background image

9

 FLARING AND CONNECTING REFRIGERANT LINES

1. Remove the protective cap from the flare fitting.

2. Remove the protective cap from the tubing and cut to the

required length. Be sure that the cut is perpendicular and
clean, without burrs.

3. Slip the flare nut on the tubing and flare the tube end using

standard flaring tools.

4. Tighten the nut until resistance is met. Mark the nut and the

fitting. Using a suitable wrench tighten an additional 1/4
turn. Use the following specified torque, according to
connection size:

Mixed-Phase line:

Suction line:

1/4 in.-(12.3 ft-lb.)

1/2 in.-(36 ft-lb.)

Both refrigerant lines
need to be insulated separatly

NOTE: The service valves on the outdoor unit must remain closed
until all 4 connections have been made.

EVACUATE TUBING AND CHARGE THE SYSTEM — When
all the fittings are connected, air must be expelled, then refriger-
ant charge must be checked and adjusted. Follow the steps below.

1. Open the service port cap on the suction line valve (large

valve of unit No. 1).

2. Connect the vacuum pump to the service port of unit No. 1

via the pressure gage and evacuate to 500 microns to
eliminate contamination and moisture.

3. Disconnect the vacuum pump. Unit should maintain 500

microns for 5 minutes.

4. Remove the service port caps from the mixed-phase valve

and suction line valve

5. Open the mixed-phase valve (small valve) with an Allen

wrench.

6. Open the suction line valve (large valve) with an Allen

wrench.

7. To evacuate  and charge unit No. 2 repeat steps 1 thru 6.

8. The outdoor unit is supplied with sufficient R-22

refrigerant for up to 25 ft. lineset length. Add 0.9 oz. of
refrigerant for each additional 3 ft. of tubing length.

9. Make sure that the valves are properly opened. Be careful not

to open them more than required as this may damage the
thread.

10. Replace the service port cap. Using refrigerant oil, lubricate

the cap beam and hand tighten until resistance is met. Use a
suitable wrench to tighten the cap by an additional 1/2 turn.

Power Supply

  — See Tables 4 and 5 for electrical data and

Fig. 13-14 for system wiring diagrams.

Leak Test

 — Leak test all fittings with appropriate test equipment.

OFF   ON

TIMER

IR RECEIVER

FILTER

PLASTIC CONTROL

COVER

SERVICE LED

Operation push button for
automatic operation (23

°

C/73

°

F),

turning the a/c OFF, canceling
the malfunction indication,
and resetting the filter LED.

Fig. 12A — Indoor unit LED’s and Wiring

INDOOR UNIT BCC/BCQ018, 024

Содержание BCC018

Страница 1: ...al Data System Requirements IMPORTANT The Indoor units the inter units cable voltage is 30 VDC IMPORTANT Each refrigerant line must be insulated Separately See line sizing requirements in tabel 2 Cons...

Страница 2: ...IAGRAM Mounting Bracket 2 X 1 Long Screws 2 X 8 Outdoor Sensor Connecting Cable 2 X 1 Available for HEAT PUMP ONLY Absorption Cushions 4 Electric Terminals 2 X 8 2 X Remote Controller 1 Mounting Mount...

Страница 3: ...NQ012 COOLING CAPACITY Btuh 2 X 9 000 2 X 11 400 SEER 13 0 13 0 HEATING CAPACITY Btuh 17 200 23 600 HSPF 7 7 7 7 SYSTEM CHARGE Ib 2 X 2 4 2 X 3 1 MOISTURE REMOVAL pt hr 2 X 2 6 2 X 4 5 AIRFLOW 3 Speed...

Страница 4: ...nch mm FRONT VIEW RIGHT SIDE VIEW BOTTOM VIEW LEFT SIDE VIEW TOP VIEW A C B 20 06 2006 GAD L EITANC NEW 815 260 185 635 230 40 12 7 6 35 27 50 32 08 10 23 7 28 25 9 06 1 57 1 2 1 4 1 06 1 96 815 260 1...

Страница 5: ...R EITANC SUPERSEDES NEW 38BCC BCQ 018 024 101 CONDENSING UNITS REV TOP VIEW AIR DISCHARGE AIR IN VIEW MINIMUM CLEARANCES SEE NOTE 1 MOUTING SLOT FIELD POWER CONNECTION CONTROL CONNECTION UNDER THIS CO...

Страница 6: ...four long screws to attach the mounting bracket to the wall 5 Check that the bracket is leveled and securely fastened to the wall DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER UNIT CONNECTIONS To m...

Страница 7: ...p the cables back 1 4 inch 2 Remove the unit s front panel by lifting the lower part and pulling it gently outward and upward See Fig 6 3 Remove the two screws from the control box cover and take off...

Страница 8: ...all the connections are made Bend tubing with special bending tools to avoid the forma tion of sharp bends Take care to avoid kinks or flattening of the tubing Keep the tubing free of dirt sand moist...

Страница 9: ...ns to eliminate contamination and moisture 3 Disconnect the vacuum pump Unit should maintain 500 microns for 5 minutes 4 Remove the service port caps from the mixed phase valve and suction line valve...

Страница 10: ...both sections NOTE Specifications and performance data are subject to change without notice Table 5 Electrical Data Outdoor Units 115 1 60 UNIT VOLTAGE MCA MOCP FULL LOAD FAN MOTOR COMPRESSOR COMPRES...

Страница 11: ...D O O R U N I T TH2 WH YEL GREEN RED J12 J6 J7 J8 FAN RVS COMP J18 K6 K5 K1 K2 STEPPER MOTOR K8 K9 K7 J11 J14 BLK RED 1 3 12V 12V BLK WH RED GREEN BLDC MOTOR J1 J5 1 3 J3 J4 TH1 TAC 670 control TAC 6...

Страница 12: ...YEL 2 3 4 6 5 TB H L T V 1 OR GND BLK I N D O O R U N I T TH2 WH GREEN RED J12 J6 J7 J8 FAN RVS COMP J18 K6 K5 K1 K2 STEPPER MOTOR K8 K9 K7 J11 J14 BLK RED 1 3 12V 12V BLK WH RED GREEN BLDC MOTOR J1 J...

Страница 13: ...rt and debris from drain holes in base of unit Fan motors are waterproof WARNING Indoor Units To avoid the possibility of electric shock before performing any cleaning and maintenance operations alway...

Страница 14: ...harge Check thermistors TH1 and TH2 for correct resistance Check system pressures 4 Flashes High Pressure Check refrigerant charge Check thermistors TH1 and TH2 for correct resistance Check operating...

Страница 15: ...41 0 5 1 8 1 0 10 40 10 80 11 21 42 8 6 1 8 1 0 9 986 10 370 10 76 44 6 7 1 8 1 0 9 595 9 960 10 33 46 4 8 1 8 1 0 9 222 9 569 9 921 48 2 9 1 8 1 0 8 866 9 196 9 530 50 0 10 1 8 1 0 8 526 8 840 9 157...

Страница 16: ...2 055 2 137 2 220 123 8 51 2 3 1 3 1 990 2 070 2 151 125 6 52 2 3 1 3 1 928 2 006 2 085 127 4 53 2 3 1 3 1 867 1 943 2 021 129 2 54 2 3 1 3 1 809 1 883 1 959 131 0 55 2 5 1 4 1 753 1 826 1 900 132 8...

Страница 17: ...oor fan motor In Heat mode Delayed start for indoor fan motor Normal software delay maximum of 20 sec Clogged air filters Clean filters Lack of refrigerant Ice formation on the evaporator coil Unit mu...

Отзывы: