ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
31
Wiring and DIP switch configurations 17 to 20 – AC systems
Outputs
Config. 17:
HP22
2/3 Speed fan
(1)
,
Humidifier, Dehumidifier
Config. 18:
HP21
2/3 Speed fan
(1)
,
Humidifier, Reheat for
Dehumidification
Config. 19:
HP22
Fan VFS, Humidifier
Config. 20:
HP21
Fan VFS, Humidifier,
Reheat for
Dehumidification
11
Fan high
Fan high
X
X
12
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Economizer
(5)
(option – SW2.6 ON)
Economizer
(5)
(option – SW2.6 ON)
13
Fan low
Fan low
X
X
14
Compressor 2
(3)
Heat element
(2nd stage heat)
Compressor 2
(3)
Heat element
(2nd stage heat)
15
Compressor 1
(3)
Compressor
(3)
Compressor 1
(3)
Compressor
(3)
16
Heat pump
(2)
Heat pump
(2)
Heat pump
(2)
Heat pump
(2)
AO1
Humidifier
Humidifier
Humidifier
Humidifier
AO2
Dehumidifier
X
Fan VFS
Fan VFS
SW1
SW2
(1)
SW1.1, SW1.2 – Fan speeds:
2 speeds (Low and High):
3 speeds (Low, Med., and High):
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – HP (Heat pump):
HC (not heat pump):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
(3)
SW1.5 – Compressor delay:
ON = Disable, OFF = Enable
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation: ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in
Wiring terminals and DIP switches
(page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
Fan VFS, Humidifier, Dehumidifier: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Heat pump, Compressors, Economizer: 110-230 Vac, 0.3A max.