Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
27
50YCS018 / 38WQS018 With GAH018
Performance capacities shown in thousands of Btuh.
WPD
HEATING - EAT 70
°
F
COOLING - EAT 80/67
°
F
EWT
°
F
GPM
PSI
FT
CFM
HC
KW
HE
LAT
COP
HWC
TC
SC
KW
HR
EER
HWC
2.2
0.5
1.2
475
600
Operation not recommended
20
3.5
1.2
2.7
475
Operation not recommended
600
4.5
1.8
4.2
475
11.8
1.19
7.7
92.9
2.89
1.3
600
12.1
1.12
8.2
88.6
3.17
1.2
2.2
0.5
1.2
475
12.9
1.22
8.7
95.2
3.10
1.5
20.7
12.9
0.80
23.4
26.0
0.5
600
13.2
1.14
9.3
90.4
3.40
1.3
22.1
14.7
0.80
24.9
27.5
0.5
30
3.5
1.1
2.6
475
13.5
1.23
9.3
96.4
3.22
1.6
20.9
12.9
0.75
23.5
27.9
0.6
600
13.9
1.16
9.9
91.4
3.52
1.3
22.3
14.7
0.76
24.9
29.5
0.5
4.5
1.8
4.1
475
13.8
1.24
9.6
96.9
3.26
1.6
20.9
12.9
0.74
23.5
28.3
0.6
600
14.1
1.16
10.2
91.8
3.57
1.4
22.4
14.7
0.75
24.9
30.0
0.5
2.2
0.5
1.1
475
14.8
1.26
10.5
98.9
3.44
1.8
20.3
12.9
0.87
23.2
23.2
1.0
600
15.2
1.18
11.2
93.4
3.77
1.5
21.7
14.7
0.88
24.7
24.6
0.9
40
3.5
1.1
2.5
475
15.6
1.28
11.3
100.5
3.58
1.8
20.6
12.9
0.81
23.4
25.6
0.9
600
16.0
1.20
11.9
94.7
3.92
1.6
22.1
14.7
0.81
24.8
27.1
0.8
4.5
1.7
3.9
475
16.0
1.29
11.6
101.1
3.63
1.9
20.8
12.9
0.79
23.4
26.4
0.8
600
16.4
1.21
12.2
95.2
3.98
1.7
22.2
14.7
0.79
24.9
27.9
0.8
2.2
0.5
1.1
475
16.8
1.31
12.4
102.8
3.78
2.0
19.7
12.7
0.97
23.0
20.3
1.4
600
17.2
1.22
13.1
96.6
4.13
1.8
21.0
14.6
0.98
24.3
21.4
1.3
50
3.5
1.1
2.5
475
17.8
1.33
13.3
104.7
3.93
2.1
20.2
12.8
0.89
23.2
22.7
1.2
600
18.2
1.24
14.0
98.1
4.31
1.8
21.6
14.7
0.90
24.6
24.0
1.2
4.5
1.7
3.8
475
18.2
1.33
13.6
105.5
4.00
2.2
20.3
12.9
0.86
23.3
23.7
1.0
600
18.6
1.25
14.4
98.8
4.38
1.9
21.7
14.7
0.87
24.7
25.0
1.1
2.2
0.5
1.0
475
18.9
1.35
14.3
106.8
4.10
2.3
18.9
12.5
1.08
22.6
17.4
1.7
600
19.3
1.26
15.0
99.9
4.49
2.0
20.2
14.3
1.09
23.9
18.4
1.6
60
3.5
1.0
2.4
475
20.0
1.37
15.3
109.0
4.28
2.4
19.5
12.7
0.99
22.9
19.7
1.5
600
20.5
1.28
16.1
101.6
4.69
2.1
20.9
14.5
1.00
24.3
20.9
1.5
4.5
1.6
3.7
475
20.5
1.38
15.8
109.9
4.35
2.4
19.7
12.8
0.96
23.0
20.6
1.3
600
21.0
1.29
16.6
102.4
4.77
2.2
21.1
14.6
0.97
24.4
21.8
1.4
2.2
0.4
1.0
475
21.0
1.39
16.2
110.8
4.43
2.6
18.0
12.2
1.21
22.2
14.9
2.0
600
21.5
1.30
17.0
103.1
4.84
2.2
19.3
13.9
1.22
23.4
15.8
2.0
70
3.5
1.0
2.3
475
22.3
1.41
17.4
113.4
4.62
2.6
18.7
12.5
1.11
22.5
16.9
1.8
600
22.8
1.32
18.3
105.2
5.06
2.3
20.0
14.2
1.12
23.8
17.9
1.8
4.5
1.5
3.6
475
22.8
1.42
17.9
114.4
4.70
2.7
19.0
12.6
1.07
22.6
17.7
1.6
600
23.4
1.33
18.8
106.0
5.14
2.4
20.3
14.3
1.08
24.0
18.8
1.7
2.2
0.4
1.0
475
23.1
1.43
18.2
114.9
4.74
2.9
17.1
11.8
1.34
21.7
12.7
2.2
600
23.6
1.34
19.1
106.5
5.18
2.4
18.3
13.5
1.36
22.9
13.5
2.3
80
3.5
1.0
2.2
475
24.5
1.45
19.5
117.8
4.94
3.0
17.8
12.1
1.24
22.1
14.4
2.1
600
25.1
1.36
20.5
108.8
5.41
2.5
19.1
13.8
1.25
23.3
15.3
2.2
4.5
1.5
3.5
475
25.1
1.46
20.1
118.9
5.03
3.1
18.1
12.2
1.20
22.2
15.1
1.9
600
25.7
1.37
21.1
109.7
5.51
2.7
19.4
14.0
1.21
23.5
16.0
2.0
2.2
0.4
0.9
475
25.1
1.46
20.2
119.0
5.04
3.1
16.1
11.3
1.48
21.1
10.9
2.5
600
25.8
1.37
21.1
109.8
5.51
2.7
17.2
12.9
1.49
22.3
11.5
2.6
90
3.5
0.9
2.1
475
26.7
1.49
21.6
122.1
5.26
3.3
16.8
11.7
1.37
21.5
12.3
2.4
600
27.4
1.40
22.6
112.3
5.76
2.8
18.0
13.3
1.39
22.7
13.0
2.5
4.5
1.4
3.3
475
27.4
1.50
22.3
123.4
5.35
3.4
17.1
11.8
1.33
21.7
12.8
2.3
600
28.1
1.40
23.3
113.3
5.85
2.9
18.3
13.5
1.35
22.9
13.6
2.3
2.2
0.4
0.9
475
15.0
10.7
1.62
20.5
9.3
2.9
600
16.1
12.2
1.63
21.6
9.8
3.0
100
3.5
0.9
2.1
475
15.8
11.1
1.52
21.0
10.4
2.7
600
16.9
12.7
1.53
22.1
11.0
2.8
4.5
1.4
3.2
475
16.1
11.3
1.48
21.1
10.9
2.5
600
Operation not recommended
17.2
12.9
1.49
22.3
11.6
2.6
2.2
0.4
0.9
475
14.0
10.1
1.75
20.0
8.0
3.2
600
14.9
11.5
1.77
21.0
8.4
3.3
110
3.5
0.9
2.0
475
14.7
10.5
1.66
20.4
8.9
3.0
600
15.7
12.0
1.67
21.5
9.4
3.1
4.5
1.3
3.1
475
15.0
10.7
1.62
20.6
9.3
2.8
600
16.1
12.2
1.63
21.6
9.8
2.9
Rev: 12/12/03 B
Operation below 40
°
F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80
°
F DB and 67
°
F WB in cooling and 70
°
F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.