Fig. 8 -- Upflow Trap Configuration
(Appearance may vary)
A11587
Fig. 9 -- Downflow Trap Configuration
(Appearance may vary)
The field--supplied, accessory horizontal drain trap grommet is
ONLY REQUIRED FOR DIRECT VENT APPLICATIONS.
It it
NOT
required for applications using single--pipe or
ventilated combustion air venting.
NOTICE
The condensate trap extends below the side of the casing in
the horizontal position. A minimum of 2--in. (51 mm) of
clearance is required between the casing side and the furnace
platform for the trap to extend out of the casing in the
horizontal position. Allow at least 1/4--in. per foot (20 mm
per meter) of slope down.
NOTICE
A11573
Fig. 10 -- Horizontal Right Trap Configuration
(Appearance may vary)
A11574
Fig. 11 -- Horizontal Left Configuration
(Appearance may vary)