315S: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

Refer to 

Fig. 3

 and install filter drier as follows:

1. Braze 5-in. liquid tube to the indoor coil. 

2. Wrap filter drier with damp cloth. 

3. Braze filter drier to above 5-in. (127 mm) liquid  tube. Flow arrow

must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 – Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

Refrigerant  tubes  and  indoor  coil  should  be  evacuated  using  the

recommended deep vacuum method of 500 microns. The alternate triple

evacuation  method  may  be  used  (see  triple  evacuation  procedure  in

service manual).  Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a

vacuum  of  500  microns  and  a  vacuum  gage  capable  of  accurately

measuring  this  vacuum  depth.  The  deep  vacuum  method  is  the  most

positive way of assuring a system is free of air and liquid water. A tight

dry system will hold a vacuum of 1000 microns after approximately 7

minutes. See 

Fig. 4

A95424

Fig. 4 – Deep Vacuum Graph

Mandatory Requirements

Pressure Proof Check 

1. Preform a pressure check of the unit with a nitrogen charge of about

200psi. 

2. The Nitrogen holding charge must 

NOT

 decrease in pressure for 

1

hour

,  as  indicated  by  the  test  gauge.  The  measuring  test  gauge

resolution not exceeding 5% of the holding charge. 

Leak Check 

This leak check requires a vacuum pump capable of pulling a vacuum of

at least 500 microns and a vacuum gage capable of accurately measuring

this vacuum depth. 

1. Vacuum unit to 500 microns. 
2. When isolating the unit from the pump, the pressure shall not rise

above 1500 microns in 10 minutes. 

Final Tubing Check

IMPORTANT: 

Check to be certain factory tubing on both indoor and

outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not

rubbing  against  each  other  or  any  sheet  metal  or  wires.  Pay  close

attention  to  feeder  tubes,  making  sure  wire  ties  on  feeder  tubes  are

secure and tight.   

Installing with Indoor Piston

Outdoor Unit Connected to Factory Approved Indoor Unit

Check piston size shipped with indoor unit to see if it matches required

indoor  piston  size.    If  it  does  not  match,  replace  indoor  piston  with

correct piston size.  
The piston included with the FMA, FMC and FMU fan coils are unique

to  those  products  and  CANNOT  be  replaced  with  the  piston  shipped

with  outdoor  unit.  Refer  to  the AHRI  Directory  to  check  if  a  certain

combination can use a piston or requires an accessory TXV.
When changing indoor piston, use a back−up wrench. Hand tighten hex

nut, then  tighten  with  wrench  1/2  turn.  Do  not  exceed 30  ft−lbs. The

indoor  piston  contains  a  Teflon  ring  (or  seal)  which  is  used  to  seat

against the inside of distributor body, and must be installed properly to

ensure proper seating. See 

Fig. 5

A10342

Fig. 5 – Indoor (Cooling) Piston

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
1. Installation of  filter  drier  in liquid line is  required.
2. Filter drier must be wrapped in a heat-sinking material such as a wet

cloth while brazing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Never use the system compressor as a vacuum pump.

WARNING

!

FIRE HAZARD

Failure to following this warning could result in personal injury, death

and/or property damage. 

DO  NOT  USE  FLAMES  OR  IGNITION  SOURCES  TO  LEAK

CHECK. 

Содержание bryant 315S

Страница 1: ...windows patios decks etc where unit operation sound may disturb customer 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes with no bends with cen...

Страница 2: ...the accessory kit NOTE Accessory wind baffles should be used on all units with accessory low ambient temperature control A07396 Fig 2 Lifting Unit with Sling Clearance Requirements Single Unit Applica...

Страница 3: ...such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Страница 4: ...uum unit to 500 microns 2 When isolating the unit from the pump the pressure shall not rise above 1500 microns in 10 minutes Final Tubing Check IMPORTANT Check to be certain factory tubing on both ind...

Страница 5: ...nimum of 15 minutes before checking charge 2 Measure suction pressure by attaching an accurate gage to suction valve service port 3 Measure suction temperature by attaching an accurate thermistor type...

Страница 6: ...4 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 110 43 108 42 106 41 104 40 427 116 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47...

Страница 7: ...et and connect leads to control wiring Refer to thermostat Installation Instructions for wiring specific unit combinations see Fig 7 Use No 18 AWG color coded insulated 35 C minimum wire If thermostat...

Страница 8: ...tory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit For TXV use subcooling method For piston use superheat method To prop...

Страница 9: ...oastal applications See Owner s Manual for information WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury and or property damage For c...

Страница 10: ...out notice and without obligations 10 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe i...

Отзывы: