All units are shipped with power plug and stripped leads for connection of field wiring to units without electric heat.

1. Connect 208/230v power leads from field disconnect to yellow and black-striped leads.

2. Connect ground wire to unit ground lug.

3. If unit contains accessory electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug

from unit wiring harness. (See Electric Heater Installation Instructions.)

B.

24-V Control System Connections to Unit Printed-Circuit Board (PCB)

Refer to unit wiring instructions for recommended wiring procedures. Use No. 18 AWG color-coded, insulated (35°C minimum) wires to make
low-voltage connections between thermostat and unit. If thermostat is located more than 100 ft from unit (as measured along the low-voltage
wires), use No. 16 AWG color-coded, insulated (35°C minimum) wires. PCB is circuited for single-stage heater operation. When additional heater
staging is desired using 2-stage or outdoor thermostats, see applicable outdoor unit instructions. Remove Jumper J2 on PCB.

1. The 5-, 8-, and 10-kw heaters are single stage only.

2. The 15- and 20-kw heaters are adaptable for 2-stage operation.

3. The 24- and 30-kw heaters are adaptable for up to 3-stage operation.

Connect low-voltage leads to thermostat and outdoor unit. (See Fig. 9 and 10.)

C.

Intelligent Heat Option

Intelligent Heat staging of the electric heat package is possible when the FK4C is installed as a part of a single-speed heat pump system using a
corporate 2-speed programmable thermostat (model TSTATXXP2S01-A) and any 1 of the following electric heat packages:
KFAEH2501N09, KFAEH2601F15, KFAEH2801C15, KFAEH2701S15, KFAEH1001F24 or KFAEH1101F30.

To activate Intelligent Heat:

1. Set thermostat dip switch C to off and D to on.

2. On the fan coil Easy Select board, remove Jumper J2 (W1-W2).

3. Complete system low-voltage wiring as shown in Fig. 11.

NOTE:

Where local codes require thermostat wiring be routed through conduit or raceways, splices can be made inside the fan coil unit. All

wiring must be NEC Class l and must be separated from incoming power leads.

A factory-authorized disconnect kit is available for installation of 0- through 10-kw applications. When electric heat packages with circuit breakers
are installed, the circuit breaker can be used as a disconnect.

Fig. 9—Single-Speed Heat Pump Wiring

A95313

Thermostat

Subbase

FK4C

Terminal

Block

Outdoor

Terminal

Board

C

C

C

W1

W2

W2

L

G

G

G

O/W2

O

O

R

R

R

Y

Y/Y2

Y/Y2

W/W1

Fig. 10—Two-Speed Heat Pump Wiring

A95314

Thermostat

Subbase

FK4C

Terminal

Block

Outdoor

Terminal

Board

C

C

C

W1

W2

W2

L

G

G

G

O

O

R

R

R

Y/Y2

Y2

E

Y1

Y1

O/W2

Y/Y2

Y1/

W2

W/W1

—8—

Содержание FK4C

Страница 1: ...ructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most se...

Страница 2: ...LEFT APPLICATIONS FRONT VIEW SHOWN WITH A COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ APPLICATIONS 3 1 16 4 11 16 10 3 4 9 1 2 LIQUID LINE CONNECTION SUCTION LINE CONNECTION ACCESS PANEL CON...

Страница 3: ...P 4 PLACES 1 TYP 2 PLACES 2 7 8 2 3 16 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN 5 16 TYP 1 5 16 3 1 4 1 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN HORIZ RIGHT FIELD CONVERTED 1 5 16 1 11 16 2 1 2 TY...

Страница 4: ...and width of unit A Upflow Installation If return air is to be ducted install duct flush with floor Set unit on floor over opening Only use return air opening provided All return air must pass throug...

Страница 5: ...rommets after brazing E Horizontal Right Conversion of Units With A Coil To convert units for horizontal right installations 1 Remove blower and coil access panels See Fig 8 2 Remove metal clip securi...

Страница 6: ...access and fitting panels aligning holes with tubing connections and condensate pan connections Be sure to reinstall metal clip between fitting panel and vertical condensate pan Fig 6 Slope Coil in Ho...

Страница 7: ...tested by UL Standard 181 for Class 1 air ducts PROCEDURE 4 ELECTRICAL CONNECTIONS A Line Voltage Connections Units with 15 and 20 kw heaters are factory wired for dual circuit operation When single...

Страница 8: ...to 3 stage operation Connect low voltage leads to thermostat and outdoor unit See Fig 9 and 10 C Intelligent Heat Option Intelligent Heat staging of the electric heat package is possible when the FK4C...

Страница 9: ...fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes Failure to follow this warning could result in an electrical s...

Страница 10: ...tat closes circuit R to W W1 or W2 The fan coil delivers the selected electric heat airflow G Heat Pump Heating Mode Single speed or 2 Speed High 1 Thermostat closes circuits R to G and R to Y Y2 The...

Страница 11: ...pan should be installed underneath the entire unit and a secondary condensate line with appropriate trap should be run from the unit into the pan Any condensate in this external condensate pan should...

Страница 12: ...AC HP SIZE Select system size installed The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to sel...

Страница 13: ...gnal is present whenever the G thermostat signal is present heat pump heating cooling and continuous blower modes When the FK4C Fan Coil is installed with an electronic air cleaner use EAC relay kit P...

Страница 14: ...and wire in a standard humidistat See Fig 21 E Dehumidify and Super Dehumidify Capabilities This model fan coil is capable of responding to a signal from indoor system control thermostat thermidistat...

Страница 15: ...ensate drain each cooling season for cleanliness Clean as necessary An inspection port is provided on all A coil delta plates Remove plastic plug to inspect 3 Inspect blower motor and wheel for cleanl...

Страница 16: ...ay to increase your knowledge of the equipment discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skil...

Отзывы: