Installation of Evaporator Coils

Upflow Coil Installation

The cased coil is designed to fit furnaces of the same width (

Fig. 2

).

1. Set coil in place on upflow furnace discharge air opening.
2. Ensure coil is level for proper condensate drainage. Do not tip coil

toward condensate drain. Coil casing does not need to be fastened

or screwed to furnace.

3. When installing wider coil on narrower furnace, it is recommended

to use a transition adapter (

Fig. 3

).

NOTE: 

On upflow  installations where the indoor coil  is placed in an

unconditioned space, a 6" wide piece of insulation should be applied and

wrapped around the outside of the coil casing and supply duct contact

point.  Consult  the  furnace  installation  instructions  for  any  special

requirements when installing the coil to the furnace.

CAUTION

!

IMPORTANT – UNCASED INSTALLATIONS

EVD4X and WMVC units are not intended to be installed uncased

in  a  plenum  and  must  be  installed  on  an  agency  listed  Furnace.

Failure to comply may damage the coil assembly and can result in

poor performance and property damage.
Any uncased V-Coil installation is not recommended due to factors

such as:

-

Mounting dimensions must be held to ensure proper alignment 

between the coil and the condensate drain pan.

-

Level installation and the relationship of the condensate drain 

pan and the coil. If the installation is not level and properly 

aligned, condensate blow-off could result.

-

Unrestricted airflow across the coil is vital to adequate system 

performance.

-

The factory-installed foil-faced insulation in the front and rear 

of the coil are required to prevent bypass airflow.

-

Heat shields for the condensate drain pan (in upflow 

installations) and cross members (in downflow installations) 

must not be removed.

CAUTION

!

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
Installing coils rotated 90° from the front of the furnace, in upflow or

downflow applications, may cause water blow-off or coil freeze-up due

to the concentration of air on one slab of the coil or lack of air to a slab

of the coil. It is required that on this type of application, a field-supplied

adapter be placed between the coil and furnace to allow air to distribute

properly between all slabs of the coil.

Table 1 – Coil Connections / Orientations

Model

Nom. 

Tons

Line Set 

Connection Tube 

Size, in.

Flush Fit to 

Furnace Width, 

in. (mm)

Fits Next Smaller Furnace 

Width

90° 

Rotation to 

Furnace

(4" Min. 

Transition 

Required)

180° 

Rotation 

to Furnace

Suction Liquid

Equal 

Overhang

Offset 

Left

Offset 

Right

EVM4X24M17A1E / WMVM24417XA1E

2

3/4

3/8

17-1/2 (445)

X

X

X

ALL

Upflow,

Downflow,

Horizontal Right,

Horizontal Left

EVM4X25M17A1E / WMVM25417XA1E

2

3/4

3/8

17-1/2 (445)

X

X

X

EVM4X30M17A1E / WMVM30417XA1E

2.5

3/4

3/8

17-1/2 (445)

X

X

X

EVM4X31M17A1E / WMVM31417XA1E

2.5

3/4

3/8

17-1/2 (445)

X

X

X

EVM4X32M17A1E / WMVC32417XA1E

2.5

3/4

3/8

17-1/2 (445)

X

X

X

EVM4X36M17A1E / WMVM36417XA1E

3

3/4

3/8

17-1/2 (445)

X

X

X

EVM4X42M21A1E / WMVM42421XA1E

3.5

7/8

3/8

21 (533)

X

X

X

EVM4X43M21A1E / WMVM43421XA1E

3.5

7/8

3/8

21 (533)

X

X

X

EVM4X44M21A1E / WMVM44421XA1E

3.5

7/8

3/8

21 (533)

X

X

X

EVM4X48M21A1E / WMVM48421XA1E

4

7/8

3/8

21 (533)

X

X

X

EVM4X49M21A1E / WMVM49421XA1E

4

7/8

3/8

21 (533)

X

X

X

EVM4X60M21A1E / WMVM60421XA1E

5

7/8

3/8

21 (533)

X

X

X

EVM4X60M24A1E / WMVM60424XA1E

5

7/8

3/8

24-1/2 (622)

X

X

X

EVM4X61M24A1E / WMVM61424XA1E

5

7/8

3/8

24-1/2 (622)

X

X

X

Содержание EVD4X

Страница 1: ...ath CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installati...

Страница 2: ...refrigerant Use only with outdoor units designed for R 410A NOTE These TXVs are factory set at approximately 10 superheat measured at the suction service valve and are not field adjustable A210138 Fi...

Страница 3: ...he factory installed foil faced insulation in the front and rear of the coil are required to prevent bypass airflow Heat shields for the condensate drain pan in upflow installations and cross members...

Страница 4: ...sted and therefore full performance specifications have not been certified In instances where a not recommended installation configuration is required it is the responsibility of the installer to ensu...

Страница 5: ...using field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line S...

Страница 6: ...n It is highly RECCOMMENDED and in some locals is it a code requirement to install a trap on the drain line s Please use the following guidelines to assure proper drainage Install a trap in condensate...

Страница 7: ...is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases Fig 9 Humidifier Application When installing a humidifier in a system...

Отзывы: