START-UP

Follow the procedure in Table 3 to check the EconoMi$er2 system

when the unit is started.

NOTE: Check that the transformer(s) are sized properly. If a common

transformer  is  used,  make  sure  that  polarity  is  observed  on  the

secondary.  This  means  connect  all  No.  1  wires  to  one  leg  of  the

transformer  and  all  No.  2  wires  to  the  other leg of  the  transformer. If

multiple transformers  are  used  with  one  control  signal,  make  sure all

No.  1  wires  are  tied  together  and  tied  to  control  signal  negative  (-).

Controllers  and  actuators  must  have  separate  24  vac/vdc  power

sources.

Table 3 — EconoMi$er2 Start-Up and Checkout

STEP

PROCEDURE

EXPECTED RESPONSE

ECONOMI$ER2 RESPONDS 

CORRECTLY

ECONOMI$ER2 RESPONDS 

INCORRECTLY

1

Remove power reset actuator.

Re-apply power.

Apply control signal to actuator.

Actuator will move to its

“Control Signal” position.

Actuator operates properly.

Step 8

No response at all

Step 2

Operation is reversed

Step 3

Does not drive toward “Control

Signal” Position

Step 4

2

Check power wiring. Correct any 

problems. See Note

Power supply rating should be 

the total power

requirement of the actuator(s). 

Minimum voltage of 19.2 vac or 

21.6 vdc.

Power wiring corrected,

actuator begins to drive

Step 1

Power wiring corrected, actuator 

still does not drive

Step 4

3

Turning reversing switch to the 

correct position. Make sure the 

switch is turned all the way left or 

right.

Actuator will move to its

“Control Signal” position.

Actuator operates properly

Step 8

Does not drive toward “Control

Signal” Position

Step 4

4

Make sure the control signal 

positive (+) is connected to Wire 

No. 3 and control signal negative 

(-) is connected to Wire No. 1. 

Most control problems are 

caused by reversing these two 

wires. Verify that the reversing 

switch is all the CCW or CW.

Drives to “Control Signal”

position

Actuator operates properly

Step 8

Step 5

5

Check input signal with a digital 

volt meter (DVM). Make sure the 

input is within the range of the 

actuator (2 to 10 vdc or 4 to 20 

mA). NOTE: The input signal 

must be above the 2vdc or 4 mA 

to have the actuator move.

Input voltage or current

should be ± 1% of what

controller’s adjustment or

programming indicate.

Controller output

(actuator input) is

correct Input Polarity

Correct

Step 6

Reprogram, adjust, repair or

replace controller as needed.

Step 1

6

Loosen the nuts on the V-bolt 

and move the damper by hand 

from fully closed to fully open.

Damper will go from fully

closed to fully open

Damper moves properly.

Step 7

Find cause of damper jam and 

repair. 

Move damper back to fully 

closed position and tighten the 

nuts.

Step 1

7

Check damper torque 

requirement.

Torque requirement is

actuator’s minimum torque.

Defective Actuator

Replace Actuator

Recalculate actuator 

requirement

and correct installation

8

Actuator works properly. Test 

controller by following controller 

manufacturer’s instructions.

Содержание CRECOMZR054B00

Страница 1: ...DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies haz...

Страница 2: ...rator box used for duct mounted CO2 room sensor c 33ZCT55CO2 Space temperature and CO2 room with over ride d 33ZCT56CO2 Space temperature and CO2 room sensor with override and setpoint 2 All units inc...

Страница 3: ...de corner post on to the unit NOTE The corner post will sit behind the economizer flange See Fig 5 Screw through the corner post and through the economizer See Fig 5 and 6 7 Insert provided screw thro...

Страница 4: ...e bottom screw holding the relief blade closed 10 Install the upper end economizer panel over the economizer s outside air damper and above the bottom panel Screw panel in place and screw panel into e...

Страница 5: ...g from the outside of the hood h Secure each central retainer Item 2 to the hood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is per...

Страница 6: ...el with Relief Relief Damper Remove Shipping Screw APPLY SEAL STRIP TO THE FRONT OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP...

Страница 7: ...7 Fig 10 Air Screen Installation Fig 11 Completed Hood Assembly 1 INSERT AIR SCREEN 2 SLIDE INTO POSITION...

Страница 8: ...e the side panels located in the hood parts box see Fig 15 3 Install parts as shown in the following exploded view see Fig 16 using the seal strip and screws provided in the parts box Figure 17 illust...

Страница 9: ...9 Fig 13 Barometric Hood Parts Fig 14 Shipping Location Vertical Units Fig 15 Barometric Hood Box Parts Location...

Страница 10: ...er See Fig 18 3 On the field installed economizer CRECOMZR0 B00 a birdscreen or hardware cloth is shipped attached to the bottom panel used for vertical applications NOTE This panel is not used for ho...

Страница 11: ...amper Fig 20 CRBARHOD001A00 Hood Sides and Top Unit Outside Air Hood Min 19 1 2 Relief Opening Return Duct 16 1 18 3 8 OUTDOOR AIR HOOD CRBARHOD001A00 RELIEF HOOD ORDERED SEPARATELY FIELD SUPPLIED RET...

Страница 12: ...ening on the unit See Fig 22 Screw panel in place 10 Install the upper end economizer panel in place over the economizer s outside air damper and above the bottom panel Screw panel in place and screw...

Страница 13: ...Panel Fig 22 Install Bottom Panel w Horizontal Duct Opening Fig 23 Reinstall Hinges and Damper on Return Duct UNIT S LEFT SIDE PANEL WITH DUCT OPENING LEFT FRONT CORNER POST Bottom Panel with Return D...

Страница 14: ...on 140 4 b Air Economizer High Limit Shut Off Control Requirements Table 2 California Title 24 Regional High Limit Dry Bulb Temperature Settings DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZ...

Страница 15: ...osition Make sure the switch is turned all the way left or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step...

Страница 16: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480312 01 Printed in U S A Form IIK CRECOMZR54 04 Pg 16 7 21 Replaces...

Отзывы: