FZ4ANP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

9

A160012A

Fig. 20 – Wiring Layout of Humidifier to Heat Pump

START-UP PROCEDURES

Refer  to  outdoor  unit  Installation  Instructions  for  system  start-up

instructions and refrigerant charging method details.

A160013A

Fig. 21 – Wiring Layout of Humidifier to Heat Pump

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment failure,

it is essential that periodic maintenance be performed on this equipment.

Consult  your  local  dealer  as  to  the  proper  frequency  of  maintenance

contract.
The ability to properly perform maintenance on this equipment requires

certain mechanical skills and tools. If you do not possess these, contact

your dealer for maintenance. The only consumer service recommended

or required is filter replacement or cleaning on a monthly basis.

CAUTION

!

PRODUCT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  poor  unit  performance

and/or product damage.
Never operate unit without a filter. Factory authorized filter kits may be

used  when  locating  the  filter  inside  the  unit.  For  those  applications

where access to an internal filter is impractical, a field-supplied filter

must be installed in the return air duct system.

HI or Y2

HI or Y2

Table 2 – Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)

UNIT SIZE

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

024

0.034 0.049

0.063 0.076 0.089

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

036

- -

- -

- -

- -

- -

0.070 0.080

0.090 0.099

- -

- -

- -

- -

- -

- -

- -

048

- -

- -

- -

- -

- -

- -

- -

- -

- -

0.063 0.070 0.076 0.083 0.090

- -

- -

060

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

0.049 0.054 0.059

0.065 0.070

061

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

0.027 0.031 0.035

0.039 0.043

Table 3 – Electric Heater Static Pressure Drop (in. wc)

FZ4A024 - 036

FZ4A048 - 060

HEATER 

ELEMENTS 

kW 

EXTERNAL STATIC 

PRESSURE 

CORRECTION 

HEATER 

ELEMENTS 

kW 

EXTERNAL STATIC 

PRESSURE 

CORRECTION 

+.02 

+.04 

3, 5 

+.01 

8, 10 

+.02 

8, 10 

9, 15 

9, 15 

–.02 

20 

–.02 

20 

–.04 

18, 24, 30 

–.10 

Содержание FZ4ANP

Страница 1: ...s 5 through 30kW See Product Data literature for all available accessory kits HEATER PACKAGES This unit may or may not be equipped with an electric heater package For units not equipped with factory i...

Страница 2: ...mid return air the Water Management Kit KFAHC0125AAA may need to be used to assist in water management A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETURN LOCATION FOR S...

Страница 3: ...f Units with A Coils 1 Remove blower and coil access panels Fig 5 2 Remove metal clip securing fitting panel to condensate pan Remove fitting panel 3 Remove 2 snap in clips securing A coil in unit 4 S...

Страница 4: ...ertical condensate pan 15 Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS 1 Fan coil unit must be se...

Страница 5: ...ance with the NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field supplied disconnect switch located within sig...

Страница 6: ...ay also be accomplished by using grounding lugs provided in control box MINIMUM CFM AND MOTOR SPEED SELECTION The fan speed selection is done at the motor connector Units with or without electric heat...

Страница 7: ...line Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensa...

Страница 8: ...er motor When G is de energized there is a 90 second delay before relay opens COOLING MODE Thermostat energizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes cir...

Страница 9: ...placement or cleaning on a monthly basis CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor unit performance and or product damage Never operate unit without a filter Fact...

Страница 10: ...cfm ton on 048 061 size could result in condensate blowing off coil or splashing out of drain pan Table 4 Airflow Performance CFM MODEL SIZE BLOWER SPEED 0 10 0 20 0 30 0 40 0 50 0 60 FZ4A 024 Tap 5 9...

Отзывы: