13. Remove tape from outdoor-air thermostat (OAT). Fas-
ten OAT to inside of hood using screws and speed clips
provided. See Fig. 12. Make sure OAT terminals are up.
14. Place knob supplied with economizer on OAT. Set for
3 F below indoor room thermostat setting. If accessory
solid-state enthalpy control (EC) is used instead of the
OAT, see instructions shipped with EC for installation
and adjustment.
15. Connect OAT per Fig. 13.
16. Slide outdoor-air inlet screen(s) into screen track of hood
side plates. On 7
1
⁄
2
to 12
1
⁄
2
ton units, clamp screens to-
gether using clasp provided. While holding screen(s) in
place, fasten screen retainer to hood using screws
provided.
NOTE: Only 1 screen is provided with 3 to 6 ton units.
EXAMPLE:
Given —
Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . 0.2 in. wg
Outdoor Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm
Determine —
Setting = 6 in.
Fig. 9 — Economizer Minimum Position Setting
(3 to 6 Ton Units)
EXAMPLE:
Given —
Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . 0.1 in. wg
Outdoor Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm
Determine —
Setting = 6 in.
Fig. 10 — Economizer Minimum Position Setting
(7
1
⁄
2
to 12
1
⁄
2
Ton Units)
BLOCK-OFF PLATE
Fig. 6 — Horizontal Discharge Block-Off Plate
WIRING
HARNESS
U-SHAPED
HOLE
(NOT SHOWN)
Fig. 7 — Typical Economizer and Wiring Harness
WARNING
WARNING
Fig. 8 — Typical Access Panel Locations
(3 to 6 Ton, Standard Efficiency Unit Shown)
3