background image

2

Fig. 2 — 

Upper End Panel with Damper Attached

3. Lift the provided upper-end panel with damper attached in

place over the top of the bottom panel. (See Fig. 2.) Do not

secure in place yet.

4. Remove and save the 12-pin jumper plug from the unit wir

-

ing  harness. Insert the harness  from  the  2-position  damper

plug into the unit wiring harness plug. (See Fig. 3.)

NOTE: The 12-pin jumper plug should be saved for future use in

the event that the 2-position damper is removed from the unit. The

jumper  plug  is  not needed  as  long  as the  2-position  damper  is

installed. 

5. Screw the upper-end panel with the damper attached, in place

on the HVAC unit. (See Fig. 4.)

Fig. 3 — 

Unit Wiring Harness Plug

Fig. 4 — 

Upper End Panel with Damper attached

6. Assemble the outside air hood per Fig. 5-7.

7. To assemble the outside air hood (see Fig. 5 for hood compo

-

nent locations and item numbers):
 a. Remove hood top panel from shipping position on unit

end.

 b. Install filters supports (Item #1) to the upper end panel

using the screws provided.

 c. Install each deflector (Item #8) on to each filter support

(Item #1) using the screws provided.

 d. Apply seal strip to mating flanges on side plates of hood

(Items #4 and #5).

 e. Secure  side  panels  (Items  #4  and  #5)  to  upper  panel

using the screws provided.

 f. Apply seal strip to mating flange of the hood (see Fig. 5).

 g. Secure  hood  top  (Item  #3)  to  upper  panel  using  the

screws provided. (On 44-in. chassis, remove the screws

from across top cover of unit. The rear flange of hood

top will slide behind unit top over flange.)

 h. Secure side retainers (Item #6) to side panels (Items #4

and #5) using the screws provided, screwing from out

-

side of the hood.

 i. Secure each central retainer (Item #2) to the hood top

(Item #3). Then align central retainers to holes located

on filter support (Item #1), so central retainer is perpen

-

dicular  to  hood  and  each  filter  support.  Secure  using

screws provided.

 j. Apply seal strip to top diverters (Item #7).

 k. Secure top diverters (Item #7) to hood top (Item #3).

 l. Install outdoor air screens by sliding them into each of

the four spaces created by the hood, filter support and

central retainers. To do so, first insert the air screens into

pocket created at the end of hood (Item #3), then fully

put the air screen into place, and then slide them back

into pocket created in the filter support (Item #1). Repeat

this for each air screen (see Fig. 6). See Fig. 7 for com

-

pleted hood assembly.

Fig. 5 — 

Hood Part Identification and Seal Strip 

Application Areas

2-Position Damper

Attached to Upper-End

Panel

Bottom

Panel

2-Position Outside
Air Damper

Provided
Upper Panel

APPLY SEAL STRIP
TO THE FRONT OF
THIS FLANGE

APPLY SEAL STRIP
TO THE BACK
OF THIS FLANGE

APPLY SEAL STRIP
TO THE BACK
OF THIS FLANGE

APPLY SEAL STRIP
TO THE BACK
OF THIS FLANGE

7

7

3

5

6

8

8

2

8

6

4

2

1

2

ITEM #

DESCRIPTION

QTY

1

Filter Supports

3

2

Central Retainer

3

3

Hood Top

1

4

Left Hood Side

1

5

Right Hood Side

1

6

Side Retainer

2

7

Top Diverters

2

8

Deflector

3

Отзывы: