63.5
67.2
66.9
63.7
58.3
50.0
036
75
63.7
63.3
66.8
66.5
64.2
60.3
53.0
042
75
62.8
62.8
67.8
67.4
63.7
57.7
50.8
048
78
69.9
69.9
71.3
73.4
70.0
66.3
60.1
060
78
67.6
67.6
71.8
75.5
71.0
68.1
59.9
NOTE
: Tested in accordance with ARI Standard 270---95 (not listed in ARI).