2
INSTALLATION
Step 1 — Install Condensate Overflow Switch
1. Remove panel that covers the control box.
2. Use 2 Item 3 supplied screws to fasten condensate con-
troller to box as shown in Fig. 1.
3. Connect RED and BRN power wires from controller to
circuit board terminals as shown in Fig. 2.
Step 2 — For SINGLE Compressor Units
1. Remove wire from C1 coil and connect to BLU “Cond
1 In” wire from controller. Connect BLU “Cond 1
Out” wire from controller to open terminal on C1 coil.
See Fig. 3.
2. The (2) extra ORN wires should be tied back.
Step 3 — For DUAL Compressor Units
1. Remove wire from C1 coil and connect to BLU “Cond 1
In” wire from controller. Connect BLU “Cond 1 Out” wire
from controller to open terminal on C1 coil. See Fig. 4.
2. Remove wire from C2 coil and connect to ORN “Cond
2 In” wire from controller. Connect ORN “Cond 2
Out” wire from controller to open terminal on C2 coil.
See Fig. 4.
Fig. 1 — Control Box
Fig. 2 — Main Circuit Board