Carrier AutoZone 50HTQ Скачать руководство пользователя страница 2

2

Job Data:

Location:

Buyer:

Buyer P.O.#:

Carrier:

Unit Number:

Model Number:

Unit Designation:
Performance Data Certified By:

®

Certified to ISO

Use of the AHRI Certified
TM Mark indicates a
manufacturer’s  
participation in the 
program For verification 
of certification for individual 
products, go to 
www.ahridirectory.org.

9001:2008

DESCRIPTION

50HTQ units are one--piece, high--efficiency heat pump

units, with a low profile, prewired, tested and charged at the

factory. These units have field convertible supply and return

openings and are intended for installation on a roof curb

accessory (ordered separately), or for slab mounting (for

horizontal duct connections). Units are designed to accept

field--installed electric heaters. Units may be ordered with

various factory--installed options. Field--installed accessories

are also available.

STANDARD FEATURES

Base Unit

S

Puron (R--410A) HFC refrigerant

S

AHRI certified

S

EER efficiency level: 11.1

S

Rated in accordance with AHRI Standards 340/360

S

Designed in accordance with Underwriters’
Laboratories Std 1995 and listed by UL and UL, Canada

S

Non--corrosive composite sloping design; side or center
drain condensate pan. Meets ASHRAE Standard 62

S

Cooling operating range from 25

_

F up to 115

_

F

(--4

_

C up to 46

_

C). Field installed accessory extends

the minimum down to --20

_

F (--29

_

C).

S

Convertible from vertical to horizontal airflow for slab
mounting

S

Return air filters are two--inch metal frames with
pleated media

S

Single point electric connections on field--installed
electric heat units

S

24--volt control circuit protected with resettable circuit
breaker and 75--VA transformer

S

Belt drive, constant torque, permanently lubricated
evaporator--fan motor on all size units.

S

Totally enclosed condenser motors with permanently
lubricated bearings

S

Centralized Terminal Board for component and unit
wiring connections.

S

Loss of Charge, High--Pressure, and Freeze Protection
switches

S

Full perimeter base rail with built--in rigging adapters
and fork truck slots.

S

Surveyor controller and associated sensors

S

Power and control wiring through the base Meyer hubs
and compressor relay

Cabinet

S

Access panels with easy grip handles and replaceable
NO--STRIP screw collar

S

Pre--painted exterior panels and primer--coated interior
panels tested to 500 hours salt spray protection

S

Fully insulated cabinet

S

Tool--less filter access door

S

Hinged panel access for the control panel and
evaporator blower motor.

Refrigerant System

S

Acutrol

t

refrigerant metering system

S

Liquid line filter drier

S

Scroll compressors with internal line--break overload
protection

S

Indoor and outdoor coils constructed of aluminum fins
mechanically bonded to seamless copper tubes.

S

Removable gauge line plugs for reading refrigerant
pressure with unit panels in place

S

Four--way reversing valve operation

S

Suction Line Accumulator standard -- prevents
excessive liquid flood back of refrigerant to the
compressor even during the start of the defrost cycle.

Standard Warranty

S

5--year electric heater (field--installed)

S

5--year compressor

S

1--year parts

50H

TQ

Содержание AutoZone 50HTQ

Страница 1: ...FORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Copyright 2010 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50HTQ 01SB Replaces NEW ...

Страница 2: ...ted media S Single point electric connections on field installed electric heat units S 24 volt control circuit protected with resettable circuit breaker and 75 VA transformer S Belt drive constant torque permanently lubricated evaporator fan motor on all size units S Totally enclosed condenser motors with permanently lubricated bearings S Centralized Terminal Board for component and unit wiring co...

Страница 3: ...ht lb Heating Power Input to Unit kw Integrated Capacity Btuh Indoor Operating Air Temperature _F db Outdoor Air Temperature _F Winter Design Rating at 70 R H Outdoors kW Heater Selected Heat Cool Ratio Electrical Capacity Required Btuh COP HSPF High Low ELECTRICAL DATA Power Supply to Unit Volts Phase Hz Minimum Circuit Amps Maximum Overcurrent Protection Fuse Only SUBMITTAL DATA Job Name Archite...

Страница 4: ...rice pages for further information FIELD INSTALLED ACCESSORIES j EconoMi er IV with controls and barometric relief vertical or horizontal j EconoMi er2 with 4 20 mA actuator barometric relief and no microprocessor vertical or horizontal j Power Exhaust vertical or horizontal j PremierLink CCN controller j Electric heat j Single point kit j Manual outdoor air damper 25 j Manual outdoor air damper 5...

Страница 5: ...5 CERTIFIED DIMENSION 50HTQ 07 C10711 50HTQ ...

Страница 6: ...6 CERTIFIED DIMENSION 50HTQ 07 C10712 50HTQ ...

Страница 7: ...7 ROOF CURB DETAILS 50HTQ 07 ROOFCURB ACCESSORY CRRFCURB001A02 CRRFCURB002A02 1 2 356 2 0 610 UNIT SIZE C10713 50HTQ ...

Страница 8: ...8 50HTQ ...

Отзывы: