background image

E

2009 Lennox Industries Inc.

Dallas, Texas, USA

ComfortSense

®

 7000 Series Model No. L7742U

Touch Screen Programmable Thermostat

Quick−Start Installation Instructions

05/09

506227−01

*P506227-01*

IMPORTANT! READ THIS FIRST!

Before beginning installation, note the type of equipment, number of stages, and any accessories being
installed. The ComfortSense

®

 L7742U thermostat is a 24VAC low−voltage thermostat and requires a common

wire to the thermostat to operate. Observe the specifications and the DO’s and DO NOT’s that follow:

Use 18 gauge thermostat wire or larger.

Maximum wire run length 300’ (one way).

Maximum load 1 Amp or less.

DO

 Shut off all power to system before installing
 Read this entire document, noting which in-

structions pertain to your equipment and sys-
tem requirements.

 Make sure that all wiring conforms to local

and national building and electrical codes and
ordinances.

 Use thermostat wire between the thermostat

and the optional outdoor temperature sensor
(may be separate wire pair or two wires of a
multi−wire cable). No shielded or twisted−wire
pair is needed.

 Consult the ComfortSense

®

 7000 Series Pro-

gramming and Application Guide 506228−01.

DO NOT

 Install on voltages higher than 30VAC.

 Short (jumper) across terminals on the gas

valve or at the system control to test installa-
tion. This will damage the thermostat and
void the warranty. 

Instead, use testing func-

tion in the thermostat shown on back
page.

 Install on outside walls or in direct sunlight

 Install for commercial applications unless

used with approved split-system matches,
and all wiring and load criteria is been met.

Install base in desired location

PULL ABOUT 3" OF THERMO-
STAT WIRE THROUGH OPENING
AND REMOVE OUTER THERMO-
STAT WIRE JACKET.

THIS WILL
HELP IN
ROUTING
THE THER-
MOSTAT WIR-
ING TO THE
PROPER
THERMOSTAT
TERMINALS

1/4"

TRIM 1/4"
INSULATION
FROM END
OF EACH
WIRE

USE THE UNIT BASE AS A TEMPLATE
AND A LEVEL TO MARK TWO MOUNTING
HOLE LOCATIONS ON WALL. USE EITHER
VERTICAL OR HORIZONTAL HOLES.

TAP DOWN THE AN-
CHORS UNTIL FLUSH
WITH WALL.

DRILL TWO 3/16" HOLES AT EITHER HOR-
IZONTALLY OR VERTICALLY MARKED
LOCATIONS ON WALL FOR ANCHORS

(USE A LEVEL)
ALIGN BASE
OVER PLASTIC
ANCHORS;
SECURE TO WALL
USING PROVIDED
SCREWS.

INSERT WALL
ANCHORS IN
HOLES.

1

2

3

4

5

6

7

CUT OR DRILL
A SMALL HOLE
FOR THERMO-
STAT WIRING

8

UNPACKAGE THE THERMOSTAT AND
OPEN THE CASE WITH A FLAT−BLADE
SCREWDRIVER. PLACE BETWEEN BASE
AND UNIT AND TWIST TO SEPARATE
UNIT FROM BASE.

9

1/2"

1/2"

HORIZON-

TAL

VERTICAL

Connect wiring, seal  hole, and setup thermostat

1

. Connect wiring between thermostat, indoor unit, and outdoor unit

similar to that shown below. See unit-specific wiring diagrams on
back page.

2

. Connect the outdoor sensor (if used) to the ’T’ connections on the

thermostat (wire run should not exceed 300’ [91m]).

3

. Seal the hole in the wall with a suitable material to prevent drafts

from entering the thermostat case.

4

. Configure thermostat and equipment for system type, program

the thermostat, and test system (see minimum configuration
guide on back page or 

Programming and Application Guide

).

TERMINAL DESIGNATIONS
T − 

Outdoor Temp. Sensor Connection 1 (Opt.)

T −  

Outdoor Temp. Sensor Connection 2 (Opt.)

C − 

Common 24 Vac

Y2 − 2nd stage heating or cooling
Y1 −  1st stage heating or cooling
B − 

Heat active reversing valve

D − 

Dehumidification relay (to DS terminal)

H − 

Humidification relay (to Humidifier)

L −  

System check (HVAC Fault Detected?)

O −

Cool active reversing valve

W1 −  1st stage heating (non−heat pump or emergency

heat) or 3rd stage heating (heat pump)

W2 −  2nd stage heating (non−heat pump) or 4th stage

(heat pump)

G −   Fan relay
R − 

24 Vac power

OUTDOOR

UNIT

INDOOR

UNIT

COMFORTSENSE

®

7000

OUTDOOR

SENSOR

Отзывы: