Carrier GT-GS Indoor Split Series Скачать руководство пользователя страница 9

9

R e s i d e n t i a l   S p l i t   -   6 0 H z   R 2 2   & R 4 1 0 A

R e v. :   5   J u n e ,   2 0 0 8

C a r r i e r :   Tu r n   t o   t h e   E x p e r t s

Installation

NOTICE! 

 Failure to remove shipping brackets from spring-

mounted compressors will cause excessive noise, and could 
cause component failure due to added vibration.

The installation of water source heat pump units and all 
associated components, parts and accessories which make 
up the installation shall be in accordance with the regulations 
of ALL authorities having jurisdiction and MUST conform to 
all applicable codes. It is the responsibility of the installing 
contractor to determine and comply with ALL applicable 
codes and regulations.

Removing Existing Condensing Unit (Where Applicable)

1.  Pump down condensing unit. Close the liquid line 

service valve of existing condensing unit and start 
compressor to pump refrigerant back into compressor 
section. Then, close suction service valve while 
compressor is still running to trap refrigerant in outdoor 
section. Immediately kill power to the condensing unit.

2.  Disconnect power and low voltage and remove old 

condensing unit. Cut or unbraze line set from unit. 
Remove condensing unit.

3.  If condensing unit is not operational or will not pump 

down, refrigerant should be recovered using appropriate 
equipment.

4.  Replace line set, especially if upgrading system from R-

22 to R-410A refrigerant. If line set cannot be replaced, 
it must be thoroughly 

fl

 ushed before installing new 

compressor section. R-410A compressors use POE 
oil instead of mineral oil (R-22 systems). Mineral oil is 
not compatible with POE oil, and could cause system 
damage if not completely 

fl

 ushed from the line set.

“Indoor” Compressor Section Location

Both “indoor” and “outdoor” versions of the geothermal split 
system compressor section are available. “Indoor” version 
is not designed for outdoor installation. Locate the unit 
in an INDOOR area that allows enough space for service 
personnel to perform typical maintenance or repairs without 
removing unit. Units are typically installed in a mechanical 
room or closet. Never install units in areas subject to freezing 
or where humidity levels could cause cabinet condensation 
(such as unconditioned spaces subject to 100% outside air). 
Consideration should be given to access for easy removal 
of service access panels. Provide suf

fi

 cient room to make 

water, electrical, and line set connections. 

Any access panel screws that would be dif

fi

 cult to remove 

after the unit is installed should be removed prior to setting 
the unit. Refer to Figure 2 for an illustration of a typical 
installation. Refer to “Physical Dimensions” section for 
dimensional data. Conform to the following guidelines when 
selecting unit location:
1.   Install the unit on a piece of rubber, neoprene or other 

mounting pad material for sound isolation. The pad should 
be at least 3/8” [10mm] to 1/2” [13mm] in thickness. 
Extend the pad beyond all four edges of the unit.

2.   Provide adequate clearance for maintenance and 

service. Do not block access panels with piping, conduit 
or other materials. 

3.   Provide access for servicing the compressor and coils 

without removing the unit.

4.   Provide an unobstructed path to the unit within the 

closet or mechanical room. Space should be suf

fi

 cient to 

allow removal of the unit, if necessary.

5.   In limited side access installations, pre-removal of the 

control box side mounting screws will allow control box 
removal for future servicing (R22 units only).

6.   Provide access to water valves and 

fi

 ttings and 

screwdriver access to the unit side panels and all 
electrical connections.

“Outdoor” Compressor Section Loacation

Locate the unit in an outdoor area that allows easy loop 
and lineset access and also has enough space for service 
personnel to perform typical maintenance or repairs. The 
“outdoor” compressor section is usually installed on a 
condensor pad directly outside the lineset access into the 
building. The service valve side can be located toward 
the building, keeping the loop access end away from the 
building. Conform to the following guidelines when selecting 
unit location:
1.   Provide adequate access for loop trench excavation.
2.   Locate unit directly outside lineset penetration if possible. 

Utilize existing condensor pad where possible.

3.   Provide access for servicing and maintenance.

“Outdoor” compressor section may be mounted on a 
vibration isolation pad with loop access hole as shown in 
Figure 3. When mounting on an existing concrete condenser 
pad, 3” [76mm] holes should be bored through the pad to 
accomodate the pipe (1-1/4” - 32mm) and insulation (1/2” 
[13mm] wall thickness). Figure 3 illustrates location and 
dimensions of the holes required.

Air Handler Installation

This manual speci

fi

 cally addresses the compressor section 

of the system. Air handler location and installation should 
be according to the instructions provided with the air 
handling unit.

Содержание GT-GS Indoor Split Series

Страница 1: ...tions 10 11 Ground Loop Applications 11 13 Open Loop Ground Water Systems 14 15 Water Quality Standards 16 Refrigeration Installation 17 22 Lineset Information 17 Hot Water Generator 23 24 Electrical...

Страница 2: ......

Страница 3: ...1 Current Revision Standard Copper Cupro Nickel C N SS Standard 3 208 230 60 1 048 060 D COPPER WATER COIL W HOT WATER GENERATOR N CUPRO NICKEL WATER COIL P CUPRO NICKEL WATER COIL W HOT WATER GENERA...

Страница 4: ...t and debris which may cause system damage WARNING WARNING WARNING CAUTION Safety Warnings cautions and notices appear throughout this manual Read these items carefully before attempting any installat...

Страница 5: ...unit configurations are typically installed in a mechanical room The installation site chosen should include adequate service clearance around the unit Before unit start up read all manuals and become...

Страница 6: ...rrier Geothermal split system heat pumps are rated in the ARI directory with a specific indoor coil match GT PX Split 50YDS models are rated with Carrier Bryant FV4 or FE4 series variable speed air ha...

Страница 7: ...y requirements as listed above The air handler capacity must be at least at the minimum capacity shown in the table in order for the ARI rating condition to be valid See Figure 1 for an example select...

Страница 8: ...propriate match Figure 1 Selecting Air Handler Equipment Selection Utilizing the Existing Air Handler or Coil R22 units only It is recommended that a new coil or air handler be installed with any geot...

Страница 9: ...water electrical and line set connections Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figure 2 for an il...

Страница 10: ...d Tighten Only Do Not Overtighten Figure 4 Water Connections Indoor Compressor Section Water Connections Residential Distributor Models Residential models utilize swivel piping fittings for water conn...

Страница 11: ...oop earth coupled heat pump systems Instructions are provided to assist the contractor in installing trouble free ground loops These instructions are recommendations only State provincial and local co...

Страница 12: ...id level drop is your only indication of air in the loop Antifreeze may be added before during or after the flushing procedure However depending upon which time is chosen antifreeze could be wasted wh...

Страница 13: ...mage unit wiring by chewing on the insulation NOTICE Outdoor compressor section may not be tilted more than 5 degrees from level Damage to the compressor or stress on the loop piping could result if u...

Страница 14: ...ogging should be referenced in Table 3 Expansion Tank and Pump Use a closed bladder type expansion tank to minimize mineral formation due to air exposure The expansion tank should be sized to provide...

Страница 15: ...water regulating valves should never be used with Carrier Geothermal equipment CAUTION CAUTION Many units installed with a factory or field supplied manual or electric shut off valve DAMAGE WILL OCCU...

Страница 16: ...Z JHZ JVTWVULU Z HYL 62 V TTVUPH PVU HZ O KYV_PKL JOSVYPKL UP YH L HUK Z SMH L JVTWV UKZ SS WWT 4H_PT T 4H_PT T SSV HISL H TH_PT T H LY LTWLYH YL OSVYPKL 3L LSZ 100 F 38 VWWLY WWT 59 NR WYV5PJRLS WWT...

Страница 17: ...s kinked or distorted and it cannot be formed back into its original shape the damaged portion of the line should be replaced A restricted line set will effect the performance of the system A reversib...

Страница 18: ...gized to avoid blowing hot air directly into the coil elevating refrigerant pressures during operation The heat pump will trip out on high pressure lockout without some method of disengaging the compr...

Страница 19: ...on Compressor Section TXV IN toward Compressor Section TXV IN toward Compressor Section Figure 12a Typical Split Air Handler Installation Indoor Compressor Section Insulated Linesets Low Voltage Air p...

Страница 20: ...Compressor Section Refrigeration Installation Insulated line set with UV Paint Power Disconnects PVC Condensate with vented trap Pad Low Voltage Wiring Return Plenum Compressor Section Air Handler TXV...

Страница 21: ...Graph Charging The System There are two methods of charging a refrigerant system One method is the total charge method where the volume of the system is determined and the refrigerant is measured and...

Страница 22: ...ading depending on the location of the measurement Therefore it is recommended that charging be monitored in the heating mode Charge should be evaluated by monitoring the subcooling in the heating mod...

Страница 23: ...piping connections on a unit with built in pump This piping layout minimizes scaling potential Electric water heaters are recommended If a gas propane or oil water heater is used a second preheat tan...

Страница 24: ...h point Cold Inlet Hot Outlet Coaxial Fitting Insulated water lines 5 8 OD 50 ft 15m maximum Water Heater Upper element to 120 130 F 49 54 C Lower element to 100 110 F 38 43 C Water Tank Refill Figure...

Страница 25: ...ose to the water heater as possible Unbraze the hot gas u bend as shown in Figure 19 Take care to avoid overheating components Install the dual 1 2 lineset to the HWG Maximum length should be 30 feet...

Страница 26: ...lumbing and electrical building codes take precedence over instructions contained herein The Manufacturer accepts no liability for equipment damaged and or personal injury arising from improper instal...

Страница 27: ...ze based on 60 C copper conductor and Minimum Circuit Ampacity Rated Voltage of 208 230 60 1 Min Max Voltage of 197 254 HACR circuit breaker in USA only All fuses Class RK 5 Wire length based on one w...

Страница 28: ...wires to the L side of the contactor as shown in Figures 21a through 21c Consult Tables 8a through 8c for correct fuse size 208 230 Volt Operation Verify transformer tap with air handler wiring diagra...

Страница 29: ...This connection can also serve as a HWG disable when servicing the unit HWG Wiring Outdoor Compressor Section The HWG module should be wired to the outdoor section pump controls see Figure 20 A safety...

Страница 30: ...n The CXM control allows the field selection of low water or water antifreeze solution temperature limit by clipping jumper JW3 which changes the sensing temperature associated with thermistor FP1 Not...

Страница 31: ...will operate properly with the following notations 1 The valve will remain open during a unit lockout 2 The valve will draw approximately 25 35 VA through the Y signal of the thermostat Note This val...

Страница 32: ...ump thermostat will work with these units provided it has the correct number of heating and cooling stages Y O G R C Y O G R C W1 W2 W E Typical Air Handler Typical T stat CXM Board Compressor Section...

Страница 33: ...ation options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the UPS feature On Enabl...

Страница 34: ...the initial 60 seconds of a compressor run cycle FP1 is set at the factory for one try Therefore the control will go into lockout mode once the FP1 fault has occurred FP1 lockout code 4 Air coil low t...

Страница 35: ...2 heating 1 Stage 2 heating 3 Stage 2 heating 5 G Y1 Y2 W Stage 3 heating 1 Stage 3 heating 3 N A G W Emergency heat Emergency heat Emergency heat G Y or Y1 O Stage 1 cooling 2 Stage 1 cooling 4 Cool...

Страница 36: ...an be used if anticipation current is less than that specified above Thermostat Signals Y and W have a 1 second recognition time when being activated or being removed O and G are direct pass through s...

Страница 37: ...of operating limits is dependent primarily upon three factors 1 return air temperature 2 water temperature and 3 ambient temperature When any one of these factors is at minimum or maximum levels the...

Страница 38: ...ance trip outs and high velocity water flow that could erode heat exchangers Unit air coil and filters Insure that filter is clean and accessible Clean air coil of all manufacturing oils Unit controls...

Страница 39: ...h 12b f Check air temperature drop across the air coil when compressor is operating Air temperature drop should be between 15 F and 25 F 8 C and 14 C g Turn thermostat to OFF position A hissing noise...

Страница 40: ...0 12 0 1 1 2 2 3 9 4 5 0 9 2 1 3 6 4 2 0 8 2 0 3 2 3 8 0 7 1 8 3 1 3 5 064 7 0 10 5 14 0 15 0 0 5 1 9 3 9 4 8 0 3 1 8 3 5 4 3 0 2 1 7 3 2 3 9 0 1 1 6 2 9 3 5 Model GPM Pressure Drop psi 30 F 50 F 70...

Страница 41: ...267 287 270 290 5 10 5 10 5 10 2 5 2 5 2 5 8 1 10 1 5 9 7 9 3 7 5 7 17 23 18 24 19 25 50 1 5 2 25 3 131 141 130 140 130 140 222 242 208 228 194 214 13 18 13 18 14 19 10 15 9 14 9 14 21 9 23 9 16 1 18...

Страница 42: ...192 407 427 411 431 415 435 8 14 8 14 8 14 13 18 13 18 14 19 18 2 20 2 13 9 15 9 9 6 11 6 42 50 43 51 44 52 110 1 5 2 25 3 138 148 137 147 136 146 505 525 483 503 459 479 6 11 6 11 6 11 10 15 9 14 8 1...

Страница 43: ...even quicker than the water coil and may need more frequent inspections In areas with extremely hard water a HWG is not recommended Filters Filters must be clean to obtain maximum performance Filters...

Страница 44: ...and can be verified using a voltmeter The fan signal is passed through the board to the external fan relay units with PSC motors only The alarm relay can either be 24VAC as shipped or dry contacts for...

Страница 45: ...r further help Check Main power see power problems Check fault LED code on control board Yes No No No No No Yes No Yes See HP Fault See LP LOC Fault See FP1 Fault See FP2 Fault See Condensate Fault Se...

Страница 46: ...in cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp wi...

Страница 47: ...thermistor Check temp and impedance correlation per chart FP2 fault Code 5 X Reduced or no Air flow Check for dirty air filter and clean or replace Air Coil low temperature limit in cooling Check fan...

Страница 48: ...SAT PSI SAT F F AIR COIL F F LIQUID LINE F HEATING EXPANSION VALVE COOLING EXPANSION VALVE AIR COIL F F LIQUID LINE F HEATING EXPANSION VALVE COOLING EXPANSION VALVE PSI SAT PSI SAT F F AIR HANDLER S...

Страница 49: ...49 Residential Split 60Hz R22 R 410A Rev 5 June 2 0 0 8 Carrier Turn to the Experts...

Страница 50: ...the Manufacturer s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express wa...

Отзывы: