Nov-21
Page 37 of 132
59812-K001 Rev 10
Feed the cable into the Control Panel via a metal IP65 EMC gland supplied, ensuring that the metal
prongs make a good contact with the exposed cable screen as shown. The gland should be fixed in place
using a toothed nut to cut through the Control Panel paint.
The relays should be connected to the Alarm Monitoring System, AMS, to initiate the required response
when the relay is activated.
2.6.3
Control Panel to Junction Box Connections
Control Panel Connections
The cables from the Control Panel to each Junction Box should be of the following types:
Power Cable:
2 Cores + Earth, CSA 2.5mm
2
(50/0.25mm), flexible stranded bare copper conductors, low smoke
halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath grey, outside
diameter 9.8mm, operating temperature 0
o
C + 80
o
C.
Approved cables
Lapp Kabel
CY cable 3 core 2.5mm
2
Prysmian
LSM-HF 3 core 2.5mm
2
Helkama
LKAM-HF 3 core 2.5mm
2
Communications Cable:
2 Twisted low capacitance pairs, 27(7) AWG tinned copper conductors, foam polyolefin insulation, each
pair foil screened with a tinned copper drain wire, low smoke halogen free sheath grey, outside
diameter 8.1mm, operating temperature 0
o
C to 70
o
C.
Approved cables
Beldon 9729
Helkama
RFE-HF(i) 2x2x0.75
FS Cables
2402PIFFH
Jinro 60V RCOP(IS)
At the Control Panel strip the power and communications cables to the required length. The cables
should be long enough to reach easily from the gland to the terminal and run tidily around the edge of
the Control Panel. Leave approximately 35mm of screen and fold it back over the outer insulation.
Alternatively, for the power cable
remove approximately 1cm of the outer sheath to expose the cable
screen as shown see Figure 21
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...