14
95-8562
4.2
APPENDIX F
PSS-MP TES
T
LAMP
F
igur
e F1—PSS-MP
Test Lamp
LAMP
REPLACEMENT
REPLACE
XENON
LAMP
MODULE
WITH
PN
18801
(UNDER
WA
TER
KINETICS).
W
ARNING
THIS
UNIT
IS
NOT
RA
TED
FOR
USE
IN
HAZARDOUS
(CLASSIFIED)
LOCA
TIONS.
CAUTION
A
FULL
SYSTEM
TEST
RESUL
TS
IN
AN
ALARM
OUTPUT
. THIS
WILL
RESU
LT
IN
THE
AUT
OMA
TIC
SUPPRESSION
SYSTEM
BEING
ACTIV
ATED
IF
IT
IS
NOT
DISABLED
PRIOR
TO
TESTING.
OPERA
TION
TURN
ON
PSS-MP
,
WAIT
15
SECONDS.
TO
CAUSE
AN
ALARM,
HOLD
PSS-MP
SO
THA
T
THE
INFRARED
FIL
TER
LENS
IS
LESS
THAN
1
INCH
FROM
THE
FRONT
OF
THE
FLAME
DETECT
OR
TO
BE
TESTED.
IT
CAN
TAKE
SEVERAL
SECONDS
FOR
THE
DETECT
OR
TO
ALARM.
NOTE
FOR
VALID
TEST
RESUL
TS,
THE
TEST
LAMP
AND
THE
SENSOR
UNDER
TEST
MUST
BE
AT
APPROXIMA
TEL
YT
HE
SAME
TEMPERA
TURE.
BA
TTER
Y
REPLACEMENT
THE
TEST
LAMP
REQUIRES
6
ALKALINE
C-SIZE
BA
TTERIES.
W
ARNING
CHANGE
BA
TTER
Y
IN
NON-HAZARDOUS
LOCA
TION
ON
LY
.
ON
OFF
INFRARED BEAM
INFRARED FILTER LENS
8 5/8
2 3/8
+
+
+
+
+
+
C
C
CC
C
C