
ERV & HRV: User and Installer Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
Unit should be synchronized with AHU/furnace operation to avoid Stale
air from bathroom condensation and mold growth in furnace/AHU
distribution ducting if cooling mode of furnace/AHU is used.
This configuration is not recommended with high velocity furnace.
NOTE:
For this type of configuration, the T-3 option must be selected
on the LCD screen when auto-balancing the unit.
SIMPLIFIED INSTALLATION (T-4)
A200565
Fig. 8 – Simplified Installation
For this type of installation, the furnace/AHU
must always be
synchronized
with the unit in order to maximize the amount of fresh air
to the building
(CONNECTION TO THE FURNACE/AHU on p9)
When performing duct connection to the furnace/AHU, installation must
be done in accordance with all applicable codes and standards. Please
refer to your local building code.
Fresh air and exhaust air flow through the furnace/AHU ducts, which
simplifies the installation.
The use of bathroom fans and a range hood is suggested to exhaust stale
air.
STALE AIR EXHAUST DUCTWORK:
Connect the stale air intake port of the unit to the furnace return duct at
least 3 feet ahead of the fresh air distribution from the unit.
FRESH AIR DISTRIBUTION:
Connect the fresh air distribution duct of the unit to the furnace return
duct at least 10 feet away from the furnace (A+B).
NOTE:
This 10-ft. distance applies only in areas where the outside
temperature falls below the freezing point 0°C (32°F).
NOTE:
For this type of configuration, the T-4 option must be selected
on the LCD screen when auto-balancing the unit.
ALTERNATE INSTALLATION (T-5):
A200566
Fig. 9 – Alternate Installation
Unit should be synchronized with AHU/Furnace operation to building
avoid condensation and mold growth in furnace/AHU distribution
ducting if cooling mode of furnace/AHU is used.
NOTE: For this type of configuration, the T-5 option must be selected on
the LCD screen when auto-balancing the unit.
CONNECTING THE DRAIN (HRV ONLY)
• Cut the appropriate length of drain tubing (
).
• Connect the tubing to the provided adapter.
• Make a water trap loop in the tube to prevent the unit from drawing
unpleasant odors from the drain source.
• Add water in the loop to prevent noise or hiss.
• Make sure there is a distance of at least 2" between the unit and the
tubing loop.
• Using the tie wrap provided, attach the tubing as illustrated.
• Run the tube to the floor drain or to an alternate drain pipe or pail.
IMPORTANT:
If using a pail to collect water, place the tube end
approximately 1" inside the pail in order to prevent water from being
drawn back up into the unit.
A200567
Fig. 10 – Drain Connection
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
This configuration is not recommended with high velocity furnace.
High pressures produced by these systems could cause errors.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
This configuration is not recommended with high velocity furnace.
High pressures produced by these systems could cause errors.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment/property damage
or improper operation.
A drain hose (included) must be installed on these units, as they may
generate a large amount of water, especially in cooler weather.