VERTICAL INSTALLATION

These economizers are designed to work in both a vertical and

horizontal  applications.  These  instructions  are  for  a  vertical

installation.

1. Turn off unit power supply and install lockout tag.

2. Prepare the unit for economizer installation:

 a. For units with 2 position damper installed, remove the

outside  air  hood.  Unplug  the  damper  actuator  and

remove assembly from unit.

 b. For  units  with  manual  damper  installed,  remove  the

manual damper and hood.

3. Remove the upper panel and bottom panel (provided with the

HVAC  unit)  on  the  end  of  the  unit  to  expose  the  return

section.  (See  Fig.  2.)  Save  the  screws  for  use  later  when

replacing the panel. The panels can be discarded.

4. Remove the unit’s left side corner post and left side panel

from the unit to allow for easy economizer installation. (See

Fig. 3.)

5. Install  economizer,  as  shown  in  Fig  3,  into  the  return  air

section of the unit. Be careful not to pinch the wires during

installation. The bottom of economizer will rest on the base

of the unit. (See Fig. 4.)

6. Reinstall the left side corner post on to the unit. 

NOTE:  The  corner  post  will  sit  behind  the  economizer

flange.  (See  Fig.  5.)  Screw  through  the  corner  post  and

through the economizer. (See Fig. 5 and 6.)

7. Insert  provided  screw  through  the  bottom  left  rear  of  the

economizer and into the unit base. (See Fig. 4.) Reinstall the

unit’s left side panel.

8. Before the economizer is secured in place on the right hand

side, remove and save the 12-pin jumper plug from the unit

wiring harness. (See Fig 7.) Insert the economizer plug into

the unit wiring harness plug. (See Fig 7 and 12.)

NOTE: The 12-pin jumper plug should be saved for future use in

the event that the EconoMi$er2 component is removed from the

unit. The jumper plug is not needed as long as the EconoMi$er2

component is installed.

Fig. 2 — Upper and Bottom Panel on end of Unit

Fig. 3 — Unit Left Side Panel and Corner Post

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in personal injury and

damage to unit.

Cover the duct opening as a precaution so objects cannot fall

into  the  return  duct  opening.  Be  sure  to  remove  the  cover

when installation is complete.

Indoor-fan Panel

Upper End Panel

Shipped on Base Unit

Bottom Panel

Shipped on Base Unit

UNIT’S LEFT
SIDE PANEL

ECONOMI$ER IV

LEFT 
CORNER 
POST

Содержание CRECOMZR054B00

Страница 1: ...DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies haz...

Страница 2: ...rator box used for duct mounted CO2 room sensor c 33ZCT55CO2 Space temperature and CO2 room with over ride d 33ZCT56CO2 Space temperature and CO2 room sensor with override and setpoint 2 All units inc...

Страница 3: ...de corner post on to the unit NOTE The corner post will sit behind the economizer flange See Fig 5 Screw through the corner post and through the economizer See Fig 5 and 6 7 Insert provided screw thro...

Страница 4: ...e bottom screw holding the relief blade closed 10 Install the upper end economizer panel over the economizer s outside air damper and above the bottom panel Screw panel in place and screw panel into e...

Страница 5: ...g from the outside of the hood h Secure each central retainer Item 2 to the hood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is per...

Страница 6: ...el with Relief Relief Damper Remove Shipping Screw APPLY SEAL STRIP TO THE FRONT OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP...

Страница 7: ...7 Fig 10 Air Screen Installation Fig 11 Completed Hood Assembly 1 INSERT AIR SCREEN 2 SLIDE INTO POSITION...

Страница 8: ...e the side panels located in the hood parts box see Fig 15 3 Install parts as shown in the following exploded view see Fig 16 using the seal strip and screws provided in the parts box Figure 17 illust...

Страница 9: ...9 Fig 13 Barometric Hood Parts Fig 14 Shipping Location Vertical Units Fig 15 Barometric Hood Box Parts Location...

Страница 10: ...er See Fig 18 3 On the field installed economizer CRECOMZR0 B00 a birdscreen or hardware cloth is shipped attached to the bottom panel used for vertical applications NOTE This panel is not used for ho...

Страница 11: ...amper Fig 20 CRBARHOD001A00 Hood Sides and Top Unit Outside Air Hood Min 19 1 2 Relief Opening Return Duct 16 1 18 3 8 OUTDOOR AIR HOOD CRBARHOD001A00 RELIEF HOOD ORDERED SEPARATELY FIELD SUPPLIED RET...

Страница 12: ...ening on the unit See Fig 22 Screw panel in place 10 Install the upper end economizer panel in place over the economizer s outside air damper and above the bottom panel Screw panel in place and screw...

Страница 13: ...Panel Fig 22 Install Bottom Panel w Horizontal Duct Opening Fig 23 Reinstall Hinges and Damper on Return Duct UNIT S LEFT SIDE PANEL WITH DUCT OPENING LEFT FRONT CORNER POST Bottom Panel with Return D...

Страница 14: ...on 140 4 b Air Economizer High Limit Shut Off Control Requirements Table 2 California Title 24 Regional High Limit Dry Bulb Temperature Settings DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZ...

Страница 15: ...osition Make sure the switch is turned all the way left or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step...

Страница 16: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480312 01 Printed in U S A Form IIK CRECOMZR54 04 Pg 16 7 21 Replaces...

Отзывы: