18
Checkout Tests
Use the Checkout menu (see Table 9) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
NOTE: See User Interface for information about menu navigation
and use of the keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
▲
and
▼
buttons.
2. Press the
(Enter) button to select the item.
3. RUN? appears.
4. Press the
(Enter) button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press
the (Menu up) button to end the test.
Checkout test can be performed at any time during the operation
of the system as a test that the system is operable.
W7220 Economizer Module Wiring
Use Tables 10 and 11 to locate the wiring terminals for the
economizer module.
TIME-OUT AND SCREEN SAVER
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status item displays in turn and cycles to the next item after
5 seconds.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor startup and shut-
down between checkout tests so that you do not short-cycle the
compressors.
Table 10 — Economizer Module — Left Hand
Terminal Blocks
LABEL
TYPE
DESCRIPTION
Top Left Terminal Block
MAT
MAT
20k NTC
and COM
Mixed Air Temperature Sensor
(Polarity insensitive connections)
OAT
OAT
20k NTC
and COM
Outdoor Air Temperature Sensor
(Polarity insensitive connection)
S-BUS
S-BUS
S-BUS
(Sylk Bus)
Enthalpy Control Sensor
(Polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
Air Quality Sensor Input
(e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24V
24 vac
Damper Actuator 24 vac Source
Table 11 — Economizer Module — Right Hand
Terminal Blocks
LABEL
TYPE
DESCRIPTION
Top Right Terminal Block
—
n/a
The first terminal is not used
AUX2 I
24 vac IN
Shut Down (SD) or Heat (W)
Conventional only
and
Heat Pump Changeover (O/B) in Heat
Pump mode.
OCC
24 vac IN
Occupied / Unoccupied Input
E - GND
E-GND
Earth Ground - System Required
EXH1
24 vac OUT Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Bottom Right Terminal Block
Y2-1
24 vac IN
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2-O
24 vac OUT Y2 out - Cooling Stage 2 Output to stage 2
mechanical cooling
Y1-I
24 vac IN
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1-O
24 vac OUT Y1 out - Cooling Stage 2 Output to stage 2
mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (Hot)