Sizes 2 and 3

NOTE : Carrier recommends not to exceed an air velocity of
4 m/s (125 l/s) per spigot.

Accessory 

retur

n air plenum

Accessory 

retur

n air plenum

Size 1

2 - FEATURES

2.1 - General

The Carrier 42EM Atmosphera is a range of fan coil units
designed for installation above false ceilings.

Three major aspects influenced the design of this product range:
-

Configuration flexibility

-

Low noise levels

-

Compact design

2.1.1 - Configuration flexibility

To best meet customer requirements, many models and confi-
gurations are available.

The Carrier 42EM Atmosphera comes in three sizes - 1, 2 and 3.
Sizes 2 and 3 are both available in four models and four motor
drive selections, suitable for air conditioning of rooms from
25 to 75 m

2

in size.

To ensure dimensional and location flexibility for the suction
and discharge spigots, two distinct separate product ranges are
available:
-

modular models

-

compact in-line models

Modular models

These models offer more duct connection flexibility, as they
not only allow connection spigots with a diameter of 200 mm
on the sides, but also easy reconfiguration on site.

The modular model consists of a non-ducted base unit, on
which a return air plenum (factory-assembled) can be installed.

Compact in-line models

These one-piece units are ducted in-line supply and return air
models (only 125 mm diameter fresh air ducts can be connected
on the sides).

Size 1

 

Sizes 2 and 3

2.1.2 - Low noise levels

In order to further enhance occupant comfort this product
range offers especially low noise levels.

The casing of the Carrier 42EM Atmosphera is made of
galvanised sheet steel with full high-efficiency internal lining
for optimised thermal and sound insulation of the unit.

In order to comply with the various local regulations (fire
class) the Carrier 42EM Atmosphera is available in two
insulation versions:
-

class M1 type insulation

-

class 0 insulation in accordance with BS 476, part 6 and 7.

The 42EM Atmosphera is also equipped with anti-vibration
mounts with a strong vibration absorption levels.

2.1.3 - Compact design

To allow installation in most false ceiling designs, the conden-
sate removal pan height in the 42EM Atmosphera is the same
for all sizes (1, 2 or 3) - 215 mm from the top of the unit.

In order to reduce the dimensions of the 42EM to the minimum,
the units are equipped with high-efficiency heat exchangers
with very high cooling capacity/treated air flow ratios.

Base unit 

Base unit 

Содержание Atmosphera 42EM A Series

Страница 1: ...42EM Ducted Fan Coil Unit Selection manual Supply Moduboot...

Страница 2: ...densate drain pan 19 4 5 Electric heater 19 4 6 Fan motor assembly 20 5 DIFFERENT ATMOSPHERA CONFIGURATIONS 21 6 CONTROL 22 6 1 Control with room thermostat only 23 7 TECHNICAL SPECIFICATIONS 24 7 1 V...

Страница 3: ...e absence of noise is a deciding factor for the comfort of the occupants The 42EM Atmosphera has been designed to be particularly quiet Low noise levels and easy maintenance are key factors influencin...

Страница 4: ...guration on site The modular model consists of a non ducted base unit on which a return air plenum factory assembled can be installed Compact in line models These one piece units are ducted in line su...

Страница 5: ...lar model with insulation class 0 in accordance with BS 476 part 6 and 7 and metal spigots C compact model with standard insulation D compact model with insulation class 0 in accordance with BS 476 pa...

Страница 6: ...uration filter removal is from the rear of the unit Filter 42EMxxA 42EMxxB There are two types of ducted units available the modular version base unit plus return air plenum sub assembly Filter 42EMxx...

Страница 7: ...2 0 02 ppm H2 S 0 02 ppm NO NO2 1 ppm NH3 6 ppm N2 O 0 25 ppm Recommended coil water quality At installation handover and then periodically every year it is advised to analyse the water for bacteria d...

Страница 8: ...4 pole asynchronous internal overload protection permanent capacitor class B winding insulation varnish class F Maximum absorbed power at 230 V W 119 110 128 182 229 Nominal current A 0 52 0 52 0 60 0...

Страница 9: ...ernal overload protection permanent capacitor class B winding insulation varnish class F Maximum absorbed power at 230 V W 110 128 182 229 Nominal current A 0 52 0 60 0 82 1 02 Starting current A 1 4...

Страница 10: ...ce required mm Sizes 1 2 and 3 Non ducted return air Sizes 1 2 and 3 Ducted return air B C A A C B A B C 42EM Size 1 220 850 250 42EM Size 2 220 1250 250 42EM Size 3 220 1250 250 A B C 42EM Size 1 50...

Страница 11: ...11 2 5 2 Overall dimensions mm Size 1 Non ducted return air Size 1 Ducted return air modular model 42EM10A 42EM10B 42EM10A 42EM10B...

Страница 12: ...12 2 5 Dimensional drawings cont Size 1 Ducted return air compact in line model 42EM10C 42EM10D...

Страница 13: ...cted return air modular model 2 5 2 Overall dimensions mm Size 2 Non ducted return air H 42EM Size 2 0 225 42EM Sizes 2 1 2 2 2 3 250 H 42EM Size 2 0 225 42EM Sizes 2 1 2 2 2 3 250 42EM2xA 42EM2xB 42E...

Страница 14: ...14 2 5 Dimensional drawings cont Size 2 Ducted return air compact in line model H 42EM Size 2 0 225 42EM Sizes 2 1 2 2 2 3 250 42EM2xC 42EM2xD...

Страница 15: ...imensions mm Size 3 Non ducted return air H 42EM Size 3 0 225 42EM Sizes 3 1 3 2 3 3 250 H 42EM Size 3 0 225 42EM Sizes 3 1 3 2 3 3 250 Left hand connections Left hand connections Right hand connectio...

Страница 16: ...16 2 5 Dimensional drawings cont Size 3 Ducted return air compact in line model H 42EM Size 3 0 225 42EM Sizes 3 1 3 2 3 3 250 Left hand connections Right hand connections 42EM3xC 42EM3xD...

Страница 17: ...circuit breaker If neces sary an easily operated emergency stop device such as a punch button switch must cut off the power to all equipment These safety devices shall be sized and installed in accor...

Страница 18: ...of the unit supply air flow rate at minimum speed NOTE To operate correctly the 30 m3 h or 8 3 l s constant fresh air flow controller requires a differential pressure in the range of 50 Pa to 200 Pa T...

Страница 19: ...pan insulation foam fire class M1 Condensate drain connection 16 mm external diameter 4 5 Electric heater Electric heater resistance wire type Supply voltage 230 V 1 ph 50 Hz Heater size and capacity...

Страница 20: ...nlet double wheel fans The fan motor has 6 speeds provided by a multi winding electric motor Three speeds must be selected to allow connec tion of the fan motor in accordance with the applicable elect...

Страница 21: ...Operates in cooling or heating mode heat pump type applications This option includes a 3 port on off valve a heating cooling changeover switch and two insulated flexible water pipes c The Atmosphera...

Страница 22: ...e factory On special request other types of controllers can be factory installed on the units supplied by Carrier Carrier room thermostat Other controls available on request from the factory 6 speed s...

Страница 23: ...y coil With this option the six fan motor speeds are available from this terminal This plug in quick connect terminal board is installed on a DIN rail In addition a fuse is also installed on this DIN...

Страница 24: ...alve Kvs 1 or 2 5 2 5 bar 3 way valve Kvs 1 1 5 bar Logic NF valve closed if no voltage 7 1 2 Two way valve body 11 5 26 5 1 2 17 56 6 5 28 M30 0x1 5 Travel 7 1 2 1 Features of the 1 2 two way valve 1...

Страница 25: ...echnical specification for the heating cooling changeover switch The heating cooling changeover switch is designed to be installed straight onto the couplings of the 3 way valves on the thermostat It...

Страница 26: ...temperature pro grammable and set point offset requested by the user 8 3 Wall mounted base for Zone User Interface Wall mounted base supplied without fixing screws as these vary depending on the type...

Страница 27: ...f the alarm threshold is reached or exceeded the condensate drain pump keeps running The alarm condition applies if the condensate level is above the alarm threshold The alarm condition no longer appl...

Страница 28: ...12 5 12 2 DE 268 211 161 384 302 231 491 387 297 591 466 360 684 538 418 725 571 444 769 605 471 7 13 TC 1 42 1 10 0 83 2 03 1 57 1 19 2 60 2 01 1 54 3 12 2 43 1 88 3 60 2 81 2 19 3 82 2 98 2 33 4 04...

Страница 29: ...1 Size 3 2 Size 3 3 Relative humidity 50 Water Air flow l s m3 h temp C 83 300 125 450 167 600 208 750 264 950 319 1150 347 1250 entering Dry bulb temperature at coil inlet C leaving 27 25 23 27 25 2...

Страница 30: ...1006 1040 1042 1079 1116 55 40 HC 2 34 2 46 2 58 3 39 3 57 3 74 4 39 4 61 4 83 5 29 5 56 5 83 6 44 6 77 7 11 7 50 7 89 8 28 8 01 8 43 8 85 TSA 43 9 44 0 44 1 43 1 43 2 43 3 42 4 42 4 42 4 41 7 41 7 4...

Страница 31: ...358 370 55 40 HC 1 06 1 11 1 16 1 45 1 51 1 58 1 79 1 87 1 95 2 09 2 18 2 27 2 45 2 56 2 67 2 77 2 90 3 02 3 93 3 06 3 19 TSA 31 4 30 9 30 3 30 4 29 8 29 2 29 7 29 1 28 4 29 2 28 5 27 8 28 6 27 9 27 2...

Страница 32: ...900 1000 2000 3000 100 1 10 100 1000 0 1 1000 10 9 3 Water coil pressure drops 9 3 1 Size 1 9 3 2 Size 2 9 3 3 Size 3 Pressure drop kPa Pressure drop kPa Pressure drop kPa Water flow l h Water flow l...

Страница 33: ...ter valve pressure drop KVs 1 Flow A AB Pressure drop kPa Pressure drop kPa KVs 1 Flow A AB KVs 0 63 Flow B AB Water flow l h Water flow l h 9 4 2 3 way 1 2 water valve pressure drop valve with integr...

Страница 34: ...25 15 14 19 8 36 4 RET 48 3 43 5 39 30 26 21 5 22 40 2 RAD 41 8 33 6 27 1 17 13 2 11 18 6 30 3 V5 SUP 42 5 38 31 3 21 9 11 8 11 7 19 33 4 RET 45 3 40 5 36 26 8 22 9 19 1 20 37 2 RAD 38 8 30 6 24 1 14...

Страница 35: ...RET 47 8 42 6 38 6 29 8 25 4 22 3 22 5 39 6 RAD 40 4 32 3 26 4 17 9 15 13 3 18 6 29 5 V5 SUP 42 37 31 3 22 1 14 2 13 4 18 6 33 RET 44 8 39 6 35 6 26 6 22 3 19 9 20 5 36 7 RAD 37 4 29 3 23 4 14 9 12 12...

Страница 36: ...6 13 4 9 6 7 6 3 4 42EM 2 1 3 1 1 3 6 9 13 9 4 6 4 8 42EM 2 2 3 2 1 1 2 7 5 4 9 13 2 8 8 6 1 4 42EM 2 3 3 3 0 4 1 1 2 6 7 4 10 7 6 8 4 1 2 5 9 5 4 Sound damper attenuation As a standard option a sound...

Страница 37: ...4 461 128 22 0 29 61 434 121 32 0 27 57 370 103 51 0 25 54 313 87 62 0 23 51 364 73 71 0 22 46 167 46 84 Legend I Current drawn by the fan motor P Power input to the fan motor Vn Fan motor speed Qv Ai...

Страница 38: ...1320 514 143 101 0 49 107 1337 440 122 110 V3 0 62 140 917 926 257 0 0 59 132 1010 849 236 20 0 53 120 1123 723 201 51 0 5 113 1181 649 180 66 0 47 105 1236 559 155 81 0 45 101 1262 493 137 91 0 43 9...

Страница 39: ...6 127 1384 522 145 111 Legend I Current drawn by the fan motor P Power input to the fan motor Vn Fan motor speed Qv Air flow rate Press Available static pressure NOTE To convert rpm to r s divide by 6...

Страница 40: ...boxes as a function of the number of spigots 200 mm Size 1 Air flow m3 h 100 200 300 400 450 500 550 600 650 700 Air flow l s 28 56 83 111 125 139 153 167 181 194 1 spigot SUP 1 4 9 15 19 24 RET 2 7...

Страница 41: ...1 unit without spigot 0 10 20 30 40 50 60 70 80 90 100 110 120 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 V1 V2 V3 V4 V5 V6 Air flow m3 h Available static pressure Pa IM...

Страница 42: ...num pressure drops Atmosphera size 2 2 and 3 2 unit without spigot 0 10 20 30 40 50 60 70 80 90 100 110 120 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100...

Страница 43: ...116 14 7 18 1 21 9 RET 0 0 2 0 7 1 7 3 0 4 6 6 7 9 1 11 9 15 0 18 6 22 5 4 spigots SUP 0 0 0 2 0 4 0 7 1 1 1 6 2 1 2 8 3 5 4 3 5 2 5 2 7 3 8 5 9 7 RET 0 0 1 0 3 0 8 1 4 2 1 3 0 4 1 5 4 6 8 8 5 10 2 1...

Страница 44: ...m3 h 272 l s for sizes 2 and 3 3 1170 m3 h 325 l s for sizes 2 and 3 7 Chassis and insulation type A Modular model with standard insulation B Modular model with insulation class 0 in accordance with B...

Страница 45: ...with 1 on off type three way control valve changeover switch cables wired to a terminal block and protected by a cover AS Unit with 1 on off type three way control valves with flexible water pipes ch...

Страница 46: ...valve electric heater relay cables wired to a terminal block and protected by a metal cover Character Codification Description 8 9 Control continued Terminal strip and metal cover QN Unit with 1 on o...

Страница 47: ...es PF Unit with manual speed selector 1 on off type two way control valve with flexible water pipes and electric heater control Character Codification Description 8 9 Control continued Manual speed se...

Страница 48: ...f type three way control valves with flexible water pipes and a return air sensor Character Codification Description 8 9 Control continued Maestro control CM Unit with Maestro controller 1 on off type...

Страница 49: ...0 1000 W Size 2 1 and 3 1 1000 W Size 2 2 and 3 2 2000 W Size 2 3 and 3 3 2000 W Y Other special coil Character Codification Description 11 Fresh air supply N Base unit without fresh air supply Right...

Страница 50: ...s 2 3 3 return air spigots 5 Sizes 2 3 Plenum with 5 return air spigots not available when the fresh air option is selected X Special plenum Character Codification Description 13 No of supply air spig...

Страница 51: ...1 Size 2 Codification RED wire Fan set GREY wire BLACK wire REP L wire 6 speed wiring Auto transformer terminal connection arrangements Q std NOTE Terminal 1 highest speed Terminal 6 lowest speed Cha...

Страница 52: ...ed with flexible water pipes with 1 2 BSP union nuts to simplify connections on site and maintenance and servicing work 42EM units supplied shall be provided with disposable 85 gravimetric EU3 or G3 a...

Отзывы: