G e n e s i s
Supply
Heater Amps
Min Circ Ampacity
Max Fuse
Supply Wire
Electric Heat Model
Circuit
2 4 0 V
2 0 8 V
2 4 0 V
2 0 8 V
2 4 0 V
2 0 8 V
Min AWG
Max Ft
AGS4 or AGSH4
Single
15.8
13.7
19.8
17.1
20
20
12
50
AGM5 or AGMH5
Single
20.0
17.3
25.0
21.6
25
25
10
70
AGM8 or AGMH8
Single
31.7
27.5
39.6
34.4
40
35
8
70
AGM10 or AGMH10
Single
40.0
34.7
50.0
43.4
50
45
6
90
Single
47.5
41.2
59.4
51.5
60
60
6
70
AGM12 or AGMH12
Dual - L1/L3
31.7
27.5
39.6
34.4
40
35
8
70
Dual - L2/L4
15.8
13.7
19.8
17.1
20
20
12
50
AGL10 or AGLH10
Single
40.0
34.7
50.0
43.4
50
45
6
80
Single
60.0
52.0
75.0
65.0
80
70
6
50
AGL15 or AGLH15
Dual - L1/L3
40.0
34.7
50.0
43.4
50
45
6
80
Dual - L2/L4
20.0
17.3
25.0
21.6
25
25
10
70
Single
80.0
69.3
100.0
86.6
100
90
2
100
AGL20 or AGLH20
Dual - L1/L3
40.0
34.7
50.0
43.4
50
45
6
80
Dual - L2/L4
40.0
34.7
50.0
43.4
50
45
6
80
All heaters rated single phase 208-240V 60 Hz
Wire length based on one way measurement with 2% voltage drop
Wire size based on 90°C copper conductor
Part numbers with "H" included are for horizontal units only
All models 12kW or larger feature internal circuit breakers
Genesis Auxiliary
Gensis Model Compatibility (shaded)
kW Rating (kW)
Btuh Rating (Btuh)
Minimum
Electric Heat Model
009 012 015 018 024 030 036 042 048 060 070
240V
208V
240V
208V
CFM
Required
AGS4 or AGHS4
3.8
2.9
12900
9700
250
AGM5 or AGMH5
4.8
3.6
16300
12300
500
AGM8 or AGMH8
7.6
5.7
25900
19400
650
AGM10 or AGMH10
9.6
7.2
32700
24600
650
AGM12 or AGMH12
11.4
8.6
38900
29200
750
AGL10 or AGLH10
9.6
7.2
32700
24600
1300
AGL15 or AGLH15
14.4
10.8
49100
36900
1350
AGL20 or AGLH20
19.2
14.4
65500
49200
1350
Note: Horizontal units rated for zero clearance unit and 1" clearance for first three feet of duct, vertical units rated for zero clearance for
both unit and duct.
Table 4. GT-G Electric Heat Staging Options
Table 3. GT-G Electric Heat Electrical Data
Table 2. GT-G Electric Heat Ratings
Carrier works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without
notice and may not be as described herein. Please contact Carrier’s Customer Service Department at 1-405-745-6620 for specific information on the
current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain
between the parties, but are merely Carrier’s opinion or commendation of its products.
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
FAX: 405-745-2051
www.Carrier.com
© Carrier 1999
*97B0005N01*
97B0005N01
G e n e s i s
S t a g i n g
F a c t o r y
Staging in kW
Auxiliary Electric
O p t i o n s
S e t t i n g
Jumper 1-4, 2-3†
Jumper 1-3, 2-4
Jumper 1-2-3
Heat Model
Stage 1
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1 Stage 2
AGS4 or AGSH4
4
4
4
0
4
0
4
0
AGM5 or AGMH5
5
5
5
0
5
0
5
0
AGM8 or AGMH8
4 or 8
4
4
4
4
4
8
0
AGM10 or AGMH10
5 or 10
5
5
5
5
5
10
0
AGM12 or AGMH12
4, 8 or 12
4
4
8
8
4
12
0
AGL10 or AGLH10
5 or 10
5
5
5
5
5
10
0
AGL15 or AGLH15
5,10 or 15
5
5
10
10
5
15
0
AGL20 or AGLH20
5,10, 15 or 20
10
10
10
10
10
15
5
Part numbers with "H" included are for horizontal units only
† Factory jumper setting
®