background image

8

3--Phase Monitor

In 3--phase units a small circuit board is factory installed to monitor

line voltage. A small led will flash if a phase problem exists. See
code descriptions on monitor. If LED is flashing, disconnect

power to unit and interchange 2 field--wiring leads on unit
contactor.

A00010

Fig. 7 -- 3--Phase Monitor Control

(Applies to 3--Phase Units Only)

Table 5 – Three--Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Ensure compressor rotation is correct.

S

3--phase scroll compressors are rotation sensitive.

S

A flash LED on phase monitor indicates reverse rotation.
(See Table 3)

This will not allow contractor to be energized.

S

Disconnect power to unit and interchange 2 field--wiring
leads on unit contactor.

CAUTION

!

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is
energized.
On a call for cooling, thermostat makes circuits R--Y and R--G.
Circuit R--Y energizes contactor, starting outdoor fan motor and

compressor circuit. R--G energizes indoor unit blower relay,

starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de--energizing

contactor and blower relay. Compressor and motors stop.
If indoor unit is equipped with a time--delay relay circuit, the

indoor blower will run an additional 90 seconds to increase system

efficiency.

Check Charge

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside
unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line
above or below 15ft (4.57 m) respectively.

NOTE:

For 15 ft (4.57 m) line set charge, refer to the table below.

some units may require additional charge depending on size. Find
model size in chart below, reference factory charge on unit’s rating
plate and add additional charge if there is a difference. Additional
charge will be needed for longer line sets (charge unit to nameplate
subcooling).

UNIT SIZE

15 ft. (4.57 m) Line Set Charge

lb (kg)

13 SEER

14 SEER

15 SEER

18

4.10 (1.86)

4.77 (2.16)

4.87 (2.21)

24

4.22 (1.91)

4.20 (1.91)

4.60 (2.09)

30

4.90 (2.22)

5.67 (2.57)

5.67 (2.57)

36

5.00 (2.27)

5.42 (2.46)

6.40 (2.90)

42

6.07 (2.75)

7.90 (3.58)

7.46 (3.38)

48

7.00 (3.18)

8.31 (3.77)

8.31 (3.77)

60

8.80 (3.99)

9.39 (4.26)

9.39 (4.26)

For standard refrigerant line lengths (80 ft/24.38 m or less), allow

system to operate in cooling mode at least 15 minutes. If conditions
are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to
drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

Final Checks

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and
covers.

3. Tighten service valve stem caps to 1/12--turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in
manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Owner’s Manual for
information.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: CA13---16N---02SI

Replaces: CA13--- 16N--- 01SI

Содержание CA13NA 018--060

Страница 1: ...injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a...

Страница 2: ...iping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remainin...

Страница 3: ...y tube or fixed orifice indoor coils to these units 2 For Tubing Set lengths between 80 and 200 ft 24 38 and 60 96 m horizontal or 35 ft 10 7 m vertical differential 250 ft 76 2 m Total Equivalent Len...

Страница 4: ...han indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The fo...

Страница 5: ...108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 Table 3 Superheat Charging AC Only OUTDOOR TEMP _F EVAP...

Страница 6: ...57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63...

Страница 7: ...power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load w...

Страница 8: ...t to nameplate subcooling UNIT SIZE 15 ft 4 57 m Line Set Charge lb kg 13 SEER 14 SEER 15 SEER 18 4 10 1 86 4 77 2 16 4 87 2 21 24 4 22 1 91 4 20 1 91 4 60 2 09 30 4 90 2 22 5 67 2 57 5 67 2 57 36 5 0...

Страница 9: ...7 m vertical differential refer to Residential Piping and Longline Guideline Additional requirement for Low Ambient Controller full modulation feature MotorMasterr Control Always Ask For 24 VAC HOT 24...

Страница 10: ...ine longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics...

Отзывы: